The packaged unit requires an air filter. The unit does
not come with a factory installed filter rack in it,
however, two filter frame accessories are offered that
will allow the installation of a filter within the unit,
BAYFLTR101 & BAYFLTR201. Otherwise a field
supplied filter rack must be installed by the installer in
the return duct work.
Affix the filter label supplied with the unit adjacent to
the filter area. Refer to table
to determine
filter size.
Table 8. Determine Filter Size
Unit
Nominal CFM
Filter Size
(Sq Ft)
Filter
(a)
Resistance
(W.C.)
YC~4024A
800
2.67
0.08
YC~4030A
1000
3.33
0.08
YC~4036A
1200
4
0.08
YC~4042A
1400
4.67
0.08
YC~4048A
1600
5.33
0.08
YC~4060A
2000
6.67
0.08
(a)
Filters must be installed in the return air system. The above square
footages are based on 300 F.P.M. face velocity. If permanent filters
are used, size per mfg. Recommendation with clear resistance of
0.05" WC.
IIm
mp
po
orrtta
an
ntt:: Air filters and media wheels or plates shall
meet the test requirements in UL 900
E
Elle
eccttrriicca
all W
Wiirriin
ng
g
N
No
otte
e:: This unit is factory wired for 230V. See wiring
diagram for 208V conversion.
E
Elle
eccttrriicca
all C
Co
on
nn
ne
eccttiio
on
nss
Electrical wiring and grounding must be installed in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code ANSI/NFPA 70,
Latest Revision.
E
Elle
eccttrriicca
all P
Po
ow
we
err
It is important that proper electrical power be available
for the unit. Voltage variation should remain within the
limits stamped on the unit nameplate.
D
Diisscco
on
nn
ne
ecctt S
Sw
wiittcch
h
Provide an approved weatherproof disconnect within
close proximity and w
wiitth
hiin
n ssiig
gh
htt o
off tth
he
e u
un
niitt..
O
Ov
ve
err C
Cu
urrrre
en
ntt P
Prro
otte
eccttiio
on
n
The branch circuit feeding the unit must be protected
as shown on the unit's rating plate.
P
Po
ow
we
err W
Wiirriin
ng
g
The power supply lines must be run in weather-tight
conduit to the disconnect and into the side of the unit
control box. Provide strain relief for all conduit with
suitable connectors.
Provide flexible conduit supports whenever vibration
transmission may cause a noise problem within the
building structure.
1. Remove the Control/Heat access panel. Pass the
power wires through the Power Entry hole in the
end of the unit.
2. Connect the high voltage wires to the appropriate
contactor terminals. Single phase units use a two
(2) pole contactor and three phase units use three
(3) pole contactor. Connect the ground to the
ground lug on the chassis.
Ensure all connections are tight.