50
HDWA-SVX001D-EN
Figure 34.
Sequence of operation: Tracer AdaptiView power up
Black Screen
Grey Screen
Loading UI
(User Interface from UC800)
First Trane Logo
Second Trane Logo
Display Ready
Apply
Control
Power
Last Mode
(i.e., Auto
or Stopped
as Shown)
12 seconds
18 seconds
30 seconds
15 seconds
15 seconds
90 seconds total
Note: The variation in power up time is dependent on the number of installed options.
In the following diagrams:
•
The time line indicates the upper level operating
mode, as it would be viewed in the Tracer
®
AdaptiView
™
.
•
The shading color of the cylinder indicates the
software state.
•
Text in parentheses indicates sub-mode text as
viewed in the Tracer
®
AdaptiView
™
.
•
Text above the time line cylinder is used to illustrate
inputs to the UC800. This may include user input to
the Tracer
®
AdaptiView
™
touch screen, control
inputs from sensors, or control inputs from a
generic BAS.
•
Boxes indicate control actions such as turning on
relays, or moving the inlet guide vanes.
•
Smaller cylinders under the main cylinder indicate
diagnostic checks.
•
Text outside a box or cylinder indicates time-based
functions.
•
Solid double arrows indicate fixed timers.
•
Dashed double arrows indicate variable timers.
Power Up
“Software Operation Overview Diagram,” p. 49
includes an illustration of Tracer
®
AdaptiView
™
during
a power up of the UC800. This process takes from 30 to
50 seconds depending on the number of installed
options.