Maintenance 

Symptoms 

Possible causes 

Checks 

Corrective action 

The system operates
for too long or
continuously. 

A. Control switch no longer responds to the

ambient temperature. 

1. Check operation and connections of

the control switch. 

1. Replace the control switch if it is defective. 

B. Loss of refrigerant fluid. 

1. Check there are no leaks in the system. 1. Repair and recharge.

C. Insufficient ventilation. 

1. Check the air circulation in the

condenser.

1. Make sure air circulation is satisfactory.

Move the outdoor unit if necessary.

D. Incorrectly adjusted control switch.

1. Check the set point.

1. Adjust or replace if defective.

System operates in
short cycles. 

A. Defective control switch 

1. Check operation of the control switch.  1. Replace if defective. 

B. Insufficient air circulation.

1. Check air circulation in the indoor and

outdoor units.

1. Clean the coil and filter if necessary.

C. Insufficient or excess refrigerant fluid. 

1. Check if there are leaks or excess

pressure. 

1. Repair if there are leaks. Add or remove

refrigerant fluid. 

D. Incorrect electric power supply. 

1. Check the electric power supply. 

1. Find cause and stabilise the power supply. 

Internal coil frozen. 

A. Insufficient refrigerant fluid. 

1. Check if there are leaks in the system.  1. Repair the leak and recharge.

B. Insufficient air circulation. 

1. Check the filter. 

1. Clean and put back in position. 

2. Check the fin block. 

2. Clean the fins. If the filter is missing, install

one.

3. Check the fan.

3. Fan free on the bearing, tighten the fixing

screws - connection fault, find the cause
and repair.

C. Defective anti-frost sensor.

1. Check the sensor.

1. Replace if necessary. 

Unit is noisy 

A. Defective installation. 

1. Check installation of the compressor

and motor. 

1. Tighten any loose components. 

2. Check the fan position. 

2. If the fan is rubbing against a part, re-align

it. 

3. Check for vibrations of piping and

crankcase. 

3. Find the cause and repair. 

4. Check positioning of unit concerning

noise and vibrations. 

4. Find the cause and repair. 

B. Motor bearings are worn. 

1. Check the motor. 

1. Replace the motor if necessary. 

C. Noisy compressor. 

1. Check if the compressor is losing oil. 

1. Locate the leak, repair and add oil. 

D. Excess refrigerant fluid or oil. 

1. Remove the excess charge.

Содержание MCD 048

Страница 1: ...Installation Operation Maintenance MCD MWD 512 518 524 530 536 048 060 Ductable ceiling suspended unit SS SVX07B E4...

Страница 2: ...f this condition is not respected the constructor warranty could be cancelled Do not release refrigerant into the atmosphere Foreword These Installation Operation and Maintenance instructions are give...

Страница 3: ...e t l i F 9 1 r e l l o r t n o c d e r i w e h t g n i l l a t s n I Operation 0 2 m u u c a v a g n i t a e r C 0 2 e g r a h c t n a r e g i r f e r l a n o i t i d d A 1 2 d e e p s n a F 1 2 n o...

Страница 4: ...lations Check that the electrical characteristics on the nameplate correspond to those of the national grid The electrical installation shall include a disconnect switch in compliance with local elect...

Страница 5: ...62 Length mm 420 755 755 855 855 Face Area m2 0 213 0 420 0 420 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 1 2 2 4 4 Fins per feet fpf 180 180 180 180 180 Outdoor Fan Type Axial Axial Axi...

Страница 6: ...h mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 4 4 6 6 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 2 2 Di...

Страница 7: ...Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 1...

Страница 8: ...2 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial Axial Number 1 2 2 Diameter mm...

Страница 9: ...ove Height mm 508 559 610 762 762 Length mm 420 755 855 855 855 Face Area m2 0 213 0 420 0 521 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 2 4 2 3 3 Fins per feet fpf 180 180 240 180 180 O...

Страница 10: ...Height mm 762 762 1219 1219 Length mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 2 2 4 4 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial A...

Страница 11: ...er Groove Height mm 508 559 559 762 Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type...

Страница 12: ...roove Inner Groove Height mm 762 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial...

Страница 13: ...MCD MWD 524 23 578 12 305 42 9 1090 36 1 920 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 530 23 578 12 305 48 3 1228 42 1 1069 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 536 23 578 12 305 48 3 1228 42 1 1069 6...

Страница 14: ...x 2 5 TTK TWK 048 4 x 2 5 TTK TWK 060 4 x 2 5 1 Indoor and outdoor units are powered separately 2 Number of wires and section area are given for a maximum wire length of 50m If the wire is longer tha...

Страница 15: ...the drilling of the holes in the walls to connect the unit Make sure the maximum distances between the two units are not exceeded See Figure 3 and Table 10 Figure 3 Recommended clearances and maximum...

Страница 16: ...vertical line and an additional trap must be positioned every 7 5 m of vertical elevation to allow oil return to the compressor There are no special technical recommendations for liquid lines because...

Страница 17: ...same way as for brazing of the indoor unit s lines Line insulation To prevent heat losses and condensation both liquid and gas lines must be thoroughly insulated Unscrew the Flare nuts which are place...

Страница 18: ...iring and earthing arrangements must comply with local legislation WARNING Never open the indoor or outdoor unit without first disconnecting the power supply There is a risk of electrocution CAUTION 1...

Страница 19: ...C Intake from the back Table 12 Duct connection dimensions Unit size Length mm Height mm 512 518 748 198 524 530 536 948 248 048 060 1148 298 Filtering Filtering the air is necessary to ensure the un...

Страница 20: ...the system has been vacuum pumped and is in operation and if the distance between the units is greater than 6m it may be necessary to add an additional charge Table 13 indicates the amounts of refrige...

Страница 21: ...d discharge ducts are not blocked 11 Check the filters are correctly positioned Show the user how to change the filters 12 Power up the system and observe operation carefully make any necessary adjust...

Страница 22: ...ton 4 Sleep button 5 Mode button 6 Sweep button to turn on off the sweep motor 7 Louver button 8 Timer start button 9 Send button to transmit all parameters shown on the LCD to the main control board...

Страница 23: ...they are not damaged Clean them if necessary and verify their alignment 3 Motor check the wiring and ensure the commutators are operating correctly Replace any damaged components 4 Disconnection of p...

Страница 24: ...perating but the fan does not start 1 Check the fan motor the capacitor or the wiring 1 Repair or replace D Control switch is defective incorrectly wired or adjusted 1 Check the control switch connect...

Страница 25: ...or remove refrigerant fluid D Incorrect electric power supply 1 Check the electric power supply 1 Find cause and stabilise the power supply Internal coil frozen A Insufficient refrigerant fluid 1 Chec...

Страница 26: ...he second digit of 7 segment LED indicates that the compressor is on if lit and indicates either the freeze or defrost protection is active if blinking Figure 14 LEDs blinking signals On board setting...

Страница 27: ...SS SVX07B E4 27 Notes...

Страница 28: ...manual is the result of many years of research and continuous development To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time th...

Отзывы: