Installation

ACC-SVN67M-EN

8. TCO-A is the limit control located in the center or right part 

of the heater mounting plate that is located on the bottom 
of the two heater element assemblies. See 

Figure 4

. To 

replace this device, first remove the two wires connected 
to the terminals. Next, remove the two screws which 
secure it to the heater element mounting plate. Once TCO-
A has been removed from the heater element mounting 
plate, discard this device.

9. Obtain the replacement TCO-A which is secured with a 

wire tie near the unit/heater terminal block located on the 
electric heater control panel. Attach it to the heater element 

mounting plate with the two screws that were removed in 
step 8. Connect the two wires that were un-hooked in step 
8 to the terminals on the new TCO-A. Refer to the heater 
package wiring diagram to assure that the wiring is 
connected properly.

Note:

The back of the electric heater element assembly 
is supported by a factory installed Electric Heat 
Support Rod Hanger or other sheet metal device in 
the unit.

10. Tilt the back of the electric heater element assembly 

slightly upward as it is positioned in the opening to engage 
the support rod with the support rod hanger. The 
BAYHTRA, BAYHTRB, and BAYHTRD models will have a 
guide rod and a support bracket to help with the 
installation. Se

Figure 5

. Be very careful to avoid 

dragging the heater element on the edges of the opening 
in vestibule panel, as this could damage or pinch the heater 
elements resulting in a short circuit. Engage the bottom 
edge of heater element panel with the two locator tabs. See 

Figure 3

. BAYHTRB and BAYHTRD kits will have 4 locator 

tabs along the top, a filler panel to be placed below the 
heater, and 12 screws to attach the assembly in place. See 

Figure 6

.

Table 2. TCO-A replaced for horizontal duct 

configuration

Unit Model Number

Electric Heater Model 

Number

TCO-A 

location

TSC120H4, WSC120H4

BAYHTRA454

Right

TSC120HW, TZC072FW, 

TZC090FW, and TZC102FW

BAYHTRAW18, 

BAYHTRAW36, W54

Right

TZC120FW, WHC120HW

BAYHTRBW18A, 
BAYHTRZW36A, 
BAYHTRZW54A, 

BAYHTRBW36, W54

Right

THC092F4, THC074F4, 
THC102F4, TSC120H4, 

TZC072F4, TZC090F4, and 

TZC102F, TZ102F4

BAYHTRA427, 
BAYHTRA436, 
BAYHTRZ409, 

BAYHTRA418

Right

THC072E4, WSC090H4

BAYHTRU427, 436

Center

WSC090HW

BAYHTRUW27, W36

Center

WSC072H3

BAYHTRW327, 336

Center

TSC090E4, WSC072H4

BAYHTRW427, 436

Center

TSC090EW, WSC072HW

BAYHTRWW27, W36

Center

WSC092H3, WSC102H3

BAYHTRU336

Center

WSC092H4, WSC102H4

BAYHTRU436

Center

Figure 4.

TCO-A LOCATED ON THE RIGHT

TCO-A LOCATED IN THE CENTER

Figure 5.

GUIDE ROD

GUIDE ROD

SUPPORT BRACKET

SUPPORT BRACKET

Содержание BAY24X042

Страница 1: ...and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe...

Страница 2: ...ous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or prope...

Страница 3: ...ment are the trademarks of their respective owners Revision History Updated Heater Model Number for WSC120H3 in Electrical Data chapter WARNING Follow EHS Policies Failure to follow instructions below...

Страница 4: ...4 ACC SVN67M EN Table of Contents General Information 5 General 7 Inspection 7 Installation 8 Electrical Data 12...

Страница 5: ...H3 a WHC074H3 WHC092H3 WHC102H3 THC102F3 WSC120H3 BAYHTRA327 TSC120H3 WSC090H3 a THC074F3 TZC072F3 WSC102H3 a WSC120H3 THC092F3 TZC090F3 THC102F3 TZC102F3 TSC092H3 TSC102H3 WSC092H3 a WHC074H3 WHC092H...

Страница 6: ...HC120H4 BAYHTRB436 WHC120H4 BAYHTRB454 WHC120H4 BAYHTRBW18 TZC120FW WHC120HW BAYHTRBW36 WHC120HW BAYHTRBW54 WHC120HW BAYHTRD318 THC120E3 TZC120F3 BAYHTRD327 THC120E3 TZC120F3 BAYHTRD336 THC120E3 BAYHT...

