22
HDWA-SVX001D-EN
Figure 12.
Location of relief valves
Condenser
Pressure
Relief Valve
Evaporator
Pressure
Relief Valve
Con
den
ser
Evapo
rato
r
Relief valve connection sizes and locations are shown
in unit submittals. Refer to local codes for relief valve
vent line sizing information.
N
NO
OT
TIIC
CE
E
E
Eq
qu
uiip
pm
me
en
ntt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o cco
om
mp
plly
y w
wiitth
h ssp
pe
ecciiffiicca
attiio
on
nss m
ma
ay
y rre
essu
ulltt iin
n
cca
ap
pa
acciitty
y rre
ed
du
uccttiio
on
n,, u
un
niitt d
da
am
ma
ag
ge
e a
an
nd
d//o
orr rre
elliie
eff v
va
allv
ve
e
d
da
am
ma
ag
ge
e..
D
Do
o N
NO
OT
T e
ex
xcce
ee
ed
d v
ve
en
ntt p
piip
piin
ng
g cco
od
de
e ssp
pe
ecciiffiicca
attiio
on
nss!!
Relief valve discharge setpoints and capacities rates
are provided in the following table. After the relief
valve has opened, it will re-close when pressure is
reduced to a safe level.
N
No
otte
e:: After they are opened, relief valves may have
tendency to leak and must be replaced.
Pressure relief valve discharge capacities varies with
shell diameter and length and also compressor
displacement. Discharge venting capacity should be
calculated as required by ASHRAE Standard 15-94. Do
NOT adjust relief valve setting in the field.
Table 6. Pressure relief valve data
Valve Location
Discharge Setpoint
Rated Capacity
Field Connection Pipe Size
Factory Shell Side
Connection
psi
kPa
lb air/
min.
kg air/
min.
NPT
mm
in.
mm
Evaporator—
Compressor Low Side
Pipe (Suction)
200
1379.0
78.8
35.7
1-1/4
31.8
1-5/8 - 12
41.3 – 304.8
Condenser
300
2068.4
49.2
22.3
3/4
19.1
7/8 - 14
22.2 – 355.6