7
Ceiling Concealed Unit
Clearance Requirements
23.6” (600mm)
(150 mm)
23.6” (600mm)
Air outle
t
Air inlet
inspection
opening
5.9”
Nut with
washer
500
mm
250
mm
Spring
pad
>19.7 inch
>9.8 inch
NOTE: Be sure to place an inspection/service opening at the position indicated in the diagram above
for maintenance of the equipment.
Indoor Ceiling Concealed Unit
NOTE: The minimum distance from the floor to the bottom of the unit is 5.6 feet (1.7m).
The maximum distance from the floor to the bottom of the unit is 13 feet (4m) for adequate com
-
fort control.