Installation

Refrigerant connections

It is possible to remove the electrical
cabinet to facilitate access to the
refrigerant connection. 

Installation procedure

- Make sure the route taken by your

refrigerant lines is as short as
possible.

- Limit pressure losses in the lines

which may be caused by crushing
of the lines, a large number of
bends or bending radii that are too
small.

- Slope all the gas lines leaving the

indoor unit so that oil can return to
the compressor by gravity.

· Prevent any possibility of oil

trapped in the gas lines.

CAUTION!

An insufficiently lubricated
compressor may break down.

If the vertical difference in level
between the units is greater than
2.5 m, an oil trap must be positioned
at the bottom of the vertical line, and
an additional trap must be
positioned every 7.5 m of vertical
elevation to allow oil return to the
compressor. There are no special
technical recommendations for
liquid lines because of the well-
balanced mixture of refrigerant and
oil. Movement of the liquid
refrigerant also causes the oil to
move. 

Passage of the tube and cable
bundle

Before drilling into the wall
- make sure there are no pipes or

electrical cables in the wall at the
place where you are going to drill
provide a protective sleeve for the
bundle of tubes and cables at the
point where it passes through the
hole (Figure 4). If permitted by
legislation, the condensate
drainage line can also be included
in the bundle. Wrap tape around
all the lines and cables from the
bottom of the outside unit to the
point where the piping enters the
wall. Carry out the same operation
for each circuit.

Figure 4 - Protective sleeve

A = Cable bundle
1 = Wall
2 = Inside
3 = Outside

A

Содержание MCD 048

Страница 1: ...Installation Operation Maintenance MCD MWD 512 518 524 530 536 048 060 Ductable ceiling suspended unit SS SVX07B E4...

Страница 2: ...f this condition is not respected the constructor warranty could be cancelled Do not release refrigerant into the atmosphere Foreword These Installation Operation and Maintenance instructions are give...

Страница 3: ...e t l i F 9 1 r e l l o r t n o c d e r i w e h t g n i l l a t s n I Operation 0 2 m u u c a v a g n i t a e r C 0 2 e g r a h c t n a r e g i r f e r l a n o i t i d d A 1 2 d e e p s n a F 1 2 n o...

Страница 4: ...lations Check that the electrical characteristics on the nameplate correspond to those of the national grid The electrical installation shall include a disconnect switch in compliance with local elect...

Страница 5: ...62 Length mm 420 755 755 855 855 Face Area m2 0 213 0 420 0 420 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 1 2 2 4 4 Fins per feet fpf 180 180 180 180 180 Outdoor Fan Type Axial Axial Axi...

Страница 6: ...h mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 4 4 6 6 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 2 2 Di...

Страница 7: ...Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type Axial Axial Axial Axial Number 1 1 1...

Страница 8: ...2 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial Axial Number 1 2 2 Diameter mm...

Страница 9: ...ove Height mm 508 559 610 762 762 Length mm 420 755 855 855 855 Face Area m2 0 213 0 420 0 521 0 650 0 650 Number of rows 2 2 2 2 2 Number of circuits 2 4 2 3 3 Fins per feet fpf 180 180 240 180 180 O...

Страница 10: ...Height mm 762 762 1219 1219 Length mm 855 855 855 855 Face Area m2 0 650 0 650 1 048 1 048 Number of rows 2 2 2 2 Number of circuits 2 2 4 4 Fins per feet fpf 180 180 240 240 Outdoor Fan Type Axial A...

Страница 11: ...er Groove Height mm 508 559 559 762 Length mm 420 755 755 855 Face Area m2 0 213 0 420 0 420 0 650 Number of rows 2 2 2 2 Number of circuits 2 4 4 4 Fins per feet fpf 180 180 180 180 Outdoor Fan Type...

Страница 12: ...roove Inner Groove Height mm 762 1219 1219 Length mm 855 855 855 Face Area m2 0 650 1 048 1 048 Number of rows 2 2 2 Number of circuits 4 6 6 Fins per feet fpf 180 240 240 Outdoor Fan Type Axial Axial...

Страница 13: ...MCD MWD 524 23 578 12 305 42 9 1090 36 1 920 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 530 23 578 12 305 48 3 1228 42 1 1069 6 7 170 3 3 87 8 3 210 4 3 110 MCD MWD 536 23 578 12 305 48 3 1228 42 1 1069 6...

Страница 14: ...x 2 5 TTK TWK 048 4 x 2 5 TTK TWK 060 4 x 2 5 1 Indoor and outdoor units are powered separately 2 Number of wires and section area are given for a maximum wire length of 50m If the wire is longer tha...

Страница 15: ...the drilling of the holes in the walls to connect the unit Make sure the maximum distances between the two units are not exceeded See Figure 3 and Table 10 Figure 3 Recommended clearances and maximum...

Страница 16: ...vertical line and an additional trap must be positioned every 7 5 m of vertical elevation to allow oil return to the compressor There are no special technical recommendations for liquid lines because...

Страница 17: ...same way as for brazing of the indoor unit s lines Line insulation To prevent heat losses and condensation both liquid and gas lines must be thoroughly insulated Unscrew the Flare nuts which are place...

Страница 18: ...iring and earthing arrangements must comply with local legislation WARNING Never open the indoor or outdoor unit without first disconnecting the power supply There is a risk of electrocution CAUTION 1...

Страница 19: ...C Intake from the back Table 12 Duct connection dimensions Unit size Length mm Height mm 512 518 748 198 524 530 536 948 248 048 060 1148 298 Filtering Filtering the air is necessary to ensure the un...

Страница 20: ...the system has been vacuum pumped and is in operation and if the distance between the units is greater than 6m it may be necessary to add an additional charge Table 13 indicates the amounts of refrige...

Страница 21: ...d discharge ducts are not blocked 11 Check the filters are correctly positioned Show the user how to change the filters 12 Power up the system and observe operation carefully make any necessary adjust...

Страница 22: ...ton 4 Sleep button 5 Mode button 6 Sweep button to turn on off the sweep motor 7 Louver button 8 Timer start button 9 Send button to transmit all parameters shown on the LCD to the main control board...

Страница 23: ...they are not damaged Clean them if necessary and verify their alignment 3 Motor check the wiring and ensure the commutators are operating correctly Replace any damaged components 4 Disconnection of p...

Страница 24: ...perating but the fan does not start 1 Check the fan motor the capacitor or the wiring 1 Repair or replace D Control switch is defective incorrectly wired or adjusted 1 Check the control switch connect...

Страница 25: ...or remove refrigerant fluid D Incorrect electric power supply 1 Check the electric power supply 1 Find cause and stabilise the power supply Internal coil frozen A Insufficient refrigerant fluid 1 Chec...

Страница 26: ...he second digit of 7 segment LED indicates that the compressor is on if lit and indicates either the freeze or defrost protection is active if blinking Figure 14 LEDs blinking signals On board setting...

Страница 27: ...SS SVX07B E4 27 Notes...

Страница 28: ...manual is the result of many years of research and continuous development To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time th...

Отзывы: