Pos.
Item
Pos.
Item
1
Current heating/cooling mode
● Sun = heating
● Snowflake = cooling
7
Warm water out
2
Trends
8
Warm water in
3
Alarms
9
Power: cooling*
4
Home view
10
Power consumed by the system’s
compressors*
● The lowest value is the current taken
by the compressor or compressors.
5
Cold water in
11
Power: heating*
6
Cold water out
12
Compressors
*The values for each circuit are shown on separate lines.
If the system has a buffer tank on the cold or the warm side, the tank will be displayed
along the left or the right edge of the screen. The tank’s temperature measurements
will also be displayed. Note that these buffer tanks must be enabled in the
Warm
settings
or the
Cold settings
view (see section
Cold side and warm side settings
)
before they are displayed.
Start delay, stop delay, and oil heating delay
The start delay and stop delay are shown in the top left corner as degree minutes.
These values can be changed. For example, if the stop delay value is 30Cmin and the
temperature is 1 degree below the setpoint, the heat pump will start to ramp down in 30
minutes. If the temperature is 10 degrees below the setpoint, the heat pump will start to
ramp down after 3 minutes. This can be speeded up by changing the
Left
values (time
left).
If the oil heating delay is active, the delay is displayed in minutes.
46 (66)
EXES01 2150EN