ntt:: Do not lift the unit without test lifting for

balance and rigging. Do not lift the unit in
windy conditions or above personnel. Do
not lift the unit by attaching clevis, hooks,
pins, or bolts to the unit casing, casing
hardware, corner lugs, angles, tabs, or
flanges. Failure to observe these warnings
may result in equipment damage.

1. Before preparing the unit for lifting, check the unit

dimension drawings for center of gravity for lifting
safety (Figures

“Step 2 — Determine Unit

Clearances,” p. 5

). Because of placement of internal

components, the unit’s weight may be unevenly
distributed. Approximate unit weights are also
provided in the unit drawings.

N

No

otte

e:: Unit rigging and hoisting requires accessory kit

BAYLIFT002A. It includes a kit of four (4) lifting
lugs.

2. Insert the four lifting lugs in the openings provided

in the drip lip on each end of the unit. A tap or jerk
to the lug will overcome the interference that arises
due to the dimple on the lug.

3. When hoisting the unit, be sure that a proper

method of rigging is used. Use slings and spreader
bars for protection during lifting. Always test-lift the
unit to determine the exact unit balance and
stability before hoisting it to the installation
location.

4. When the curb and air ducts have been properly

installed, the unit is ready to be hoisted to the roof
and set in position.

IIm

mp

po

orrtta

an

ntt::

To prevent damage to the sides and top
of the unit when hoisting use “spreader
bars”.

The unit must be lowered into position.
The P.V.C. rubber tape on the curb
flange permits the unit to be
repositioned if required without
destroying the P.V.C. rubber seals
affixed to the mounting curb.

P

Plla

acciin

ng

g tth

he

e U

Un

niitt o

on

n tth

he

e M

Mo

ou

un

nttiin

ng

g C

Cu

urrb

b

1. The unit is designed with a perimeter drip lip that is

lower than the unit base pan.

2. Position the unit drip lip down over and in contact

with the outside corner of the curb. Continue to
lower the unit on top of the curb, with the unit drip
lip astraddle, and in contact with, both the end and
side rail of the curb. The unit should now rest on
top of the curb. Use the extreme mounting kit,
BAYEXMK001A, to add additional hold down
strength to the mounting.

R

Ro

oo

offtto

op

p IIn

nsstta

alllla

attiio

on

n —

— F

Frra

am

me

e M

Mo

ou

un

nttiin

ng

g

For rooftop applications using field fabricated frame
and ducts use the following procedure:

1. Prepare the hole in the roof in advance of installing

the unit.

2. Secure the horizontal or down airflow ducts to the

roof. Refer to the previous Convert from Horizontal
Airflow to Down Airflow section if conversion is
needed.

3. All fabricated outdoor ducts should be as short as

possible.

4. Place the unit on the frame.
5. The unit must be mounted level for proper drainage

of water through the holes in the base pan.

6. Secure the unit to the frame.
7. Insulate any ductwork outside of the structure with

at least two (2) inches of insulation and then
weatherproof. There must be a weatherproof seal
where the duct enters the structure.

8. The unit should not be exposed to direct roof water

runoff.

9. Flexible duct connectors must be of a flame

retardant material. All duct work outside of the
structure must be insulated and weatherproofed in
accordance with local codes.

10. Access and service clearances for the unit must be

given careful consideration when locating the duct
entrance openings. Figures

“Step 2 — Determine

Unit Clearances,” p. 5

provide unit dimensions.

11. Continue with the following installation sections to

complete the installation: Ductwork, Filter, and
Electrical Wiring.

R

Ro

oo

offtto

op

p IIn

nsstta

alllla

attiio

on

n —

— F

Frra

am

me

e M

Mo

ou

un

nttiin

ng

g

For roof top applications using field fabricated ducts
and sleeper rails rather than a curb or frame, use the
following procedure:

1. Locate and secure the sleeper rails to the roof by

bolting (three (3) rails required). One on each end to
support the edges of the unit and one across the
center of the unit. The center rail must run inside
both drip lips. Vibration isolators should be
installed, adjust as necessary for your sleeper rails.
The isolators must be placed on base pan, not drip
lip. Add flashing as required. Flashing must
conform to local building codes.

2. Prepare the hole in the roof in advance of installing

the unit.

3. Secure the horizontal or down airflow ducts to the

roof. Refer to the previous Convert from Horizontal
Airflow to Down Airflow section if conversion is
needed.

4. All fabricated outdoor ducts should be as short as

possible.

5. Place the unit on the rails.
6. The unit must be mounted level for proper drainage

of water through the holes in the base pan.

S

Stte

ep

p 4

4 —

— U

Un

niitt IIn

nsstta

alllla

attiio

on

n

Содержание 4YCA4024A1060A

Страница 1: ...uipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached t...

Страница 2: ...tr ri ic ca al l c cu ur rr re en nt t a ar re e g gr ro ou un nd de ed d I If f g gr ro ou un nd di in ng g w wi ir re es s s sc cr re ew ws s s st tr ra ap ps s c cl li ip ps s n nu ut ts s o or r...

