![Trane RTAD 085 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/trane/rtad-085/rtad-085_installation-operation-and-maintenance_1149696061.webp)
RTAD-SVX01F-E4
61
Installation - Electrical
In many cases, the Trane user-
defined types contain standard
network
variable types (SNVTs) to make
them easy to understand.
User defined types
This appendix includes
❏
User-defined network variable
types
❏
User-defined configuration
property types
These user-defined types have been
created by Trane for use by Trane
controllers.
User-defined network variable types
(UNVTs)
UNVT_purge_information
Structure definition
Field in structure
Byte
Bit definition
Description
SNVT_state
Byte 0 (MSB)
Bits 0-7 (MSB)
Validity of bits 8-15 (1=Valid)
Bit 8
Refrigeration Circuit On (1)
Bit 9
Pumping Out (1)
Bit 10
Regenerating (1)
Bits 11-15(LSB)
Not Used
SNVT_time_f
Byte 1-2 (LSB)
UNVT_starts_runtime
Structure definition
Field in structure
Definition
SNVT_count_f Compressor
Starts
SNVT_time_f Compressor
Run
Time
SUNVT_3phase_current
Structure definition
Field in structure
Definition
SNVT_amp_ac
L1 Current (Amps)
SNVT_amp_ac
L2 Current (Amps)
SNVT_amp_ac
L3 Current (Amps)
SNVT_lev_percent
L1 Current (%RLA)
SNVT_lev_percent
L2 Current (%RLA)
SNVT_lev_percent
L3 Current (%RLA)
UNVT_3phase_volt
Structure definition
Field in structure
Definition
SNVT_volt_ac AB
Voltage
SNVT_volt_ac BC
Voltage
SNVT_volt_ac CA
Voltage
Purge 24 Hour
Pumpout Average