UNT-IOM-6
49
Tracer
®
ZN.010
and ZN.510
Table 13. Test Sequence for 1-Heat /1-Cool Configurations
Steps
Fan
Cool Output
Heat Output
Damper
BOP1-3
BOP4 (1)
BOP5BOP6
1. Off
Off
Off
Off
Closed
2. Fan High
High
Off
Off
Closed
3. Fan Medium
Medium Off
Off
Closed
4. Fan Low
Low Off
Off
Closed
5. Cool
High On
Off
Closed
6. Heat
High Off
On
Closed
7. Fresh Air
High Off
Off
Open
Damper
(3)
8.
Exit
(2)
Notes:
(1) At the beginning of step 2, the controller attempts to clear all diagnostics.
(2) For all 1-heat/1-cool applications including 2-pipe changeover, BOP4 energizes in the cooling test
stage and BOP5 energizes in the heat test stage.This occurs even though during normal 2-pipe
changeover operation BOP4 controls the unit valve for both cooling and heating.
(2) After the Fresh Air Damper step, the test sequence performs the Exit step.This initiates a reset and
attempts to return the controller to normal operation.
(3) The fresh air damper (BOP6) only energizes during this step if binary output 6 has been configured as
a fresh air damper.