Страница 3: ...Determine Unit Clearances 5 Step 3 Review Location and Recommendation Information 7 Step 4 Unit Installation 8 Step 5 Unit Startup 19 Sequence of Operation 21 Airflow Tables 23 Maintenance 25 Importan...

Страница 4: ...c ct t S Sh hi ip pm me en nt t 1 Check for damage after the unit is unloaded Report promptly to the carrier any damage found to the unit Do not drop the unit I Im mp po or rt ta an nt t To prevent da...

Страница 5: ...88 4YCA4001 1A EN 5 Step 2 Determine Unit Clearances Figure 1 Outline Drawing...

Страница 6: ...6 88 4YCA4001 1A EN Figure 2 Outline Drawing S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 7: ...serviceability maximum capacity and peak operating efficiency 2 Refer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assemb...

Страница 8: ...oof There must be a weatherproof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through exterior walls in accordance with local codes 7...

Страница 9: ...ure 4 Converting Horizontal to Down Airflow HORIZONTAL SUPPLY AIR COVER SHEET METAL SCREWS HORIZONTAL RETURN AIR COVER Figure 5 Lifting and Rigging Base of unit rest on top of curb r ails Drip lip on...

Страница 10: ...ta al ll la at ti io on n F Fr ra am me e M Mo ou un nt ti in ng g For rooftop applications using field fabricated frame and ducts use the following procedure 1 Prepare the hole in the roof in advanc...

Страница 11: ...and weatherproofed in accordance with local codes 11 Access and service clearances for the unit must be given careful consideration when locating the duct entrance openings Figures Step 2 Determine U...

Страница 12: ...w these guidelines for ductwork construction Connections to the unit should be made with three 3 inch canvas connectors to minimize noise and vibration transmission Elbows with turning vanes or splitt...

Страница 13: ...ol ll lo ow w t th he e s sa af fe et ty y w wa ar rn ni in ng g e ex xa ac ct tl ly y c co ou ul ld d r re es su ul lt t i in n s se er ri io ou us s i in nj ju ur ry y d de ea at th h o or r p pr r...

Страница 14: ...lt at pressures lower than 5 5 inches water column at the unit inlet If the supply line pressure is below the minimum supply pressure indicated on the unit nameplate contact the gas supply company Fol...

Страница 15: ...32 hex wrench or flat head screwdriver N No ot te e For manifold pressures and orifice sizes for gas with other BTU ratings contact the local gas utility Manifold pressure should be 3 5 inches water c...

Страница 16: ...on E El le ec ct tr ri ic ca al l C Co on nn ne ec ct ti io on ns s Electrical wiring and grounding must be installed in accordance with local codes or in the absence of local codes with the National...

Страница 17: ...supply agrees with equipment and heater nameplate 3 Low voltage wiring to be 18 AWG minimum conductor 4 The thermostat on the Gas Electric unit must provide a G signal in the cooling mode only During...

Страница 18: ...ring within the unit and make sure all connections are tight Replace and secure all electrical box covers and access panels before leaving the unit or turning on the power to the unit H Hi ig gh h A A...

Страница 19: ...t period of time install pressure gauges on the gauge ports of the discharge and suction line valves behind the Compressor access panel Check the suction and discharge pressures and compare them to th...

Страница 20: ...N No ot te e Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger This oil will burn off quickly 8 Set the th...

Страница 21: ...ignition has been achieved the delay to indoor fan on period begins timing and after approximately 45 seconds the indoor blower motor IDM will be energized and will continue to run during the heating...

Страница 22: ...hes High Limit switch protection device open Steady ON Normal Call for Heat 5 Flashes Flame sensed and gas valve not energized or flame sensed and no W signal 6 Flashes Flame Rollout Switch open 7 Fla...

Страница 23: ...47 255 263 270 277 283 289 294 Cooling High 0 CFM 1276 1229 1186 1137 1087 1039 994 950 913 874 WATTS 230 239 247 255 263 270 277 283 289 294 Heat Low 0 CFM 1116 1060 1006 950 898 849 805 760 723 668...

Страница 24: ...1408 1355 WATTS 483 499 514 528 543 557 568 583 592 601 Heat Low 0 CFM 1928 1876 1819 1764 1714 1660 1602 1543 1482 1437 WATTS 526 541 557 573 586 601 613 627 641 651 Heat High 0 CFM 1829 1769 1702 16...

Страница 25: ...ine these areas of the unit filters for cleaning or replacement motors and drive system components economizer gaskets for possible replacement safety controls for mechanical cleaning electrical compon...

Страница 26: ...26 88 4YCA4001 1A EN N No ot te es s...

Страница 27: ...88 4YCA4001 1A EN 27 N No ot te es s...

Страница 28: ...anstandardair com The AHRI Certified mark indicates company participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org The manufacturer h...

Отзывы: