WSHP-SVX015C-EN
43
Figure 47.
Control box 12.5 to 20 tons
LTB
TEST 1
TEST 2
RTRM
Space Temperature Averaging
Space temperature averaging is accomplished by
wiring a number of remote sensors in a series/parallel
circuit.
Using the BAYSENS016* or BAYSENS075*, at least
four sensors are required to accomplish space
temperature averaging. Example #1 illustrates two
series circuits with two sensors in each circuit wired in
parallel. The square of any number of remote sensors
is required. Example #2 illustrates three sensors
squared in a series/parallel circuit. Using
BAYSENS075*, two sensors are required to accomplish
space temperature averaging. Example #3 illustrates
the circuit required for this senor. The temperature vs.
resistance table lists the temperature versus resistance
coefficient for all sensing.
Содержание Axiom GWS Series
Страница 75: ...WSHP SVX015C EN 75 N No ot te es s...