Description of controller
System parameter query list
Press the Sleep button for 5s, the buzzer gives a sound, enter the query mode, the query address
is displayed in the temperature display area, the clock indicates the parameter, press
Đ
▲
đ
or
Đ
▼
đ
once, and the query address is switched once. If no operation is executed, quit the query mode
automatically.
Attached list: parameter query
Address code
Parameter enquired
Unit
00
Last fault code of system
01
Set address of indoor unit
02
Capacity of indoor unit
kW
03
Indoor unit coil inlet temperature (T2)
ņ
04
Indoor unit coil midpoint temperature (T3)
ņ
05
Indoor unit coil outlet temperature (T4)
ņ
06
Indoor return air temperature (T1)
ņ
07
Opening of indoor unit EXV
08
Capacity of outdoor unit
kW
09
Operating frequency of VF compressor
HZ
10
Opening of outdoor unit EXV
11
Operating current of VF compressor
A
12
Input voltage of outdoor unit
V
13
Input current of outdoor unit
A
14
VF compressor exhaust temperature (T9)
ņ
15
VF compressor suction temperature (T10)
ņ
16
Condenser inlet temperature (T6)
ņ
17
Condenser midpoint temperature (T7)
ņ
18
Outdoor ambient temperature (T5)
ņ
19
Temperature of VF module radiator
ņ
AMS-SVX04A-EN
25