67
RT-PRC010-EN
Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0” H
2
O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0” H
2
O.
Cfm
Total Static Pressure
Std.
6.250
6.500
6.750
7.000
7.250
7.500
Air
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
31000
1434
48.20
1459
50.30
1484
52.52
1508
54.60
1532
56.79
1557
59.10
1579
61.23
32000
1442
49.55
1464
51.55
1489
53.77
1512
55.85
1538
58.33
1559
60.35
1584
62.78
33000
1451
51.09
1473
53.11
1496
55.23
1518
57.33
1541
59.53
1565
61.85
1589
64.28
34000
1461
52.70
1482
54.63
1506
56.90
1527
59.03
1550
61.26
1570
63.29
1594
65.73
35000
1471
54.27
1491
56.22
1515
58.53
1536
60.68
1558
62.93
1578
64.99
1601
67.45
36000
1482
55.91
1503
58.03
1523
60.10
1544
62.28
1566
64.55
1589
66.93
1609
69.11
37000
1494
57.77
1514
59.79
1534
61.91
1555
64.11
1576
66.42
1597
68.68
1618
71.04
38000
1505
59.46
1527
61.78
1547
63.94
1568
66.19
1586
68.24
1608
70.69
1627
72.92
39000
1518
61.37
1540
63.74
1560
65.94
1579
68.09
1598
70.33
1617
72.50
1638
74.92
40000
1533
63.50
1552
65.66
1572
67.90
1592
70.24
1610
72.37
1629
74.58
1649
77.03
41000
1547
65.62
1566
67.82
1585
69.97
1603
72.20
1624
74.68
1642
76.94
1661
79.28
42000
1561
67.70
1580
69.96
1598
72.15
1617
74.44
1635
76.65
1654
79.10
43000
1576
69.89
1593
72.06
1613
74.46
1630
76.64
1650
79.22
44000
1591
72.20
1609
74.43
1628
76.89
1645
79.12
45000
1607
74.63
1625
76.92
1643
79.30
46000
1624
77.20
1641
79.40
Notes:
1. Shaded areas indicate non-standard BHP or RPM selections. Contact your local Trane representive for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component
static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb).
3. Maximum static pressure leaving the rooftop is 4.0’’ H20 positive. The static pressure drops from the supply fan to the space cannot exceed 4.0’’ H20.
4. Maximum Cfm as follows: 105 Ton Std. — 44,000 Cfm, 105 Hi-Cap., 115, 130 Tons — 46,000 Cfm
5. Minimum motor horsepower is 30 hp.
6. See RT-EB-104 for further details.
Table PD-43 — Supply Fan Performance WITH INLET GUIDE VANES — 105,115,130 Tons (Cont.)
Figure PD-12 — Supply Fan Performance WITH INLET GUIDE VANES — 105,115,130 Tons
(105,115,130 Tons)
Performance
Data
0
10000
20000
30000
40000
50000
60000
0
1
2
3
4
5
6
7
8
9
4
0
%
W
O
C
F
M
5
0
%
W
O
C
F
M
6
0
%
W
O
C
F
M
90%
WO
CFM
80
%
W
O
CF
M
7
0
%
W
O
C
F
M
10
0
H
P
7
5
H
P
60
H
P
5
0
H
P
40
H
P
3
0
H
P
2
5
H
P
20
H
P
1600 RPM
1500 RPM
1400 RP
M
1300 RPM
1200 RPM
1100 RPM
1000 RPM
900 RPM
CFM