UNT-IOM-6
43
Tracer
®
ZN.010
and ZN.510
Table 6. Binary Outputs
Binary Output
Description
Pin
BOP1
Fan high speed
J1-1
BOP2
Fan medium speed
J1-2
BOP3
Fan low speed
J1-4
BOP4
Main valve
J1-5
BOP5
Auxiliary valve/electric heat
J1-6
BOP6
2-position fresh air damper J1-7
Notes:
1. In a four-pipe application, BOP4 is used for cooling and BOP5 is
used for heating.
2. If no valves are ordered with the unit, the factory default for the
Tracer
®
ZN.010 and ZN.510 controller are:
BOP4 configured as normally closed
BOP5 configured as normally open
3. If the fresh air damper option is not ordered on the unit, BOP6 will
be configured as none.
Binary Outputs
Table 5. Occupancy Sensor State Table
Sensor Type
Sensor Position
Unit Occupancy Mode
Normally Open
Open
Occupied
Normally Open
Closed
Unoccupied
Normally Closed
Open
Unoccupied
Normally Closed
Closed
Occupied
Содержание LO
Страница 19: ...UNT IOM 6 19 Figure 5 Trim ring assembly installation ...
Страница 128: ...128 UNT IOM 6 Appendix Factory Piping Packages Automatic Circuit Setter C ...
Страница 135: ...UNT IOM 6 135 ...