background image

20

SS-SVX07B-E4

Operation

Creating a vacuum

For this operation, use a pump
capable of creating a vacuum of
1 mm Hg (1.3mbar) or less. To create
the vacuum you must connect the
pump to the Schrader pressure
connection on service valve
A located on the outdoor unit (gas
line). To use the vacuum pump,
follow the pump manufacturer's
instructions. Create a vacuum up to
2 mm Hg (2.6mbar) or less. Once the
value of 2mm Hg or less has been
reached, an increase in pressure will
be observed after a certain time. The
maximum permissible increase is
1 mm Hg after 15 minutes. If the
increase is greater and remains at a
constant value, this means there is
too much humidity in the system.
In this case, break the vacuum using
dry nitrogen and start the vacuum
creation procedure again.
A continuous increase in pressure
means there is a leak in the system.

WARNING!

Valves A and B must not be opened
before the installation of the
refrigerant circuit has been
completely finished, or the
refrigerant charge will be lost.

Figure 9 - Refrigerant circuit

1 = Outdoor unit
2 = Vacuum pump
3 = Indoor unit
4 = Gas line
5 = Liquid line
6 = TTK/TWK cooling mode

Additional refrigerant
charge 

Once the system has been vacuum
pumped and is in operation and if
the distance between the units is
greater than 6m, it may be
necessary to add an additional
charge. Table 13 indicates the
amounts of refrigerant to add per
additional meter of line. Once the
appropriate amount of refrigerant
has been added, fully open liquid
line valve and check the operating
pressure.

Figure 10 - Adding refrigerant charge

1 = Outdoor unit
2 = Gas line
3 = Indoor units
4 = Liquid line
5 = For sizes 512 to 524 
6 = For sizes 530 to 060

A

R22 Refrigerant

While the unit is operating, charge
the unit with gas through the service
Schraeder valve located at the
compressor suction. R22 refrigerant
can also be added in liquid phase in
the liquid line: see method used for
R407C. Never add liquid in the
suction line of the compressor.

R407C Refrigerant

WARNING!

add only R407C

refrigerant in liquid state. Never add
liquid in the suction line of the
compressor period. Use service
Schraeder valve located on the liquid
line to charge the unit. While the unit
is operating, close partially the
service valve in order to create a
lower pressure downstream the
service valve. Add the refrigerant
necessary. Control the added weight
with a scale.

Table 13 - Additional refrigerant charge

Liquid line 

Gas line 

Additional 

R22/R407C charge (g) 

1/4'' 1/2'' 

26 

5/16" 5/8" 

36 

3/8'' 5/8'' 

60 

3/8'' 3/4'' 

60 

3/8'' 7/8'' 

63 

3/8'' 1 

1/8'' 

68 

Содержание MCD 048

Страница 1: ...Installation Operation Maintenance MCD MWD 512 518 524 530 536 048 060 Ductable ceiling suspended unit SS SVX07B E4...

Страница 2: ...f this condition is not respected the constructor warranty could be cancelled Do not release refrigerant into the atmosphere Foreword These Installation Operation and Maintenance instructions are give...

Страница 3: ...e t l i F 9 1 r e l l o r t n o c d e r i w e h t g n i l l a t s n I Operation 0 2 m u u c a v a g n i t a e r C 0 2 e g r a h c t n a r e g i r f e r l a n o i t i d d A 1 2 d e e p s n a F 1 2 n o...

Страница 4: ...lations Check that the electrical characteristics on the nameplate correspond to those of the national grid The electrical installation shall include a disconnect switch in compliance with local elect...

Страница 5: ...62 Length mm 420 755 755 855 855 Face Area m2 0 213 0 420 0 420 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 1 2 2 4 4 Fins per feet fpf 180 180 180 180 180 Outdoor Fan Type Axial Axial Axi...

Страница 6: ...h mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 4 4 6 6 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 2 2 Di...

Страница 7: ...Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 1...

Страница 8: ...2 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial Axial Number 1 2 2 Diameter mm...

Страница 9: ...ove Height mm 508 559 610 762 762 Length mm 420 755 855 855 855 Face Area m2 0 213 0 420 0 521 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 2 4 2 3 3 Fins per feet fpf 180 180 240 180 180 O...

Страница 10: ...Height mm 762 762 1219 1219 Length mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 2 2 4 4 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial A...

Страница 11: ...er Groove Height mm 508 559 559 762 Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type...

Страница 12: ...roove Inner Groove Height mm 762 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial...

Страница 13: ...MCD MWD 524 23 578 12 305 42 9 1090 36 1 920 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 530 23 578 12 305 48 3 1228 42 1 1069 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 536 23 578 12 305 48 3 1228 42 1 1069 6...

Страница 14: ...x 2 5 TTK TWK 048 4 x 2 5 TTK TWK 060 4 x 2 5 1 Indoor and outdoor units are powered separately 2 Number of wires and section area are given for a maximum wire length of 50m If the wire is longer tha...

Страница 15: ...the drilling of the holes in the walls to connect the unit Make sure the maximum distances between the two units are not exceeded See Figure 3 and Table 10 Figure 3 Recommended clearances and maximum...

Страница 16: ...vertical line and an additional trap must be positioned every 7 5 m of vertical elevation to allow oil return to the compressor There are no special technical recommendations for liquid lines because...

Страница 17: ...same way as for brazing of the indoor unit s lines Line insulation To prevent heat losses and condensation both liquid and gas lines must be thoroughly insulated Unscrew the Flare nuts which are place...

Страница 18: ...iring and earthing arrangements must comply with local legislation WARNING Never open the indoor or outdoor unit without first disconnecting the power supply There is a risk of electrocution CAUTION 1...

Страница 19: ...C Intake from the back Table 12 Duct connection dimensions Unit size Length mm Height mm 512 518 748 198 524 530 536 948 248 048 060 1148 298 Filtering Filtering the air is necessary to ensure the un...

Страница 20: ...the system has been vacuum pumped and is in operation and if the distance between the units is greater than 6m it may be necessary to add an additional charge Table 13 indicates the amounts of refrige...

Страница 21: ...d discharge ducts are not blocked 11 Check the filters are correctly positioned Show the user how to change the filters 12 Power up the system and observe operation carefully make any necessary adjust...

Страница 22: ...ton 4 Sleep button 5 Mode button 6 Sweep button to turn on off the sweep motor 7 Louver button 8 Timer start button 9 Send button to transmit all parameters shown on the LCD to the main control board...

Страница 23: ...they are not damaged Clean them if necessary and verify their alignment 3 Motor check the wiring and ensure the commutators are operating correctly Replace any damaged components 4 Disconnection of p...

Страница 24: ...perating but the fan does not start 1 Check the fan motor the capacitor or the wiring 1 Repair or replace D Control switch is defective incorrectly wired or adjusted 1 Check the control switch connect...

Страница 25: ...or remove refrigerant fluid D Incorrect electric power supply 1 Check the electric power supply 1 Find cause and stabilise the power supply Internal coil frozen A Insufficient refrigerant fluid 1 Chec...

Страница 26: ...he second digit of 7 segment LED indicates that the compressor is on if lit and indicates either the freeze or defrost protection is active if blinking Figure 14 LEDs blinking signals On board setting...

Страница 27: ...SS SVX07B E4 27 Notes...

Страница 28: ...manual is the result of many years of research and continuous development To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time th...

Отзывы: