background image

Warnings and Cautions

WARNING

R-410A Refrigerant under Higher Pressure than R-22!

The units described in this manual uses R410-A refrigerant which operates at 50 to 70% 
higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant 
cylinders are painted with "pink" color to indicate the type of refrigerant and may contain 
a "dip" tube to allow for charging of liquid refrigerant into the system. For specific handling 
concerns with R-410A, please contact your local sales office. 
Failure to use R-410A approved service equipment could result in standard equipment 
exploding under R-410A higher pressure which could result in death or serious injury.  

NOTICE

Use PVE Oil with R-410A Mini Split Units!

Most R-410A mini-splits use a PVE oil (Polyvinyl Ether Oil) that readily absorbs moisture 
from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed 
whenever possible. If a system has been open to the atmosphere for more than 4 hours, 
the compressor oil must be replaced. Never break a vacuum with air and always change 
the driers when opening the system for component replacement. For specific handling 
concerns with the PVE oil, contact your local sales office. 
USE ONLY THE FACTORY RECOMMENDED - DAFNE HERMETIC OIL FV50S - for servicing 
these units.  

Important! 

Environmental Concerns 

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring 
stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals 
that may affect the ozone layer are refrigerants that contain chlorofluorocarbons (CFC's) and those containing 
hydrochlorofluorocarbons (HCFC's). Not all refrigerants containing these compounds have the same potential 
impact to the environment. The Company advocates the responsible handling of all refrigerants, including 
industry replacements for CFC's such as HCFC's and HFC's. 

Responsible Refrigerant Practices

The manufacturer believes that responsible refrigerant practices are important to the environment, our 
customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The 
Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling 
of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or 
municipalities may have additional requirements that must also be adhered to for responsible management of 
refrigerants. Know the applicable laws and follow them. 

Содержание American Standard 4MXD8509A

Страница 1: ...the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2020 MS SVN34D EN 11 Jun 2020 Supersedes MS SVN34C EN January 2016 The...

Страница 2: ...autions Attention Warnings and Cautions appear at appropriate sections throughout this literature Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could re...

Страница 3: ...contact your local sales office USE ONLYTHE FACTORY RECOMMENDED DAFNE HERMETIC OIL FV50S for servicing these units Important Environmental Concerns Scientific research has shown that certain man made...

Страница 4: ...f the Drain Pipe 14 Design of the Drain Pipe 14 Precautions for the Drain Pipe 15 Test the Drainage System 16 Connecting the Pipe at the Indoor Unit 17 Installation of the Connection Pipe 18 Flare Pro...

Страница 5: ...complete installation may cause injury or property damage in the event the unit falls off of the base 5 Electrical work should be carried out in accordance with the installation manual and local state...

Страница 6: ...ge to the air conditioner 16 Be sure to follow your local state and National Electric Codes when grounding this unit 17 This appliance is not intended for use by persons with a lack of experience and...

Страница 7: ...inch 9 8 inch NOTE Be sure to place an inspection service opening at the position indicated in the diagram above for maintenance of the equipment Indoor Ceiling Concealed Unit NOTE The minimum distanc...

Страница 8: ...e indoor unit far away from heat sources vapor and flammable gas 4 Be sure that the installation of the indoor unit conforms to the installation dimension diagram 5 Be sure to leave enough space to al...

Страница 9: ...e a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks Failure to follow all of the recommended safety warnings provided...

Страница 10: ...ation depends on the actual installation environment After installation of the indoor unit the leveling must be checked to make sure the unit is kept horizontal fore and aft and a downward slope of 5...

Страница 11: ...he transition connection to the air outlet of the unit and attach it with a rivet Connect the outlet to the short duct and secure them with tape CAUTION This unit is intended for free air discharge or...

Страница 12: ...flange is in the back and the return air cover plate is in the bottom 2 If downward return air is desired exchange the location of the rectangular flange and the return air cover plate 3 Connect one e...

Страница 13: ...ge from the joint of the condensate pipe Failure to do so may result in equipment and or property damage 1 The condensate pipe should keep a downward sloping angle of 5 10 which can facilitate drainag...

Страница 14: ...for multiple units the joined section of the pipe should be 3 9 inches 100mm lower than the drain hole of each device and it is suggested to use a larger diameter pipe when connecting multiple units I...

Страница 15: ...accessory Clamp accessory Max 4mm 0 16 inch Precautions for the Drain Pipe The installation height of the lift pipe should be less than 33 5 inches 850mm It is recommended to set an inclination angle...

Страница 16: ...drain pipe should be suitable to the running capacity of the unit Drain Hose accessory Max 75mm Max 1000mm Max 39 4 inch Max 3 inch Test the Drainage System 1 After the electrical installation test t...

Страница 17: ...pe is to be connected so as to prevent dust and impurities from coming into the pipe system Back up Wrench 1 When connecting the pipe to the unit or removing it from the unit please use both the spann...

Страница 18: ...with that of the indoor unit Installation of the Connection Pipe Flare Processing 1 Cut the connection pipe with the pipe cutter and remove the burrs 2 Hold the pipe downward to prevent cuttings from...

Страница 19: ...To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 5 9 in 150 mm or more 2 If the pipe is bent repeatedly at the same place it will break CAUTION Be sure to...

Страница 20: ...ed insulation 5 All wiring should be done strictly in accordance with the wiring diagram otherwise improper wiring would cause abnormal operation or damage to the unit 6 Do not let the electric wires...

Страница 21: ...rd through the insulation tube fasten it with the cord clamp Stranded Wire Note Match the terminal block numbers and connection cord colors with those of the indoor unit WARNING 1 Before starting work...

Страница 22: ...nd electrocution hazards For high voltage connections flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure To avoid these hazards...

Страница 23: ...The communication distance between the main board and the wired controller can be up to 65 ft The standard distance is 25 ft Note When connecting the power supply cord make sure that the phase of the...

Страница 24: ...malfunction and fire or electrocution hazard 8 Does the power cord match the unit requirements Improper wiring can create malfunction and fire or electrocution hazard 9 Are there any obstructions nea...

Страница 25: ...ck VT Violet OG Orange n Color Key Indoor Unit Ceiling Concealed NOTE The wiring diagrams in this guide are included as a reference The manufacturer has a policy of continuous product and product data...

Страница 26: ...it Dimensions In mm MODEL A B C D E F G H I J 4MXD8509A 30 742 19 491 26 662 24 620 28 700 24 615 31 782 6 156 8 200 25 635 4MXD8512A 4MXD8518A 37 942 19 491 34 862 32 820 35 900 24 615 39 982 6 156 8...

Страница 27: ...hen unit is running or after running The sound of the drainage system operating Cracking sound is heard when unit is operating and after operating This sound occurs when the unit panels expand or cont...

Страница 28: ...roperly 3 If the batteries of the wireless remote controller have been replaced 4 If the filter screen has been cleaned and replaced securely 5 After long periods of shutdown open the main power switc...

Отзывы: