near the TXV bulb location to shut the
cooling off when coil frosting conditions
occur. The supply fans are not shut off
and will de-ice the coil. Timers prevent
the compressors from rapid cycling.

7

Occupied/Unoccupied Switching

a

Description — 3 ways to switch
Occupied/Unoccupied:

(1) NSB Panel

(2) Field-supplied contact closure
(hardwired binary input to RTM)

(3) TRACER

Night Setback Sensors

Trane’s night setback sensors are
programmable with a time clock function
that provides communication to the
rooftop unit through a 2-wire
communications link. The desired
transition times are programmed at the
night setback sensor and communicated
to the rooftop.

Night setback (unoccupied mode) is
operated through the time clock
provided in the sensors with night
setback. When the time clock switches to
night setback operation, the outdoor air
dampers close and heating/cooling can
be enabled or disabled depending on
set-up parameters. As the building load
changes, the night setback sensor
energizes the rooftop heating/cooling (if
enabled) function and the evaporator
fan. The rooftop unit will cycle through
the evening as heating/cooling (if
enabled) is required in the space. When
the time clock switches from night
setback to occupied mode, all heating/
cooling functions begin normal
operation.

When using the night setback options
with a VAV heating/cooling rooftop,
airflow must be maintained through the
rooftop unit. This can be accomplished
by electrically tying the VAV boxes to the
Unoccupied output relay contacts on the
Rooftop Module (RTM) or by using
changeover thermostats. Either of these
methods will assure adequate airflow
through the unit and satisfactory
temperature control of the building.

Occupied/Unoccupied input on the RTM

This input accepts a field supplied switch
or contacts closure such as a time clock.

Trane Tracer®  System

The Trane Tracer System can control the
Occupied/Unoccupied status of
the rooftop.

8

Timed Override Activation — ICS

This function is operational when the
RTM is the zone temperature sensor
source, which was set up at the Human
Interface Panel. When this function is
initiated by the push of a override button
on the ICS sensor, the Tracer will switch
the unit to the Occupied mode. Unit
operation (Occupied mode) during timed
override is terminated by a signal from
Tracer.

Timed Override Activation — Non-ICS

This function is active whenever the
RTM is selected as the Zone Temperature
Sensor source, which was set up at the
Human Interface Panel. When this
function is initiated by the push of an
override button on the zone sensor, the
unit will switch to the Occupied mode.
Automatic Cancellation of the Timed
Override Mode occurs after three hours
of operation.

9

Low Ambient Compressor Lockout

This function will lock out the
compressor if the outdoor air
temperature is below the low ambient
compressor lock out temperature set
point. The factory setpoint is 50 F on
standard units and 0 F on low ambient
units. This setpoint is adjustable at the
Human Interface Panel. Compressors
will be locked out when outdoor air
temperatures falls below that selected
temperature and will be allowed to start
again when the temperature rises 5 F
above the setpoint.

10

Comparative Enthalpy Control of
Economizer

An optional Comparative Enthalpy
system is used to control the operation
of the economizer, and measures the
temperature and humidity of both return

air and outside air to determine which
source has lower enthalpy. This system
allows true comparison of outdoor air
and return air enthalpy by measurement
of outdoor air and return air
temperatures and humidities.

Reference Enthalpy Control of
Economizer

The optional reference enthalpy
compares ambient temperature and
humidity to the economizer enthalpy
control setpoint. If ambient temperature
and humidity are below the economizer
enthalpy control setpoint the economizer
will operate freely. This system provides
more sophisticated control where
outdoor air humidity levels may not be
acceptable for building comfort and
indoor air quality.

Dry Bulb Temperature Control of
Economizer

The optional dry bulb system measures
ambient temperature comparing it to the
economizer control temperature
setpoint. If the ambient temperature is
below the economizer dry bulb
temperature control setpoint, the
economizer will operate freely. This
system is best suited for arid regions
where the humidity levels of fresh air
would not be detrimental to building
comfort and indoor air quality.

11

Compressor Lead/Lag

Compressor lead/lag is a user-selectable
feature through the Human Interface
Panel available on all units. After each
request for compressor operation, the
lead refrigeration circuit or compressor
on 20-30 tons units switches, thereby
causing a more equitable or balanced
run time among compressors.

12

Emergency Stop Input

A binary input is provided on the
Rooftop Module (RTM) for installation
of field provided switch or contacts for
immediate shutdown of all unit
functions.

(VAV/CV Units)

Controls

Содержание RT-PRC010-EN

Страница 1: ...Packaged Rooftop Air Conditioners IntelliPak Rooftops 20 130Tons 60 Hz RT PRC010 EN October 2001 20 75Tons 90 130Tons...

Страница 2: ...ws for stand alone operation of the unit Access to the unit controls via a Human Interface Panel provides a high degree of control superior monitoring capability and unmatched diagnostic information O...

Страница 3: ...efits Application Considerations Selection Procedure Model Number Description General Data Performance Data Performance Adjustment Factors Controls Electric Power Dimension andWeights Mechanical Speci...

Страница 4: ...er control options comparative enthalpy reference enthalpy dry bulb control Variable frequency drive control of supply exhaust fan motor Inlet guide vanes on FC supply fans VAV only Outside air CFM co...

Страница 5: ...tresses of expansion and contraction Stainless steel provides corrosion resistance through the entire material thickness Integral condenser subcooler improves efficiency while helping avoid liquid fla...

Страница 6: ...utomation and controls isTrane s Trane s andTrane s The IntelliPak rooftop as a part of an Integrated Comfort system provides powerful maintenance monitoring control and reporting capabilities The Tra...

Страница 7: ...rooftop air conditioner The efficiency is achieved with a 100 percent modulating exhaust system with two forward curved fans with modulating discharge dampers that operate only when needed compared t...

Страница 8: ...tanding feature of the 3 D Scroll compressor is that slugging will not cause failure In a reciprocating compressor however the liquid or dirt can cause serious damage LowT orqueVariation The 3 D Scrol...

Страница 9: ...l the building pressure to within the adjustable specified dead band that is set at the Human Interface Panel Advantages of the Statitrac 100 percent modulating exhaust system are a The exhaust fan ru...

Страница 10: ...signal that varies with the position of the economizer dampers When the exhaust fans start the modulating discharge dampers are fully closed and exhaust airflow is 15 to 20 percent of total exhaust c...

Страница 11: ...arge and return openings The supply and return air is routed through the curb to horizontal openings on the sides of the curb The second method available for horizontal supply and return applies to 20...

Страница 12: ...G Rooftops 90 to 130 tons The SXHG SLHG SSHG rooftops can be field modified to supply and return air horizontally without the use of a horizontal supply return curb To supply air horizontally use Pane...

Страница 13: ...ntelliPak Rooftops Ventilation Override Sequences One of the benefits of using an exhaust fan rather than a return fan in addition to the benefits of lower energy usage and improved building pressuriz...

Страница 14: ...t fittings Trane s Engineering Bulletin RT EB 80 describes various duct installation considerations specifically addressing indoor sound level concerns This bulletin includes sound power data on Trane...

Страница 15: ...essure to static pressure However when job conditions dictate elbows be installed near the rooftop outlet the loss of capacity and static pressure may be reduced through the use of guide vanes and pro...

Страница 16: ...aporator RADB OA OADB RADB 80 0 10 95 80 80 1 5 81 5 F Approximate wet bulb mixture temperature RAWB OA OAWB RAWB 65 0 10 76 65 65 1 1 66 1 F Step 3 Determine Supply Fan Motor Heat Gain Having selecte...

Страница 17: ...isfy the winter heating load of 563 MBh Table PD 28 shows an air temperature rise of 30 6 F for 17 500 cfm through the 170 kw heat module Unit supply temperature at design heating conditions mixed air...

Страница 18: ...ive selection number 6 600 rpm Where altitudes are significantly above sea level useTables PAF 2 and PAF 3 and Figure PAF 1 for applicable correction factors UNIT ELECTRICAL REQUIREMENTS Selection pro...

Страница 19: ...3 bhp actual Compressor MBh SHR and kw should be calculated at standard and then converted to actual using the correction factors inTable PAF 2 Apply these factors to the capacities selected at standa...

