Page 35
Symptom
Cooling
Heating
Who can take
corrective action U
= User
S = specialised
personnel
Probable cause
Possible remedy
M
Frost in the
compressor intake
pipe
x
x
s
Expansion device that is not working
properly
Verify and replace.
x
x
s
Water circulation pump blocked
Unlock the pump.
x
x
s
Water circulation pump defective
Check the pump and replace if necessary.
x
x
s
Low refrigerant charge
See point G.
x
x
s
The liquid filter is clogged
Replace.
N
Abnormal noise
detected in the
system
x
x
s
Compressor noisy
Check and replace if necessary.
x
x
s
The panel vibrate
Fasten properly.
O
The defrosting
cycle is never
activated
x
s
4-way reversing valve defective
Check the power supply and the coil
of the valve and replace the valve.
x
s
The defrost thermostat is worn out or
has an incorrect calibration value
Check and replace if defective or
change the calibration value.
P
The unit does
not start
x
x
s
Phases of the supply network
reversed
Invert two phases.