6
General Data
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUH
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER (BTU/Watt-Hr.)
Sound Power Rating [dB(A)]
Performance Heating
(High Temp.)BTUH
Power Input (KW)
(Low Temp.) BTUH
Power Input (KW)
HSPF (BTU / Watt-Hr.)
POWER CONN.—V/Ph/Hz
Min. Brch. Cir. Ampacity
Fuse Size — Max. (amps)
Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz
R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Refrigerant Control
INDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Refrigerant Control
Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)
REFRIGERANT
Charge (lbs.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
4WCY4036B3000A
208-230/3/60
36000
1200
3.15
11.75 / 14.0
69
32400
2.7
24800
2.6
8.0
208-230/3/60
18.4
25
25
SCROLL
208-230/3/60
10.4 / 73
SPINE-FIN
2 / 24
15.49
3/8
EXPANSION VALVE
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
3250
1/5 / 830
230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
NO
THROWAWAY
4.0
R410A
7.4
H X W X L
47.86 / 44.5 / 52.03
468 / 372
4WCY4048B1000B
208-230/1/60
47500
1400
3.96
12.0 / 14.0
73
45000
3.77
28400
3.44
8.0
208-230/1/60
33.9
50
50
SCROLL
208-230/1/60
20.5 / 109
SPINE-FIN
2 / 24
18.01
3/8
EXPANSION VALVE
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
4440
1/4 / 825
230/1/60
1.4 / 3.37
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
NO
THROWAWAY
5.3
R410A
7.75
H X W X L
47.86 / 47.4 / 61.75
607 / 479
1
Certified in accordance with the Unitary Air-Conditioner Equipment
certification program, which is based on AHRI Standard 210/240.
2
Sound Power values are not adjusted for AHRI 270-95 tonal corrections.
3
Calculated in accordance with currently prevailing Nat'l Electrical Code.
4
Standard Air — Dry Coil — Outdoor.
5
Standard Air — Wet Coil — Indoor.
6
Rated in accordance with D.O.E. test procedure.
7
Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are
used size per manufacturer's recommendations with clean resistance of 0.05" W.C.
4WCY4042B1000A
208-230/1/60
42000
1380
3.50
12.0 / 14.0
74
38000
3.23
23400
2.96
8.0
208-230/1/60
30.6
45
45
SCROLL
208-230/1/60
17.9 / 112
SPINE-FIN
2 / 24
18.01
3/8
EXPANSION VALVE
PLATE FIN
3 / 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
4470
1/4 / 825
208-230/1/60
1.4 / 3.4
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
3/4 / VARIABLE
208-230/1/60
6.8 / 6.8
NO
THROWAWAY
5.3
R410A
8.2
H X W X L
47.86 / 47.4 / 61.75
607 / 479
Содержание 4WCY4024
Страница 9: ...9 Single Power Entry Kit Data Table 2 BAYSPEK060F Ampacity and Max Fusing Circuit Breakers...
Страница 10: ...10 Table 3 BAYSPEK061 Ampacity and Max Fusing Circuit Breakers Single Power Entry Kit Data...
Страница 11: ...11 Single Power Entry Kit Data Table 4 BAYSPEK062F 63F 64E 65E Ampacity and Max Fusing Circuit Breakers...
Страница 16: ...16 Typical Wiring...
Страница 17: ...17 Typical Wiring...
Страница 24: ...24 Dimensional Data and Weights 4WCY4024 through 4WCY4036 2 of 3...
Страница 25: ...25 Dimensional Data and Weights 4WCY4024 through 4WCY4036 3 of 3...
Страница 27: ...27 Dimensional Data and Weights 4WCY4042 through 4WCY4060 2 of 3...
Страница 28: ...28 Dimensional Data and Weights 4WCY4042 through 4WCY4060 3 of 3...