Tracer
®
ZN.010
and ZN.510
50
UNT-IOM-6
Notes:
Priority Level:
Diagnostics are listed in order from highest to lowest priority. The controller senses and
records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics
present simultaneously. The diagnostics affect unit operation according to priority level.
Latching
: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic
automatically resets when the input is present and valid.
Enabled
: End device is allowed to run if there is a call for it to run.
Disabled
: End device is not allowed to run even if there is a call for it to run.
No Action
: The diagnostic has no affect on the end device.
Table 14. Controller Diagnostics
Diagnostic
Latching
Fan
Valves
Elect. Heat
Damper
Yes/No
Auxiliary
No
Enabled
No action
No action
No action
temp. failure
Condensate
Yes
Off
Closed
Off
Closed
overflow
detection
Entering
No
Enabled
Enabled
Enabled
Enabled
water temp.
failure
Fan mode
No
Enabled
Enabled
Enabled
Enabled
failure
Invalid unit
Yes
Disabled
Disabled
Disabled
Disabled
configuration
failure
Low temp.
Yes
Off
Open
Off
Closed
detection
Maintenance
Yes
Enabled
No action
No action
No action
required
Setpoint
No
Enabled
No action
No action
No action
Zone temp.
No
Off
Closed
Off
Closed
failure
Diagnostics