Страница 20: ...FILTER A Throwaway B Cleanable Wire Mesh C High Efficiency Throwaway D Bag With Prefilter E Cartridge With Prefilter F Throwaway Filter Rack Less Filter Media G Bag Filter Rack Less Filter Media DIGI...

Страница 21: ...1 50 6 2 0 7 2 5 Low Heat Coil C 1 0 D 1 25 E 1 50 F 2 0 G 2 5 DIGIT 10 DESIGN SEQUENCE A First Factory Assigned Note Sequence may be any letter A thru Z or any digit 1 thru 9 DIGIT 11 EXHAUST OPTION...

Страница 22: ...2 Enhanced 1 2 Enhanced 1 2 Enhanced Evaporator Coil High Capacity Size Ft2 20 3 20 3 24 4 32 5 Rows Fin Series 4 148 4 148 4 148 4 148 Tube Diameter Surface 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced 1 2...

Страница 23: ...x24x2 Face Area Ft2 20 0 20 0 28 0 34 0 Standard Unit Minimum Outside AirTemperature For Mechanical Cooling Without Hot Gas Option 55 F 50 F 50 F 55 F With Hot Gas Option 55 F 50 F 50 F 55 F Low Ambie...

Страница 24: ...180 4 148 Tube Diameter Surface 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced Evaporator Coil High Capacity Size Ft2 37 9 37 9 43 1 43 1 Rows Fin Series 4 148 4 148 4 148 NA 5 148 T...

Страница 25: ...4x2 8 24x24x2 8 24x24x2 Face Area Ft2 42 0 42 0 44 0 44 0 44 0 Standard Unit Min Outside AirTemperature For Mechanical Cooling Without Hot Gas Option 35 F 40 F 30 F 45 F 45 F With Hot Gas Option 35 F...

Страница 26: ...122 0 x 71 25 122 0 x 71 25 Size Ft2 59 3 59 3 59 3 59 3 Rows Fin Series 3 148 3 180 5 148 5 148 Tube Diameter Surface 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced 1 2 Enhanced Evaporator Coil High Capacit...

Страница 27: ...nameplate rating of the unit Table GD 4 ARI Performance Data 1 ARI Performance Data1 Capacity Tons Model3 MBh EER IPLV2 SAHFC2040A A A 220 9 5 12 8 SXHFC2040A A A 220 9 5 12 8 20 SFHFC204LA A A 220 9...

Страница 28: ...0 98 0 97 0 96 0 95 0 94 KW Correction Multiplier Compressors 1 00 1 01 1 02 1 03 1 04 1 05 1 06 1 07 SHR Correction Multiplier 1 00 98 95 93 91 89 87 85 Maximum Condenser Ambient 115 F 114 F 113 F 11...

Страница 29: ...259 260 259 280 198 248 248 248 248 266 193 90 294 294 294 294 308 254 284 284 284 284 296 249 273 273 273 273 283 244 261 261 261 261 269 239 Notes 1 All capacities shown are gross and have not cons...

Страница 30: ...8 308 326 326 326 326 332 302 Notes 1 All capacities shown are gross and have not considered indoor fan heat 2 CAP Total gross cooling capacity 3 SHC Sensible heat capacity Table PD 3 25Ton Gross Cool...

Страница 31: ...Notes 1 All capacities shown are gross and have not considered indoor fan heat 2 CAP Total gross cooling capacity 3 SHC Sensible heat capacity Table PD 5 30Ton Gross Cooling Capacity STANDARD CAPACITY...

Страница 32: ...487 487 487 508 428 467 467 467 467 483 419 Table PD 8 40Ton Gross Cooling Capacity HIGH CAPACITY Evaporator CoilWith Scroll Compressor AmbientTemperature 85 95 105 115 ENT EnteringWet Bulb DB 61 67 7...

Страница 33: ...645 645 645 645 658 600 Notes 1 All capacities shown are gross and have not considered indoor fan heat 2 CAP Total gross cooling capacity 3 SHC Sensible heat capacity Table PD 9 50Ton Gross Cooling Ca...

Страница 34: ...87 787 786 786 814 695 Notes 1 All capacities shown are gross and have not considered indoor fan heat 2 CAP Total gross cooling capacity 3 SHC Sensible heat capacity Table PD 11 55Ton Gross Cooling Ca...