Страница 7: ...must be reported immediately and a claim made against the transportation company 3 Check the heater nameplate model number and compare with the electrical data tables Ensure that the available power s...

Страница 8: ...the same as any in this table and the application is for horizontal airflow the limit control TCO A must be replaced with the extra limit control shipped with the heater Replace TCO A following the in...

Страница 9: ...rt rod hanger The BAYHTRA BAYHTRB and BAYHTRD models will have a guide rod and a support bracket to help with the installation See Figure 5 Be very careful to avoid dragging the heater element on the...

Страница 10: ...ush against center post and secure each door stop with 1 or 2 screws See zoom view in Figure 8 or Figure 9 14 Remove the wire nuts from W1 W2 and W3 15 For models with the control box in the outdoor s...

Страница 11: ...with ohmmeter and verify that heater element terminals are electrically isolated from cabinet and ground infinite resistance On downflow units with or without duct work installed or horizontal units w...

Страница 12: ...nimum allowable airflow for a TSC120EF TZC120F and THC120E with a 54 kW heater is 3400 cfm e The minimum allowable airflow for a WSC120 with a 54 kW heater is 4000 cfm Table 4 Unit wiring with electri...

Страница 13: ...35 34 35 33 35 7 5 c TSC092H4 BAYHTRT427 BAYHTRA427 d 27 2 44 45 48 50 47 50 7 5 c TSC092H4 BAYHTRT436 BAYHTRA436 d 36 2 58 60 61 70 60 60 8 5 TSC102H4 BAYHTRT409 BAYHTRA409 d 9 1 21 25 23 25 22 25 8...

Страница 14: ...er Model Number Heater kW Rating Control Stages Standard Indoor Fan Motor a Oversized Indoor fan Motor Optional EBM Fan Motor MCA Max Fuse Size or Max Circuit Breaker MCA MaxFuseSize or Max Circuit Br...

Страница 15: ...1 34 40 35 40 34 40 8 5 WSC102H4 BAYHTRU418 BAYHTRA418 18 0 1 47 50 49 50 48 50 8 5 WSC102H4 BAYHTRU427 BAYHTRA427 27 0 2 61 70 62 70 61 70 8 5 WSC102H4 BAYHTRU436 BAYHTRA436 36 0 2 74 80 76 80 75 80...

Страница 16: ...or Max Circuit Breaker MCA Max Fuse Size or Max Circuit Breaker 208 230 Volts Three Phase 6 WHC074H3 BAYHTRA309 6 8 9 0 1 66 69 70 70 6 WHC074H3 BAYHTRA318 13 5 18 0 1 89 96 90 100 6 WHC074H3 BAYHTRA...

Страница 17: ...nnection high efficiency and eFlex 6 to 10 tons Standard Indoor Motor Oversized Indoor Motor Tons Unit Model Number Heater Model Number Heater kW Rating a Control Stages MCA Max Fuse Size or Max Circu...

Страница 18: ...AYHTRA409 9 0 1 18 9 25 6 THC074F4 BAYHTRA418 18 0 1 32 5 35 6 THC074F4 BAYHTRA427 27 0 2 46 0 50 460 Volts Three Phase 6 THC074F4 BAYHTRA436 36 0 2 59 5 60 6 TZC072F4 BAYHTRA409A 9 1 10 8 26 6 TZC072...

Страница 19: ...egrees C b Degrees F c 6 Ton 7 5 Ton 10 Ton 6 Ton 7 5 Ton 10 Ton kW Voltage Stages 4100 M3 H 5100 M3 H 6800 M3 H kW Voltage Stages 2400 cfm 3000 cfm 4000 cfm WSC072ED WSC090ED WSC120 ED WSC072ED WSC09...

Страница 20: ...umCircuit Breaker TSC072ED BAYHTRS418 11 3 13 5 39 47 1 26 9 28 9 35 35 28 1 30 1 35 35 BAYHTRS427 16 9 20 2 58 69 2 37 5 40 5 40 45 38 8 41 8 40 45 BAYHTRS436 22 6 26 9 78 92 2 48 3 52 1 50 60 49 5 5...

Страница 21: ...Notes ACC SVN67M EN 21...

Страница 22: ...Notes 22 ACC SVN67M EN...

Страница 23: ...Notes ACC SVN67M EN 23...

Страница 24: ...cations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and reside...

Отзывы: