INSTALLER’S GUIDE

18-HE39D8-13A-EN

1

1

2

2

M9097

ENTHALPY CHANGEOVER

SETPOINT

LED LIGHTS WHEN

OUTDOOR AIR IS SUITABLE 

FOR FREE COOLING

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

TR

INSERT DC MULTIMETER BETWEEN S

O

 AND S FOR CHECKOUT 

AND TROUBLESHOOTING.

TR1

A

B C

D

SO

+

SR

+

+

C7400

620 OHM

JUMPER

DC 

W7459

S

+

1

1

M9098B

ENTHALPY

CHANGEOVER

SETPOINT

MINIMUM 

DAMPER

POSITION 

SETTING

LED LIGHTS

WHEN OUTDOOR 

AIR IS SUITABLE 

FOR FREE COOLING

MINIMUM DAMPER POSITION ADJUSTMENT 

IS PRESENT ONLY ON W7459A,D MODELS. 

MULTIMETER

Meter Location for Checkout and Troubleshooting

Location of Enthalpy Set Point, Minimum  

Position and LED

Table 2. Enthalpy Checkout Procedure - W7459 Control 

Figure 13.  Enthalpy LEDs and Checkout

Checkout Procedure

Response

A

LED is off.

Motor is in closed position.

B

1. Disconnect factory-installed 620 ohm resistor from terminals Sr and

+

LED turns on, motor drives toward open.

C

1. Disconnect power at TR and TR1.

2. Disconnect jumper P to P1.

3. Jumper TR to 1.

4. Jumper T1 to T.

5. If connected, remove C7400 Solid State Enthalpy Sensor from ter-

minals S0 and +. Ensure factory-installed 620 ohm resistor is connect-

ed to terminals Sr and +.

6. Apply power (24Vac) to terminals TR and TR1

1. To simulate high and low enthalpy (single enthalpy sensor) re-

connect factory-installed 620 ohm resistor from terminals Sr and +.

Connect 1.2K ohm 4074EJM Checkout Resistor across terminals So

and +.

2. Turn enthalpy setpoint potentiometer to "A".

LED turns on, indicating low enthalpy.

Motor drives toward open.

3. Turn enthalpy setpoint potentiometer to "D".

LED turns off, indicating high enthalpy.

Motor drives toward closed.

4. Disconnect the 1.2K ohm checkout resistor

D

1. To verify sensor operation, reconnect the + lead of the outdoor

enthalpy sensor to the + terminal of W7459.

2. Connect a DC multimeter between terminal So of the W7459A and

terminal S of the enthalpy sensor.  See Fig. 13 (positive meter lead to

terminal S of the enthalpy sensor).

Multimeter indication is between 3 and 25 mA if 

sensor is operating properly.

If multimeter indicates zero, the sensor may be 

wired backward.

3. When using differential enthalpy, check the return air enthalpy

sensor by connecting a DC multimeter between terminal Sr of the

W7459A and terminal S of the return air enthalpy sensor. (positive

meter lead to terminal S of the enthalpy sensor).

Multimeter indication is between 3 and 25 mA if 

sensor is operating properly.

If multimeter indicates zero, the sensor may be 

wired backward.

Содержание BAYRLAY004A

Страница 1: ...justed or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all pre cautions in the literature and on the tags stickers and label...

Страница 2: ...parts to your supplier immediately and replace with authorized parts only WARNING HAZARDOUS VOLTAGE DISCONNECT POWER BEFORE SERVICING 1 The economizer ships with the return air damper folded up to all...

Страница 3: ...s DC TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist...

Страница 4: ...ese options at this time per instructions provided Figure 4 Insert Economizer in Shipping Position DC TC YC or WC Unit Dry bulb outside air temperature sensor Insert economizer in folded shipping posi...

Страница 5: ...2 Insert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Lea...

Страница 6: ...Economizer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the...

Страница 7: ...urb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order separately Mount the Mixed Air Sensor to the partition using two 2 sheetm...

Страница 8: ...tinue Routing Behind Compressor Compartment and into Blower Compartment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Con...

Страница 9: ...9 INSTALLER S GUIDE 18 HE39D8 13A EN A A A A Figure 11 TC YC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 10: ...10 INSTALLER S GUIDE 18 HE39D8 13A EN Figure 12 WC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 11: ...11 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 Logic Only TC YC Economizer Connection Digram May Be C X Y...

Страница 12: ...12 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 ONLY WC Economizer Connection Digram May Be C X Y...

Страница 13: ...ion is obtained and tighten all nuts and set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage...

Страница 14: ...d to terminals Sr and 6 Apply power 24Vac to terminals TR and TR1 1 To simulate high and low enthalpy single enthalpy sensor re connect factory installed 620 ohm resistor from terminals Sr and Connect...

Страница 15: ...07 57 2 14 5 000 3 420 59 0 15 4 767 3 373 60 8 16 4 545 3 328 62 6 17 4 335 3 283 64 4 18 4 136 3 239 66 2 19 3 948 3 180 68 0 20 3 769 3 157 69 8 21 3 599 3 118 71 6 22 3 437 3 080 73 4 23 3 284 3 0...

Страница 16: ...Procedure Proper Response 1 CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaul...

Страница 17: ...rees open Remove jumper from N terminal economizer goes into not occu pied mode Motor remains at 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX...

Страница 18: ...s TR and TR1 terminals on Logic Module 24 volts No voltage No Yes Yes Yes Yes 130 ohms Open No No No G must have 24V applied to energize the minimum position damper Black wire must be connected to G l...

Страница 19: ...ate economizer beyond minimum position fresh air opening Is OAS closed Is 24V present between terminals 1 and TR1 Is resistance Remove OAS wire from S0 and terminals on the Logic module What is 620 oh...

Страница 20: ...at s Y2 connected to unit s YL Yes Is 24V present at YL Troubleshoot unit Problem is not in economizer Troubleshoot why thermostat is not calling for 2nd stage Wire per Installer s Guide Install a 2 s...

Страница 21: ...lly CCW Ensure there is not a call for cooling Does damper begin to close Adjust Minimum Position to desired setting Measure resistance of green resistor across P and P1 terminals What is the resistan...

Страница 22: ...r or replace MAS Dampers drive to 100 open although the mixed air temp is below 55F Remove MAS wires from T and T1 terminals on logic module What is It can be possible for the tip of the MAS to twist...

Страница 23: ...s for shorting Replace MAS Logic Module has repeated failures Remove MAS wires from T and T1 terminals on logic module Measure resistance from either MAS wire to cabinet ground any continuity Yes No H...