Страница 35: ...55 706 706 706 706 733 641 Table PD 14 60Ton Gross Cooling Capacity HIGH CAPACITY Evaporator CoilWith Scroll Compressor AmbientTemperature 85 95 105 115 ENT EnteringWet Bulb DB 61 67 73 61 67 73 61 67...

Страница 36: ...8 848 722 927 572 772 772 806 701 881 551 736 736 763 678 832 529 90 887 887 904 866 976 710 852 852 864 845 932 689 816 816 816 816 886 668 779 779 778 778 839 646 75 809 682 889 520 980 353 771 660...

Страница 37: ...e gross and have not considered indoor fan heat 2 CAP Total Gross Cooling Capacity 3 SHC Sensible Heat Capacity Table PD 16 75Ton Gross Cooling Capacity STANDARD CAPACITY Evaporator Coil AmbientTemper...

Страница 38: ...1324 1324 1324 1355 1222 1271 1271 1271 1271 1295 1196 1215 1215 1215 1215 1233 1169 Notes 1 All capacities shown are gross and have not considered indoor fan heat 2 CAP Total Gross Cooling Capacity 3...

Страница 39: ...1325 739 1121 1121 1153 1016 1251 710 85 1364 1364 1376 1363 1472 1041 1309 1309 1308 1308 1404 1012 1251 1251 1250 1250 1333 982 1189 1189 1189 1189 1260 951 90 1439 1439 1439 1439 1490 1289 1381 13...

Страница 40: ...ave not considered indoor fan heat 2 CAP Total Gross Cooling Capacity 3 SHC Sensible Heat Capacity Table PD 22 115Ton Gross Cooling CapacityWith 5 Row I F Evaporator Coil 100 Load AmbientTemperature 8...

Страница 41: ...tandard AirVolume Cfm Module 5000 7500 10000 12500 Low Heat 1 06 1 33 1 52 1 74 High Heat 2 20 2 85 3 31 3 65 50 Nominal Ton Unit Steam Unit Standard AirVolume Cfm Module 10000 15000 20000 25000 Low H...

Страница 42: ...14000 16000 18000 20000 22000 24000 26000 30 102 4 23 6 15 7 11 8 9 4 7 9 6 7 5 9 5 2 4 7 4 3 3 9 3 6 50 170 6 39 3 26 2 19 7 15 7 13 1 11 2 9 8 8 7 7 9 7 1 6 6 6 0 70 238 8 55 0 36 7 27 5 22 0 18 3...

Страница 43: ...ule Gpm PD Ft 12000 16000 20000 24000 28000 31500 Low 25 0 98 4 28 4 82 5 20 5 48 5 69 5 83 High 30 1 22 5 24 5 91 6 40 6 77 7 06 7 27 Low 50 2 48 4 90 5 63 6 18 6 60 6 92 7 15 High 60 3 33 6 01 6 94...

Страница 44: ...0 1 60 609 2 13 685 2 63 757 3 17 829 3 77 895 4 36 957 4 97 1015 5 59 10000 556 2 05 641 2 65 715 3 22 780 3 78 845 4 39 910 5 05 971 5 71 1028 6 38 11000 593 2 58 675 3 25 745 3 89 809 4 51 867 5 13...

Страница 45: ...00 12000 14000 16000 18000 20000 CFM STATIC PRESSURE Inches w c 40 wocfm 50 60 S_HFC20 25 Ton Dual 15 X 15 Fans Entrance Losses w ithout Inlet Guide Vanes w ithout Evap Coil w ithout Filters w ithout...

Страница 46: ...12 94 11000 1136 8 54 1181 9 24 1225 9 97 1271 10 75 1318 11 58 1364 12 45 1409 13 33 1452 14 21 Cfm Total Static Pressure Std 4 250 4 500 4 750 5 000 5 250 5 500 5 750 6 000 Air RPM BHP RPM BHP RPM...

Страница 47: ...0 14000 16000 18000 20000 CFM STATIC PRESSURE Inches w c 50 60 70 40 wocfm 90 20 HP 1500 RPM 15 HP 1400 RPM 1300 RPM 7 5 HP 10 HP 1200 RPM 5 HP 1100 RPM 1000 RPM 3 HP 900 RPM 800 RPM 700 RPM 600 RPM 5...

Страница 48: ...9 22 1037 10 15 1078 11 11 1118 12 08 1156 13 07 1193 14 07 12000 903 7 99 951 8 94 996 9 90 1039 10 88 1080 11 88 1120 12 89 1158 13 93 1195 14 98 13000 904 8 61 952 9 60 998 10 61 1041 11 63 1083 12...

Страница 49: ...0 7 5 8 0 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 CFM STATIC PRESSURE Inches w c 1400 RPM 800 RPM 900 RPM 1000 RPM 1100 RPM 1200 RPM 1300 RPM 600 RPM 700 RPM 500 RPM S_HFC30 Dual 18...

Страница 50: ...208 13 52 11000 913 7 44 961 8 19 1007 8 97 1051 9 83 1094 10 78 1135 11 81 1174 12 90 1212 14 03 12000 916 8 26 964 9 09 1009 9 90 1053 10 71 1095 11 57 1136 12 49 1175 13 50 1213 14 58 13000 920 8 9...

Страница 51: ...0 7 5 8 0 0 4000 8000 12000 16000 20000 CFM STATIC PRESSURE Inches w c 25 HP 3 HP 5 HP 7 5 HP 10 HP 15 HP 20 HP S_HFC30 Dual 18 X 18 Fans Entrance Losses w ith Inlet Guide Vanes w ithout Evap Coil w i...

Страница 52: ...73 892 8 69 927 9 67 961 10 66 993 11 67 1023 12 69 1053 13 71 9000 819 7 32 861 8 28 901 9 27 938 10 31 972 11 37 1006 12 45 1037 13 55 1068 14 67 10000 822 7 88 865 8 89 906 9 92 944 10 98 980 12 07...

Страница 53: ...0 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000 CFM STATIC PRESSURE Inches w c 40 HP 7 5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 1200 RPM 600 RPM 700 RPM 800 RPM 900 RPM 1000 RPM 1100 RPM 500 R...

Страница 54: ...0 823 7 50 865 8 50 904 9 52 942 10 58 977 11 65 1010 12 74 1042 13 85 1073 14 97 10000 827 8 02 870 9 08 910 10 16 948 11 26 985 12 39 1019 13 55 1052 14 73 1084 15 92 11000 830 8 56 873 9 67 914 10...

Страница 55: ...000 18000 20000 22000 24000 26000 28000 30000 CFM STATIC PRESSURE Inches w c 40 wocfm 50 60 70 1200 RPM 500 RPM 600 RPM 700 RPM 800 RPM 900 RPM 1000 RPM 1100 RPM 5 HP 7 5 HP 10 HP 15 HP 20 HP 25 HP 30...

Страница 56: ...762 16 37 801 18 17 838 20 06 871 22 03 903 24 03 933 26 06 962 28 10 990 30 15 24000 764 17 14 803 18 96 840 20 86 875 22 84 907 24 89 938 26 98 967 29 09 995 31 22 25000 765 17 94 805 19 82 842 21...

Страница 57: ...8 0 0 3000 6000 9000 12000 15000 18000 21000 24000 27000 30000 33000 36000 CFM STATIC PRESSURE Inches w c S_HFC60 C70 C75 Dual 22 X 22 Fans Entrance Losses w ithout Inlet Guide Vanes w ithout Evap Co...

Страница 58: ...940 25 74 968 27 60 995 29 46 23000 780 17 11 816 18 94 851 20 89 884 22 89 916 24 90 946 26 87 974 28 82 1002 30 77 24000 785 18 00 821 19 81 855 21 74 889 23 78 921 25 87 951 27 96 980 30 03 1008 3...

Страница 59: ...0 3000 6000 9000 12000 15000 18000 21000 24000 27000 30000 33000 36000 CFM STATIC PRESSURE Inches w c S_HFC60 C70 C75 Dual 22 X 22 Fans Entrance Losses w ith Inlet Guide Vane w ithout Evap Coil w itho...

Страница 60: ...35000 1062 21 64 1087 23 18 1112 24 78 1137 26 48 1162 28 28 1186 30 12 1208 31 73 1230 33 43 36000 1080 22 76 1105 24 31 1128 25 91 1152 27 60 1177 29 38 1200 31 19 1224 33 06 1246 34 83 37000 1097...

Страница 61: ...83 1592 68 92 40000 1487 58 15 1507 60 24 1528 62 42 1546 64 40 1566 66 63 1584 68 66 1603 70 93 41000 1500 59 94 1519 62 08 1538 64 16 1558 66 32 1576 68 43 1595 70 62 1615 72 92 42000 1512 61 69 153...

Страница 62: ...000 1104 24 55 1130 26 28 1154 27 95 1178 29 68 1202 31 41 1225 33 14 1248 34 90 1270 36 71 36000 1122 25 82 1148 27 58 1172 29 32 1195 31 07 1219 32 87 1241 34 59 1264 36 42 1286 38 21 37000 1141 27...

Страница 63: ...67 90 1592 70 24 1610 72 37 1629 74 58 1649 77 03 41000 1547 65 62 1566 67 82 1585 69 97 1603 72 20 1624 74 68 1642 76 94 1661 79 28 42000 1561 67 70 1580 69 96 1598 72 15 1617 74 44 1635 76 65 1654 7...

Страница 64: ...46 1145 27 10 1169 28 78 1192 30 55 1215 32 39 1239 34 32 1261 36 21 38000 1115 25 02 1139 26 67 1163 28 37 1185 30 03 1208 31 78 1230 33 59 1254 35 56 1276 37 52 39000 1133 26 18 1157 27 94 1180 29...

Страница 65: ...70 21 1600 72 40 1619 74 67 1637 76 85 44000 1542 65 85 1559 67 89 1576 70 00 1594 72 18 1612 74 41 1631 76 72 1650 79 12 45000 1558 68 03 1575 70 14 1592 72 31 1610 74 56 1625 76 54 1643 78 91 46000...

Страница 66: ...0 1303 39 85 38000 1160 28 52 1184 30 31 1208 32 13 1231 34 03 1254 35 91 1276 37 76 1297 39 57 1319 41 49 39000 1179 29 94 1203 31 81 1226 33 64 1249 35 54 1272 37 50 1293 39 35 1315 41 30 1335 43 12...

Страница 67: ...1580 69 96 1598 72 15 1617 74 44 1635 76 65 1654 79 10 43000 1576 69 89 1593 72 06 1613 74 46 1630 76 64 1650 79 22 44000 1591 72 20 1609 74 43 1628 76 89 1645 79 12 45000 1607 74 63 1625 76 92 1643...

Страница 68: ...9 N A 50 53 51 63 36 62 21 21 10 23 20 10000 17 13 23 17 12 10 11 13 16 07 15 04 04 01 37 30 03 05 14000 29 22 39 29 26 20 22 22 28 15 28 07 07 03 56 50 07 08 50 55 17000 39 30 53 40 39 29 32 31 40 22...

Страница 69: ...9 1 12 44 43000 1 42 1 10 N A N A N A 45 30 57 66 53 71 N A 22 N A 1 22 1 30 54 46000 1 58 1 23 N A N A N A 55 34 65 75 61 79 N A 24 N A 64 Notes 1 Static pressure drops of accessory components must b...

Страница 70: ...00 7 800 8 900 9 1000 A 1200 C 800 8 900 9 1000 A 1100 B 1300 D 900 9 1000 A 1100 B 1200 C 500 5 700 7 800 8 900 9 1000 A 1000 A 40 600 6 800 8 900 9 1000 A 1100 B 1100 B 700 7 900 9 1000 A 1100 B 800...

Страница 71: ...12000 737 4 44 806 5 22 860 5 64 905 5 89 956 6 49 14000 837 6 67 7500 334 0 75 438 1 21 535 1 77 616 2 35 686 2 98 750 3 64 809 4 34 864 5 06 40 9000 362 1 09 449 1 57 536 2 16 618 2 84 689 3 52 753...

