34
HDWA-SVX001D-EN
Figure 22.
Recommended area for unit insulation
N
No
otte
ess::
•
Bulbwells, drain, and vent connections must be accessible after insulating.
•
All units with evaporator marine waterboxes: wrap waterbox shell insulation with strapping and secure
strapping with seal.
•
Evaporators with ASME nameplates must have insulation cut out around the nameplate. Do NOT glue
insulation to the nameplate.
•
Apply 2-in. (50.8-mm) wide black tape on overlap joints. Where possible, apply 3-in. (76.2-mm) wide strip of
0.38-in. (9.652-mm) thick insulation over butt joint seams.