INSTALLER’S GUIDE

18-HE39D8-13A-EN

Table 4. Checkout for W7212, W7213, W7214 Economizer Connected to Honeywell Actuator (Cont.)

Step

Checkout Procedure

Proper Response

2.

DIFFERENTIAL ENTHALPY
Execute stop one, Checkout Preparation.

Turn DCV MAX to mid position.
Place 620 ohm resistor across S

O

 and + (white sleeve resistor 

makes OA enthalpy low).
Place 1.2K ohm resistor across S

R

 and + (purple sleeve resistor 

makes RA enthalpy high).

Free cool LED turn on; motor drives to approximately 45 

degrees (half) open.

Remove 620 ohm resistor from S

O

 and +.

Free cool LED turn off; motor drives closed

3.

SINGLE ENTHALPY
Execute stop one, Checkout Preparation.

Turn DCV MAX to mid position.
Set enthalpy potentiometer to A (fully CCW).

Free cool LED turns on; motor drives to approximately 45 

degrees (half) open.

Set enthalpy potentiometer to D or E for W7212C (fully CW).

Free cool LED turns off; motor drives closed.

4.

DCV AND EXHAUST
Execute step one, Checkout Preparation.

LED for both DCV and Exhaust should be off.
Turn DCV MAX to mid position.

Motor drives to mid position, 45 degrees open.

Turn MIN POS fully CW.

Motor drives fully open.

Turn MIN POS and DCV MAX to fully CCW.

Motor drives closed.

Turn DCV MAX to mid position.

Connect 9V battery positive to AQ and negative to AQ1.

LED for both DCV and Exhaust turn on.

Actuator drives to 45 degrees open.

Remove jumper from N terminal (economizer goes into not occu-

pied mode).

Motor remains at 45 degrees open.

Adjust DCV MAX towards CW.

Motor will move to position set by DCV MAX pot.

Adjust DCV MAX to fully CCW.

Motor will drive closed.

Reconnect jumper to N terminal.
Adjust DCV MAX and MIN POS pots.

Motor will drive to the most open position of the pots.

Adjust DCV MAX and MIN POS pots to fully CCW.
Remove power from N terminal adjust MIN POS towards CW.

Motor should not move.

Adjust DCV MAX towards CW.

Motor will move to position set by DCV MAX pot.

5.

MINIMUM AND MAXIMUM POSITION
Execute stop one, Checkout Preparation.

Connect 9V battery positive to AQ and negative to AQ1. Adjust 

DCV MAX potentiometer to mid position.

DCV LED turns on. Actuator drives to 45 degrees open.

Turn DCV maximum position potentiometer to fully CCW.

Actuator drives fully closed.

Turn minimum position potentiometer to midpoint.

Actuator drives to 45 degrees open.

Turn minimum position potentiometer fully CW.

Actuator drives fully open.

Turn MIN POS to fully CCW.

Actuator drives fully closed.

W7212: Remove jumper from TR and N.

Actuator drives fully closed.

W7214: Jumper TR to O.

6.

MIXED AIR INPUT
Execute stop one, Checkout Preparation.

Turn DCV MAX to mid position; set enthalpy potentiometer to A.

Free cool LED turns on.

Actuator drives to 45 degrees open.
Actuator drives to 45 degrees open.

Remove 5.6K ohm resistor (green sleeve) and place jumper from 

T and T1.
Remove jumper from T and T1 and leave open.

Actuator drives fully closed.

Содержание BAYRLAY004A

Страница 1: ...justed or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all pre cautions in the literature and on the tags stickers and label...

Страница 2: ...parts to your supplier immediately and replace with authorized parts only WARNING HAZARDOUS VOLTAGE DISCONNECT POWER BEFORE SERVICING 1 The economizer ships with the return air damper folded up to all...

Страница 3: ...s DC TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist...

Страница 4: ...ese options at this time per instructions provided Figure 4 Insert Economizer in Shipping Position DC TC YC or WC Unit Dry bulb outside air temperature sensor Insert economizer in folded shipping posi...

Страница 5: ...2 Insert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Lea...

Страница 6: ...Economizer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the...

Страница 7: ...urb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order separately Mount the Mixed Air Sensor to the partition using two 2 sheetm...

Страница 8: ...tinue Routing Behind Compressor Compartment and into Blower Compartment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Con...

Страница 9: ...9 INSTALLER S GUIDE 18 HE39D8 13A EN A A A A Figure 11 TC YC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 10: ...10 INSTALLER S GUIDE 18 HE39D8 13A EN Figure 12 WC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 11: ...11 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 Logic Only TC YC Economizer Connection Digram May Be C X Y...

Страница 12: ...12 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 ONLY WC Economizer Connection Digram May Be C X Y...

Страница 13: ...ion is obtained and tighten all nuts and set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage...

Страница 14: ...d to terminals Sr and 6 Apply power 24Vac to terminals TR and TR1 1 To simulate high and low enthalpy single enthalpy sensor re connect factory installed 620 ohm resistor from terminals Sr and Connect...

Страница 15: ...07 57 2 14 5 000 3 420 59 0 15 4 767 3 373 60 8 16 4 545 3 328 62 6 17 4 335 3 283 64 4 18 4 136 3 239 66 2 19 3 948 3 180 68 0 20 3 769 3 157 69 8 21 3 599 3 118 71 6 22 3 437 3 080 73 4 23 3 284 3 0...

Страница 16: ...Procedure Proper Response 1 CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaul...

Страница 17: ...rees open Remove jumper from N terminal economizer goes into not occu pied mode Motor remains at 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX...

Страница 18: ...s TR and TR1 terminals on Logic Module 24 volts No voltage No Yes Yes Yes Yes 130 ohms Open No No No G must have 24V applied to energize the minimum position damper Black wire must be connected to G l...

Страница 19: ...ate economizer beyond minimum position fresh air opening Is OAS closed Is 24V present between terminals 1 and TR1 Is resistance Remove OAS wire from S0 and terminals on the Logic module What is 620 oh...

Страница 20: ...at s Y2 connected to unit s YL Yes Is 24V present at YL Troubleshoot unit Problem is not in economizer Troubleshoot why thermostat is not calling for 2nd stage Wire per Installer s Guide Install a 2 s...

Страница 21: ...lly CCW Ensure there is not a call for cooling Does damper begin to close Adjust Minimum Position to desired setting Measure resistance of green resistor across P and P1 terminals What is the resistan...

Страница 22: ...r or replace MAS Dampers drive to 100 open although the mixed air temp is below 55F Remove MAS wires from T and T1 terminals on logic module What is It can be possible for the tip of the MAS to twist...

Страница 23: ...s for shorting Replace MAS Logic Module has repeated failures Remove MAS wires from T and T1 terminals on logic module Measure resistance from either MAS wire to cabinet ground any continuity Yes No H...

Страница 24: ...plications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and sp...

Отзывы: