Power supply to the auxiliary circuit
The power supply to the auxiliary circuit is 220V for all the units. Connection to the power circuit is inside the panel and is
carried out in the factory. The compressor oil heaters, the protections against compressor over temperature and the
cooling water safety indicator are connected so as to always be operative, as long as the electrical panel is power
supplied.
Description of the operation
Recommended
frequency
Control of compressor oil level
monthly
Control of the suction temperature (superheating)
monthly
Control of the hydraulic circuit water filling
monthly
Control of electric absorption fan motors and compressor
monthly
Control of power supply and auxiliary power
monthly
Control of refrigerant charge through liquid sight glass (if available)
monthly
Control of the state of the carter electric heaters
monthly
Carrying out tightening of all the electrical connections
monthly
Coil cleaning
monthly
Control of the functioning of the compressor solenoid valves and
liquid line
seasonal
Control of the setting of the regulation and safety thermostat
quarterly
Control of the state of the fan and compressor contactors
quarterly
Functional test of the evaporator heater
quarterly
Noise control of the engine and fan bearings (if available)
seasonal
Pressure tank state checking
yearly