88-4YCA4001-1A-EN

15

2. Clock the gas meter with the furnace operating

(determine the dial rating of the meter) for one
revolution.

3. Match the “Sec” column in the Gas Flow (in cfh)

Table 7, p. 15

with the time clocked.

4. Read the “Flow” column opposite the number of

seconds clocked.

5.

Table 7, p. 15

lists values for a 2 cubic foot dial. For

1, 1/2, or 5 Cu. Ft. dials use the following
conversions:

1 Cu. Ft. Dial Gas Flow CFH = Chart Flow
Reading / 2

1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow
Reading / 4

5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow
Reading / 4

6. Multiply the final figure by the heating value of the

gas obtained from the utility company and compare

to the nameplate rating. This must not exceed the
nameplate rating.

7. Changes can be made by adjusting the manifold

pressure.

a. Attach a manifold pressure gauge to the Outlet

Pressure Tap.

b. Remove the cover screw on top of the gas valve

to access the manifold pressure adjustment
screw.

c. Turn the adjustment screw in to increase the

gas flow rate, and out to decrease the gas flow
rate using a 3/32" hex wrench or flat-head
screwdriver.

N

No

otte

e:: For manifold pressures and orifice sizes for gas

with other BTU ratings, contact the local gas
utility. Manifold pressure should be 3.5 inches
water column (+ 0.1). Input for natural gas must
n

no

ott exceed the value shown on the rating plate.

Figure 10.

Burner and Valve

Regulator Cover Screw

(Adj. screw beneath 

 this screw)

Manual 

On-Off

Switch

Inlet 

Pressure

Tap

Vent Post

Outlet

Pressure Tap

REF. VIEW

(GAS VALVE)

Orifice

Burner

Manifold

Gas Valve

REF. VIEW

(3 Burners)

Table 7. Gas Flow (in cfh)

Sec.

Flow

Sec.

Flow

Sec.

Flow

Sec.

Flow

8

900

29

248

50

144

82

88

9

800

30

240

51

141

84

86

10

720

31

232

52

138

86

84

11

655

32

225

53

136

88

82

12

600

33

218

54

133

90

80

13

555

34

212

55

131

92

78

14

514

35

206

56

129

94

76

15

480

36

200

57

126

96

75

16

450

37

195

58

124

98

73

17

424

38

189

59

122

100

72

Table 7. Gas Flow (in cfh) (continued)

Sec.

Flow

Sec.

Flow

Sec.

Flow

Sec.

Flow

18

400

39

185

60

120

104

69

19

379

40

180

62

116

108

67

20

360

41

176

64

112

112

64

21

343

42

172

66

109

116

62

22

327

43

167

68

106

120

60

23

313

44

164

70

103

124

58

24

300

45

160

72

100

128

56

25

288

46

157

74

97

132

54

26

277

47

153

76

95

136

53

S

Stte

ep

p 4

4 —

— U

Un

niitt IIn

nsstta

alllla

attiio

on

n

Содержание 4YCA4024A1060A

Страница 1: ...uipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached t...

Страница 2: ...tr ri ic ca al l c cu ur rr re en nt t a ar re e g gr ro ou un nd de ed d I If f g gr ro ou un nd di in ng g w wi ir re es s s sc cr re ew ws s s st tr ra ap ps s c cl li ip ps s n nu ut ts s o or r...

Страница 3: ...Determine Unit Clearances 5 Step 3 Review Location and Recommendation Information 7 Step 4 Unit Installation 8 Step 5 Unit Startup 19 Sequence of Operation 21 Airflow Tables 23 Maintenance 25 Importan...

Страница 4: ...c ct t S Sh hi ip pm me en nt t 1 Check for damage after the unit is unloaded Report promptly to the carrier any damage found to the unit Do not drop the unit I Im mp po or rt ta an nt t To prevent da...

Страница 5: ...88 4YCA4001 1A EN 5 Step 2 Determine Unit Clearances Figure 1 Outline Drawing...

Страница 6: ...6 88 4YCA4001 1A EN Figure 2 Outline Drawing S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 7: ...serviceability maximum capacity and peak operating efficiency 2 Refer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assemb...

Страница 8: ...oof There must be a weatherproof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through exterior walls in accordance with local codes 7...

Страница 9: ...ure 4 Converting Horizontal to Down Airflow HORIZONTAL SUPPLY AIR COVER SHEET METAL SCREWS HORIZONTAL RETURN AIR COVER Figure 5 Lifting and Rigging Base of unit rest on top of curb r ails Drip lip on...

Страница 10: ...ta al ll la at ti io on n F Fr ra am me e M Mo ou un nt ti in ng g For rooftop applications using field fabricated frame and ducts use the following procedure 1 Prepare the hole in the roof in advanc...

Страница 11: ...and weatherproofed in accordance with local codes 11 Access and service clearances for the unit must be given careful consideration when locating the duct entrance openings Figures Step 2 Determine U...

Страница 12: ...w these guidelines for ductwork construction Connections to the unit should be made with three 3 inch canvas connectors to minimize noise and vibration transmission Elbows with turning vanes or splitt...

Страница 13: ...ol ll lo ow w t th he e s sa af fe et ty y w wa ar rn ni in ng g e ex xa ac ct tl ly y c co ou ul ld d r re es su ul lt t i in n s se er ri io ou us s i in nj ju ur ry y d de ea at th h o or r p pr r...

Страница 14: ...lt at pressures lower than 5 5 inches water column at the unit inlet If the supply line pressure is below the minimum supply pressure indicated on the unit nameplate contact the gas supply company Fol...

Страница 15: ...32 hex wrench or flat head screwdriver N No ot te e For manifold pressures and orifice sizes for gas with other BTU ratings contact the local gas utility Manifold pressure should be 3 5 inches water c...

Страница 16: ...on E El le ec ct tr ri ic ca al l C Co on nn ne ec ct ti io on ns s Electrical wiring and grounding must be installed in accordance with local codes or in the absence of local codes with the National...

Страница 17: ...supply agrees with equipment and heater nameplate 3 Low voltage wiring to be 18 AWG minimum conductor 4 The thermostat on the Gas Electric unit must provide a G signal in the cooling mode only During...

Страница 18: ...ring within the unit and make sure all connections are tight Replace and secure all electrical box covers and access panels before leaving the unit or turning on the power to the unit H Hi ig gh h A A...

Страница 19: ...t period of time install pressure gauges on the gauge ports of the discharge and suction line valves behind the Compressor access panel Check the suction and discharge pressures and compare them to th...

Страница 20: ...N No ot te e Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger This oil will burn off quickly 8 Set the th...

Страница 21: ...ignition has been achieved the delay to indoor fan on period begins timing and after approximately 45 seconds the indoor blower motor IDM will be energized and will continue to run during the heating...

Страница 22: ...hes High Limit switch protection device open Steady ON Normal Call for Heat 5 Flashes Flame sensed and gas valve not energized or flame sensed and no W signal 6 Flashes Flame Rollout Switch open 7 Fla...

Страница 23: ...47 255 263 270 277 283 289 294 Cooling High 0 CFM 1276 1229 1186 1137 1087 1039 994 950 913 874 WATTS 230 239 247 255 263 270 277 283 289 294 Heat Low 0 CFM 1116 1060 1006 950 898 849 805 760 723 668...

Страница 24: ...1408 1355 WATTS 483 499 514 528 543 557 568 583 592 601 Heat Low 0 CFM 1928 1876 1819 1764 1714 1660 1602 1543 1482 1437 WATTS 526 541 557 573 586 601 613 627 641 651 Heat High 0 CFM 1829 1769 1702 16...

Страница 25: ...ine these areas of the unit filters for cleaning or replacement motors and drive system components economizer gaskets for possible replacement safety controls for mechanical cleaning electrical compon...

Страница 26: ...26 88 4YCA4001 1A EN N No ot te es s...

Страница 27: ...88 4YCA4001 1A EN 27 N No ot te es s...

Страница 28: ...anstandardair com The AHRI Certified mark indicates company participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org The manufacturer h...

Отзывы: