21
INSTALLER’S GUIDE
18-HE39D8-13A-EN
Dampers drive to
100% open during a
"Continuous Fan"
call.
(drives beyond
minimum position setting)
Rotate Minimum
Position
potentiometer fully
CCW
Ensure there is not a call
for cooling.
Does damper
begin to close?
Adjust Minimum
Position to desired
setting.
Measure
resistance of
green resistor
across "P" and
"P1" terminals.
What is the
resistance?
Replace Logic
Module
Replace resistor with 130
ohm 1 watt resistor
Yes
No
or greater
130 ohms
Less than 130 ohms
Honeywell W7459 Only - Troubleshooting - Dampers Open With G