Pos.
Item
Description
4
Setpoint adjustment
Adjust the setpoint and limit value for each control method
by tapping the value.
5
Gas detector
Toggle the unit’s gas detector (optional) on or off. You will
be prompted to sign in to the Expert level.
6
Additional settings buttons
Each button will open its own settings view.
● The
Slaves
view is discussed in section
Master—Slave
operation: setting up parallel units.
● The
Dynamic setpoint
and the
Timed setpoint
view
are discussed below.
Setpoint control method
Pos.
Item
Description
A
Local
A locally-specified setpoint will be used. The setpoint can be specified
either in the
Home
view or by tapping on the setpoint values in the
Control settings
view.
B
Dynamic
The setpoint will calculated based on current outdoor temperature
and a temperature curve. A temperature curve can be set up in the
Dynamic setpoint
view.
C
Remote
A remote setpoint (through a bus connection) will be used.
Slaves
The Slaves view is discussed in section
Master–Slave operation: setting up parallel
units.
Dynamic setpoint
The
Dynamic setpoint
view allows you to specify outlet (flow) temperature values
that will apply at specific outdoor temperatures. The actual setpoint will be calculated
based on the current outdoor temperature (or process temperature) and these outlet
temperature values (Pos. 6 in the figure).
EXES01 2150EN