2

INSTALLER’S GUIDE

18-HE39D8-13A-EN

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT

 

- This Document is customer property and is to remain with this unit. Please return to service information pack  

upon completion of work.

Install Economizer Kit

1. Remove Power

     

Disconnect and verify that power is off.

2. Remove Access Panels

 

Remove these four (4) access panels (see Figure 3, page 3):

 

• Control/Heat access panel

 

• Blower access panel

 

• Coil access panel

 

• Horizontal Return Air panel (discard or store)

3.  Install Economizer Assembly

General

The economizer is a multi-damper design. It is installed in the 
return air stream and is connected to the unit low voltage supply 
through wire leads. The economizer is fully accessible through the 
Coil access panel.

IMPORTANT:

 

The Economizer installation requires that you 

install an air filter rack ordered separately. Use:
BAYFLTR101B for 2/4YC*, WC*, TC*, DC* *018-3036
BAYFLTR201B for 2/4YC*, WC*, TC*, DC* *042-3060.
When the economizer is installed in WC* models, relay accessory 

kit BAYRLAY004A is required. Refer to the drawing on page 9 to 

make your relay wiring connections in the Control Box.

Identify Economizer Kit Contents

Refer to Figures 1 and 2 on page 3 to identify the kit contents.

Inspect Contents

You must re   port damage and make claims to the transportation 
company immediately. Report missing parts to your supplier 
immediately and replace with authorized parts only.

!

WARNING:

 HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

1.  The economizer ships with the return air damper folded   
 

up to allow the assembly to fit through the Coil opening    

 

in the side of the unit, see Figures 1 and 2 on page 3.

  Insert the economizer assembly into the unit through the  
  Coil access panel opening. See Figure 4 on page 4. 
2.  Swing the return air damper section down so that it rests  

on the bottom of the unit. The economizer will sit com-
pletely over the return air opening in the bottom of the 
unit.  See Figures 5 on page 5. Screw the economizer 
assembly together with one assembly screw in the side 
of the economizer. Tighten the linkage rod between the 
return air dampers.

3.  Insert 2 screws through the holes in the front face of the  
  unit and into the matching attachment holes in the  
  economizer assembly. See Figure 6 on page 5. 

4. 

Insert a screw through the pre-punched hole in the side 
flange of the return air damper and into the mating hole  
in the economizer assembly and tighten. See Figure 5 
on page 5.

ELECTRIC SHOCK HAZARD

OPEN AND LOCK OUT ALL UNIT DISCONNECTS PRIOR TO  

ACCESSORY INSTALLATION OR UNIT MAINTENANCE, TO PRE-

VENT INJURY OR DEATH FROM ELECTRICAL SHOCK OR CON-

TACT WITH MOVING PARTS.

WARNING

!

SAFETY HAZARD

DO NOT REMOVE END COVERS FROM ECONOMIZER ACTUATOR; 

THE SPRING-RETURN ASSEMBLY MAY RELEASE AND CAUSE 

PERSONAL INJURY.

!

WARNING

Use care when inserting the economizer in the return air compart-

ment, to prevent damaging the foil faced insulation.

CAUTION

!

Содержание BAYRLAY004A

Страница 1: ...justed or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all pre cautions in the literature and on the tags stickers and label...

Страница 2: ...parts to your supplier immediately and replace with authorized parts only WARNING HAZARDOUS VOLTAGE DISCONNECT POWER BEFORE SERVICING 1 The economizer ships with the return air damper folded up to all...

Страница 3: ...s DC TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist...

Страница 4: ...ese options at this time per instructions provided Figure 4 Insert Economizer in Shipping Position DC TC YC or WC Unit Dry bulb outside air temperature sensor Insert economizer in folded shipping posi...

Страница 5: ...2 Insert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Lea...

Страница 6: ...Economizer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the...

Страница 7: ...urb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order separately Mount the Mixed Air Sensor to the partition using two 2 sheetm...

Страница 8: ...tinue Routing Behind Compressor Compartment and into Blower Compartment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Con...

Страница 9: ...9 INSTALLER S GUIDE 18 HE39D8 13A EN A A A A Figure 11 TC YC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 10: ...10 INSTALLER S GUIDE 18 HE39D8 13A EN Figure 12 WC Economizer Connection Diagram Wiring Diagram for Economizer Using a Honeywell W7459 Logic...

Страница 11: ...11 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 Logic Only TC YC Economizer Connection Digram May Be C X Y...

Страница 12: ...12 INSTALLER S GUIDE 18 HE39D8 13A EN Wiring Diagram for Economizer Using a Honeywell W7212 ONLY WC Economizer Connection Digram May Be C X Y...

Страница 13: ...ion is obtained and tighten all nuts and set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage...

Страница 14: ...d to terminals Sr and 6 Apply power 24Vac to terminals TR and TR1 1 To simulate high and low enthalpy single enthalpy sensor re connect factory installed 620 ohm resistor from terminals Sr and Connect...

Страница 15: ...07 57 2 14 5 000 3 420 59 0 15 4 767 3 373 60 8 16 4 545 3 328 62 6 17 4 335 3 283 64 4 18 4 136 3 239 66 2 19 3 948 3 180 68 0 20 3 769 3 157 69 8 21 3 599 3 118 71 6 22 3 437 3 080 73 4 23 3 284 3 0...

Страница 16: ...Procedure Proper Response 1 CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaul...

Страница 17: ...rees open Remove jumper from N terminal economizer goes into not occu pied mode Motor remains at 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX...

Страница 18: ...s TR and TR1 terminals on Logic Module 24 volts No voltage No Yes Yes Yes Yes 130 ohms Open No No No G must have 24V applied to energize the minimum position damper Black wire must be connected to G l...

Страница 19: ...ate economizer beyond minimum position fresh air opening Is OAS closed Is 24V present between terminals 1 and TR1 Is resistance Remove OAS wire from S0 and terminals on the Logic module What is 620 oh...

Страница 20: ...at s Y2 connected to unit s YL Yes Is 24V present at YL Troubleshoot unit Problem is not in economizer Troubleshoot why thermostat is not calling for 2nd stage Wire per Installer s Guide Install a 2 s...

Страница 21: ...lly CCW Ensure there is not a call for cooling Does damper begin to close Adjust Minimum Position to desired setting Measure resistance of green resistor across P and P1 terminals What is the resistan...

Страница 22: ...r or replace MAS Dampers drive to 100 open although the mixed air temp is below 55F Remove MAS wires from T and T1 terminals on logic module What is It can be possible for the tip of the MAS to twist...

Страница 23: ...s for shorting Replace MAS Logic Module has repeated failures Remove MAS wires from T and T1 terminals on logic module Measure resistance from either MAS wire to cabinet ground any continuity Yes No H...

Страница 24: ...plications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and sp...