Plug the terminal of shielded communication line in corresponding place of the wired controller.
2.
To wired controller
Cover the front cover plate of the wired controller.
3.
DIP setting of the controller
DIP for model of indoor unit
DIP for address of indoor unit Shift selection of indoor fan
S1
S2
S3
S4
S5
S6
S7
S8
DIP for model of the indoor unit
If model of the indoor unit differs, the DIP setting of the control panel is different. There are 8 DIP
switches on the control panel of the indoor unit, of which S1, S2, S3 and S4 are for model, and their
settings are as shown in following table:
Model of indoor unit
S1
S2
S3
S4
MW(C)D507
0
0
0
0
MW(C)D509
0
0
1
0
MW(C)D510
0
0
1
1
MW(C)D511
0
1
0
0
MW(C)D512
0
1
0
1
MW(C)D516
1
0
0
1
MW(C)D518
1
0
1
1
MW(C)D524
1
1
1
0
Electrical control wiring
20
AMS-SVX04A-EN