72
WSHP-SVX015C-EN
should measure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias will show an
over Load, or open circuit indication if LED is
functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect
Ohmmeter across LED in one direction, then reverse
the leads for the opposite direction. The LED should
have at least 100 times more resistance in reverse
direction, as compared with the forward direction. If
high resistance in both directions, LED is open. If low in
both directions, LED is shorted.
Method 3
To test LED’s with ZSM connected to unit, test voltages
at LED terminals on ZSM. A measurement of 32 VDC,
across an unlit LED, means the LED has failed.
N
No
otte
e:: Measurements should be made from LED
common (ZSM terminal 6 to respective LED
terminal). Refer to the Zone Sensor Module
(ZSM) Terminal Identification table at the
beginning of this section.
Programmable & Digital Zone
Sensor Test
Testing Serial Communication Voltage
W
WA
AR
RN
NIIN
NG
G
L
Liiv
ve
e E
Elle
eccttrriicca
all C
Co
om
mp
po
on
ne
en
nttss!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w a
allll e
elle
eccttrriicca
all ssa
affe
etty
y p
prre
ecca
au
uttiio
on
nss
w
wh
he
en
n e
ex
xp
po
osse
ed
d tto
o lliiv
ve
e e
elle
eccttrriicca
all cco
om
mp
po
on
ne
en
nttss cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
W
Wh
he
en
n iitt iiss n
ne
ecce
essssa
arry
y tto
o w
wo
orrkk w
wiitth
h lliiv
ve
e e
elle
eccttrriicca
all
cco
om
mp
po
on
ne
en
nttss,, h
ha
av
ve
e a
a q
qu
ua
alliiffiie
ed
d lliicce
en
nsse
ed
d e
elle
eccttrriicciia
an
n
o
orr o
otth
he
err iin
nd
diiv
viid
du
ua
all w
wh
ho
o h
ha
ass b
be
ee
en
n p
prro
op
pe
errlly
y ttrra
aiin
ne
ed
d
iin
n h
ha
an
nd
dlliin
ng
g lliiv
ve
e e
elle
eccttrriicca
all cco
om
mp
po
on
ne
en
nttss p
pe
errffo
orrm
m
tth
he
esse
e tta
asskkss..
1. Verify 24 Vac is present between terminals J6-14 &
J6-11.
2. Disconnect wires from J6-11 and J6-12. Measure
the voltage between J6-11 and J6-12; it should be
about 32 Vdc.
3. Reconnect wires to terminals J6-11 and J6-12.
Measure voltage again between J6-11 and J6-12,
voltage should flash high and low every 0.5
seconds. The voltage on the low end will measure
about 19 Vdc, while the voltage on the high end will
measure from approximately 24 to 38 Vdc.
4. Verify all modes of operation, by running the unit
through all of the steps in the “Test Modes” section
discussed in “Unit Start-Up”.
5. After verifying proper unit operation, exit the test
mode. Turn the fan on continuously at the ZSM, by
pressing the button with the fan symbol. If the fan
comes on and runs continuously, the ZSM is good.
If you are not able to turn the fan on, the ZSM is
defective.
Table 23.
System mode and fan selection chart
Resistance
Valves
(Ohms)
Zone
Sensor
Unit/Fan
Mode
Local Unit
Mode
Local Fan
Mode
2.32K
Off/ Auto
Off
Auto
4.87K
Cool/Auto
Cool
Auto
7.68K
Auto/Auto
Auto
Auto
10.77K
Off/On
Off
On
13.32K
Cool/On
Cool
On
16.13K
Auto/On
Auto
On
19.48K
Heat/Auto
Heat
Auto
27.93K
Heat/On
Heat
On
35.0K
Emergency
Heat/Auto
Emergency
Heat
Auto
43.45K
Emergency
Heat/On
Emergency
Heat
On
Out of Range
(Short)
INVALID/
Short
Invalid (CV),
Auto (VAV)
Invalid
Out of Range
(Open)
INVALID/
Open
Invalid (CV),
Off (VAV)
Invalid
ReliaTel
™
™
Refrigeration Module (RTRM)
Default Chart
If the RTCI loses input from the building management
system, the RTRM will control in the default mode after
approximately 15 minutes. If the RTRM loses the
Heating and Cooling setpoint input, the RTRM will
control in the default mode instantaneously. The
temperature sensing thermistor in the Zone Sensor
Module is the only component required for the
“Default Mode” to operate.
Unit Operation without a Zone Sensor
This procedure is for temporary operation only. The
economizer functions are disabled.
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
1. Open and Lock the unit disconnect switch.