WSHP-SVX015C-EN
73
2. Remove the Outside Air Sensor (OAS) from the
condenser section of unit.
3. Use two (2) wire nuts, to individually cap the wires.
4. Locate the RTRM (J6). Connect two (2) wires to
terminals J6-1 and 2.
5. Connect the sensor (OAS) using two wire nuts to
the two (2) field supplied wires that were connected
to terminals 1 and 2 on J6.
Unit Economizer Control (ECA)
Troubleshooting
Table 24.
Verify economizer status by economizer
actuator (ECA) LED indicator:
OFF:
No Power or Failure
ON:
Normal, OK to Economize
Slow Flash:
Normal, Not OK to Economize
Fast Flash:
1/2 Second On / 2 Seconds Off:
Error Code:
Communications Failure
Table 24.
Verify economizer status by economizer
actuator (ECA) LED indicator: (continued)
Pulse Flash:
2 Second On / 1/2 Second Off:
Error Code:
1 Flash:
Actuator Fault
2 Flashes:
CO2 Sensor
3 Flashes:
RA Humidity Sensor
4 Flashes:
RA Temp Sensor
5 Flashes:
OA Quality Sensor
6 Flashes:
OA Humidity Sensor
7 Flashes:
OA Temp Sensor
8 Flashes:
MA Temp Sensor
9 Flashes:
RAM Fault
10 Flashes:
ROM Fault
11 Flashes:
EEPROM Fault