Picco R32
Inverter air/water heat pumps with axial fan
43
PROBLEM
CAUSE
SOLUTION
Compressor does not start be-
cause of protective devices
Increase in discharge pressure
Low inlet pressure
Incorrect power supply
Incorrect wiring
Incorrect working conditions
Thermal protection intervention
Check
Damaged pressure switch
Repalce
High exhaust pressure
High outside air temperature
High water return temperature
Air in the hydraulic circuit
Refrigerant gas charge too high
Check
Poor air flow
Poor water flow rate
Check the fan and pump operation
Low exhaust pressure
High outdoor air temperature
Low plant return water temperature
Residual humidity in the cooling circuit
Air in the hydraulic circuit
Insufficient refrigerant gas charge
Check
High suction pressure
High outdoor air temperature
Low plant return water temperature
Expansion valve remains too opened / dam
-
aged
Check
Low compressor suction pressure
Low outdoor air temperature
Low plant return water temperature
Expansion valve remains too closed / clogged/
damaged
Dirty plate heat exchanger
Check
Low air flow rate
Low water flow rate
Check the fan and pump operation