Страница 72: ...1000 A 1100 B 900 9 500 5 600 6 700 7 40 600 6 700 7 800 8 700 7 800 8 800 8 400 4 600 6 700 7 700 7 50 55 500 5 700 7 800 8 800 8 600 6 800 8 900 9 700 7 400 4 600 6 600 6 700 7 800 8 60 500 5 700 7...

Страница 73: ...5 794 5 01 11000 688 5 36 725 5 80 760 6 24 793 6 66 823 7 06 850 7 42 875 7 76 4000 271 0 29 364 0 54 438 0 82 499 1 07 550 1 30 601 1 56 651 1 87 6000 339 0 71 391 0 90 456 1 22 517 1 60 572 2 01 62...

Страница 74: ...RPM Drive No 500 5 700 7 20 600 6 800 8 700 7 900 9 800 8 500 5 700 7 25 600 6 800 8 700 7 900 9 800 8 600 6 800 8 30 700 7 900 9 800 8 1000 A 900 9 500 5 700 7 40 600 6 800 8 700 7 500 5 700 7 50 55...

Страница 75: ...ring unit start up and transition to from Occupied Unoccupied modes to prevent overpressurization of the supply air ductwork However if for any reason the supply air pressure exceeds the user defined...

Страница 76: ...cycle takes place followed by another attempt to ignite If ignition fails a second time the heating section will be shut down and locked out until manually reset at the unit mounted Human Interface Pa...

Страница 77: ...only is used to satisfy cooling requirements Outdoor air dampers may be set manually for a maximum of 25 percent outdoor air if rooftop is equipped with 0 to 25 percent manual fresh air damper A Heat...

Страница 78: ...sensor The signal is sent to the UCM and the stages are sequenced based on load demand HotWater or Steam Heating Upon a call for heat the UCM will send a varying voltage signal to the valve actuator...

Страница 79: ...arying capacity is used to raise the zone temperature to the MWU zone temperature setpoint This method of warm up is used to overcome the building sink effect Cycling capacity MWU will operate until M...

Страница 80: ...haust fan On exhaust dampers Open if equipped Exhaust fanVFD On 60 Hz if equipped Outside air dampers Open Heat all stages Off Modulating heat output at 0 vdc Occupied Unoccupied output Energized VO r...

Страница 81: ...ting the unit This menu is accessible only at the unit mounted Human Interface Panel 5 Generic BuildingAutomation System odule GBAS The Generic Building Automation System Module GBAS is used to provid...

Страница 82: ...cted as the ZoneTemperature Sensor source which was set up at the Human Interface Panel When this function is initiated by the push of an override button on the zone sensor the unit will switch to the...

Страница 83: ...or units using heaters equal to or greater than 50 kw MCA 1 25 x LOAD1 LOAD2 LOAD4 LOAD3 The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode MCA value calculat...

Страница 84: ...1 8 143 2 9 8 9 9 41 9 269 41 9 251 18 2 117 14 6 94 55 Std and Hi Cap 4 15 3 15 6 62 8 409 62 8 376 27 3 178 21 8 143 60 Std and Hi Cap 4 14 4 15 0 62 8 409 62 8 376 27 3 178 21 8 143 70 Std 2 15 6 6...

Страница 85: ...4 38 6 19 3 15 4 20 58 7 51 0 25 5 20 4 25 70 5 61 0 30 5 24 5 30 86 5 75 0 37 5 30 0 40 112 0 97 0 48 5 39 0 Table ED 3 20 130Tons Electrical Service Sizing Data Electric Heat Module Electric Heat Un...

Страница 86: ...21 2 14 01 4 12 6 7 0 6 615 16 4 95 16 3 43 8 5 7 0 113 4 7 91 2 40 6 73 8 27 0 7 61 2 7 25 8 6 15 8 0 97 8 1 57 8 1 101 8 2 5 2 5 16 713 16 15 111 8 8 0 7 83 16 5 95 16 3 43 8 5 7 0 113 4 7 91 2 50...

Страница 87: ...87 RT PRC010 EN DETAIL B COVERS 40 60 70 AND 75 TON UNITS DETAIL A COVERS 20 25 30 50 AND 55 TON UNITS Dimensional Data 20 75Tons Figure DD 1 20 75Ton Cooling Only Unit Dimensions SAHF Continued...

Страница 88: ...1 57 8 1 101 8 2 5 2 5 19 105 16 19 7 18 1111 16 15 111 8 8 0 7 83 16 5 95 16 3 43 8 5 7 0 513 16 7 91 2 20 6 20 3 20 1 19 6 50 55 5 87 8 32 101 2 7 61 2 6 41 8 5 31 8 0 91 2 1 35 8 1 79 16 2 5 2 5 19...

Страница 89: ...6 2 0 3 6 4 0 1 105 8 6 117 8 0 113 16 0 113 16 2 515 16 S HF 22 41 2 5 21 16 9 1115 16 9 25 16 22 41 8 9 2 19 5 10 17 16 7 1015 16 2 0 3 6 4 0 1 105 8 7 83 4 0 113 16 0 23 8 2 515 16 Note 1 The retur...

Страница 90: ...quired to open the access doors on the unit s supply fan evaporator filter and exhaust fan sections All hinged doors swing outward in a 180 degree arc 4 90 130 ton models have two outdoor air intakes...

Страница 91: ...91 RT PRC010 EN Figure DD 6 90 130Ton Roof Curb Dimensions Cross Section Thru Roof Curb and base pan Dimensional Data 90 130Tons SECTION B B...

Страница 92: ...ilable for use with all zone sensors to provide remote sensing capabilities SINGLE SETPOINT SENSORWITH SYSTEM FUNCTION LIGHTS BAYSENS021 PROGRAMMABLE NIGHT SETBACK SENSOR BAYSENS020 Dimensional Data F...

Страница 93: ...C CHANGEOVER SENSORWITH SYSTEM FUNCTION LIGHTS BAYSENS010 WITHOUT LED STATUS INDICATORS BAYSENS008 SINGLE SETPOINTWITHOUT LED STATUS INDICATORS BAYSENS006 Note 1 Remote sensors are available for use w...

Страница 94: ...e sensing capabilities REMOTE MINIMUM POSITION POTENTIOMETER CONTROL BAYSTAT023 TEMPERATURE SENSOR BAYSENS016 ZONETEMPERATURE SENSORW TIMED OVERRIDE BUTTON AND LOCAL SETPOINTADJUSTMENT BAYSENS014 1 ZO...

Страница 95: ...8770 9320 9480 9650 10120 9650 610 640 Kg 3833 3905 3978 4187 3978 4227 4300 4377 4590 4377 277 290 70 75Lb 8970 9150 9300 9780 9300 9860 10040 10160 10640 10160 610 640 Kg 4069 4150 4218 4436 4218 4...

Страница 96: ...he discharge dampers to control the building pressure to within the adjustable specified dead band that is set at the Human Interface Panel Filters No Filters two inch throwaway filter rack only compl...

Страница 97: ...t unit power with the control box door closed for safety Hot Gas Bypass Valves piping and controls are all included to allow operation at low airflow avoiding coil frosting and damage to compressor Wh...

Страница 98: ...available These sensors are used with CV units Programmable Night Setback Sensors electronic programmable sensors with auto or manual changeover with seven day programming Keyboard selection of heat c...

Страница 99: ...se shall be watertight with 14 gauge formed load bearing members formed recess and curb overhang Unit lifting lugs shall accept chains or cables for rigging Lifting lugs shall also serve as unit tiedo...

Страница 100: ...shall have two independent fan assemblies with double inlet air foil fan motor and fixed pitch sheave drive All fans shall be statically and dynamically balanced and tested in factory Supply fans shal...

Страница 101: ...on Two double inlet forward curved fans shall be mounted on a common shaft with fixed sheave drive All fans shall be dynamically balanced and tested in factory before being installed in unit Exhaust f...

Страница 102: ...rflow 400 CFM ton at 1 inch wg static pressure Ultra low leak economizer dampers option Standard low leak dampers shall be provided with chlorinated polyvinyl chloride gasketing added to the damper bl...

Страница 103: ...shall have built in thermal overload protection Gas Safety Controls shall include electronic flame safety controls to require proving of combustion air prior to ignition sequence which shall include a...

Страница 104: ...comfort trane com SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Literature Order Numbe...

Отзывы: