Table 12. Yellow COMM LED Activity
Yellow LED Blink Activity
Description
LED off continuously
The controller is not detecting any communication.
(Normal for units in standalone applications)
LED blinks
The controller detects communication.
LED on continuously
Abnormal condition
Table 11. Green STATUS LED Activity
Green LED Blink Activity
Description
LED on continuously
Power on (normal operation)
LED blinks once
Manual output test mode
LED blinks twice
Manual output test mode, with one or more diagnos-
tic present
LED blinks (1/4 second on, 1/4 second
off for 10 seconds)
Wink mode
LED off
·
Power off
·
Abnormal condition
·
Test button is pressed
Green STATUS LED
Note:
The wink feature allows the identification of a particular controller. When sending a request from a
device, such as Rover, the controller will wink to indicate it received the signal.
Yellow COMM LED
The green LED normally indicates whether the controller is powered
on (24 VAC supplied). Reference Table 11.