24
BAS-SVU025A-EN
Data Logs
•
Stop collecting data when the trigger condition is no longer true
– this option stops
collecting data when the defined start trigger condition is no longer true. Additional options
to delay collection start/stop and resume data collection after a stop are available.
•
Stop collecting data after X time
– this option collects a sample for a defined period of time
after the trigger condition is met, and when collection begins (for example, a 24-hour
period).
•
I
ndefinite data collection
– this option allows for a continuous window of a defined amount
of time after the trigger condition is met and when collection begins. For example, seven
days of data at a 15-minute intervals. The seven day window will always maintain the last
seven days. The maximum window is seven days.
Optionally, you can check the
Delay data collection start by
box to determine an amount of time
to delay collection start after the trigger condition occurs.
7.
In the
Collection Stop
frame, select a method to stop data collection.
8. In the
Data Buffer
frame, select a data buffer option.
9. In the
Collection Interval
frame, enter the amount of time that passes between sample
collection.
10. Click
next
. The
Create Data Log
–
Summary
page appears.
11. Review the data log summary page and then click
finish
(or previous to make changes).