Electrical control wiring
Electrical parameters
Standard model
Model
Frequency
(Hz)
Rated
voltage
(V)
Range of
voltage
(V)
Rated current
of fan motor
FLA
(A)
Rated current
of electric
heater
(optional)
FLA
(A)
Without electric heatier
With electric heater
Min. line
current
MCA
(A)
Min.
specification
for diameter
of copper core
wire
(mm
2
)
Min. line
current
MCA
(A)
Min.
specification
for diameter
of copper core
wire
(mm
2
)
MW(C)
D509
50
220~240 198~264
0.23 4.5
0.29
1.5 4.79
2.5
MW(C)
D512
0.27
6.4
0.34
1.5 6.74
2.5
MW(C)
D518
0.41
8.2
0.51
1.5 8.71
2.5
MW(C)
D524
0.57
12.7
0.71
1.5 13.41
2.5
Slim model
Model
Frequency
(Hz)
Rated
voltage
(V)
Range of
voltage
(V)
Rated current
of fan motor
FLA
(A)
Rated current
of electric
heater
(optional)
FLA
(A)
Without electric heatier
With electric heater
Min. line
current
MCA
(A)
Min.
specification
for diameter
of copper core
wire
(mm
2
)
Min. line
current
MCA
(A)
Min.
specification
for diameter
of copper core
wire
(mm
2
)
MW(C)
D507
MW(C)
D509
MW(C)
D510
50
220~240 198~264
0.26
4.5
0.33
1.5
4.76
2.5
MW(C)
D511
MW(C)
D512
0.28
6.4
0.35
1.5
6.68
2.5
MW(C)
D516
MW(C)
D518
0.39
8.2
0.49
1.5
8.59
2.5
22
AMS-SVX04A-EN