Mechanical Specifications

General
The units shall be horizontal airflow as 
shipped and convertible to downflow. All 
units shall be factory assembled, piped, 
internally wired and fully charged with 
refrigerant. All units shall be factory run 
tested to check cooling operation, fan and 
blower rotation and control or TXV se-
quence. Units shall be designed to operate 
at ambient temperatures between 115°F 
and 55°F in cooling as manufactured. 
Cooling performance shall be rated in ac-
cordance with A.H.R.I. standards.
Unit Casing
All components shall be mounted in a 
weather-resistant steel cabinet with an 
enamel finish. Access panels shall be pro-
vided for unit controls and indoor coil and 
fans. Indoor air section compartment shall 
be completely insulated with fireproof, 
permanent, odorless glass fiber material. 
Knockouts shall be provided for utility and 
control connections. Drain connections 
shall be provided to accommodate indoor 
water runoff.
Compressor
The compressor shall be hermetically 
sealed, high efficiency Climatuff

®

 com-

pressors. Internal overcurrent and over 
temperature protection, internal pressure 
relief shall be standard. 
Refrigeration System
All units shall have TXV in cooling and TXV 
in heating. Service pressure tap ports, and 
a refrigerant line filter dryer shall be stan-
dard.
Indoor Coil
Coils shall be internally finned or smooth 
bore 3/8" copper tubes mechanically 
bonded to configured aluminum plate 
fin as standard. Evaporator coil leak and 
pressure tested to 200 psig; condenser 
coil tested to 450 psig.

Condenser Coil — 
The Spine Fin™condenser coil shall be 
continuously wrapped, corrosion resis-
tant all aluminum with minimum brazed 
joints. This coil is 3/8 inch O.D. seamless 
aluminum tubing glued to a continuous 
aluminum fin. Coils are lab tested to 
withstand 2,000 pounds of pressure per 
square inch. The outdoor coil provides 
low airflow resistance and efficient heat 
transfer. The coil is protected on all four 
sides by louvered panels.
Indoor Air Fan — Direct-drive, forward-
curved, centrifugal wheel in a Composite 
Vortica

®

  Blower  housing. Motor shall 

have thermal overload protection. 
Permanently lubricated motor bearings. 
Motor/blower assembly isolated from unit 
with rubber mounts.
Condenser Fan — Direct-drive, draw 
thru propeller type. Weather-proofed 
permanent split capacitor fan motor shall 
have built-in thermal overload and per-
manently lubricated motor bearings.
System Controls
System controls include condenser fan, 
evaporator fan and compressor contac-
tors.
Accessories

Roof Curb — The roof curb shall be de-
signed to mate with the unit and provide 
support and complete weathertight instal-
lation when properly installed. Adhesive 
back polyurethane sealing strips shall be 
provided to ensure an airtight seal be-
tween supply and return openings of the 
curb and unit. The roof curb design allows 
field fabricated ductwork to be connected 
directly to the curb. Curb ships knocked 
down for field assembly, and includes 
factory-installed wood nailer strips.
Electric Heaters — Each heater assem-
bly shall include power supply fusing if 
over 48 amps, automatic resetting limit 
switches and heat limiters for thermal 
protection. Heaters shall be provided with 
polarized plugs for quick connection to 
unit low voltage wiring. Electric heat mod-
ules shall be UL listed.

Single Source Power Entry — This ac-
cessory when used with electric heat 
accessory shall allow single source power 
connection to unit and heater combina-
tion. Single source power entry kits shall 
have specific matching heater(s). Kit 
shall include high voltage terminal blocks, 
fuse blocks and fuses, cut-to-length in-
terconnecting wiring, and junction box (if 
required) to provide power sources with 
fuse protection as required for both the 
unit and accessory heater. Kit compo-
nents shall install within the unit cabinet in 
the heater access section. Single source 
branch power circuit shall be protected and 
wired in accordance with local codes.
Fully Modulating Economizer — This 
accessory shall be field installed and be 
composed of the following items: 0-100% 
fresh air damper, damper drive motor, fixed 
dry bulb enthalpy control, and low voltage 
wiring plug for electrical connections. Solid 
state enthalpy or differential enthalpy con-
trol is optional. Economizer operations 
shall be controlled by the preset position 
of the enthalpy control. A barometic relief 
damper shall be standard with the econo-
mizer and provide a pressure operated 
damper that shall be gravity closing and 
prohibit entrance of outside air on equip-
ment “off” cycle. Economizer requires 
BAYRLAY004A relay kit to interface the 
economizer to the heat pump.
Manual Outside Air Dampers — Rain 
hood and screen shall be field installed. 
Suitable for up to 25% outside air.
Start Kit — Extra compressor starting ca-
pacity for single phase equipment.
Control Options

Standard Indoor Thermostats — Two 
stage heating/cooling or one stage heat-
ing/cooling thermostats shall be available 
in either manual or automatic changeover.
Programmable Electronic Night Set-

back Thermostat — Programmable 
electronic thermostat shall provide heat-
ing setback and cooling setup with 7-day, 
programming capability. 1H/1C or 2H/2C 
models available.

Содержание 4WCY4024

Страница 1: ...2013 Trane Pub No 22 1789 19 Product Data 4WCY4024 through 4WCY4060 Single Packaged Convertible Heat Pump 14 SEER 2 5 Ton R 410A 22 1789 19...

Страница 2: ...are easy and versatile to install Because cooling and heating functions are all contained in a single cabinet a Trane packaged heat pump system is easy to install and service It can be flush mounted b...

Страница 3: ...Contents Optional Equipment Listing 4 General Data 5 Heater Data 8 SPEK Data 9 Performance Data Indoor Blower 12 Typical Wiring 16 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 2...

Страница 4: ...BAYADAP053A Adapter Curb 4WCY4042 060 to BAYCURB034 BAYADAP054A 12 Duct Shroud Covers Horizontal 4WCY4024 0607 BAYCOVR112A 18 Duct Shroud Covers Horizontal 4WCY4024 060 7 BAYCOVR118A Extreme Condition...

Страница 5: ...Net lbs 4WCY4030A1000B 208 230 1 60 30000 875 2 15 12 0 14 25 71 27600 2 15 15200 1 81 8 0 208 230 1 60 19 2 30 30 RECIPROCATING 200 230 1 60 11 1 63 SPINE FIN 2 24 13 32 3 8 EXPANSION VALVE PLATE FIN...

Страница 6: ...3 468 372 4WCY4048B1000B 208 230 1 60 47500 1400 3 96 12 0 14 0 73 45000 3 77 28400 3 44 8 0 208 230 1 60 33 9 50 50 SCROLL 208 230 1 60 20 5 109 SPINE FIN 2 24 18 01 3 8 EXPANSION VALVE PLATE FIN 3 1...

Страница 7: ...61 75 607 479 4WCY4060A3000C 208 230 3 60 58000 1780 4 95 11 5 14 0 76 55000 4 60 37600 4 29 8 0 208 230 3 60 28 6 45 45 SCROLL 208 230 3 60 16 0 110 SPINE FIN 2 24 23 57 3 8 EXPANSION VALVE PLATE FIN...

Страница 8: ...048 060 4 W TC 3060 4 WCZ6048 060 4 7 5 10 0 40 45 40 45 208 240 3 42 48 15 0 20 0 51200 68300 2 7 5 10 0 45 60 208 240 1 54 63 11 27 15 0 38500 51200 2 7 5 10 0 1 36 42 7 5 10 0 25600 34100 W TC 3036...

Страница 9: ...9 Single Power Entry Kit Data Table 2 BAYSPEK060F Ampacity and Max Fusing Circuit Breakers...

Страница 10: ...10 Table 3 BAYSPEK061 Ampacity and Max Fusing Circuit Breakers Single Power Entry Kit Data...

Страница 11: ...11 Single Power Entry Kit Data Table 4 BAYSPEK062F 63F 64E 65E Ampacity and Max Fusing Circuit Breakers...

Страница 12: ...10 816 813 803 794 800 846 450 CFM TON OFF OFF ON OFF Watts 86 102 127 156 185 213 242 275 319 CFM 884 870 882 899 909 907 895 886 898 Indoor Fan Performance 4WCY4030 4WCY4030 HOR DIPSWITCH SETTINGS E...

Страница 13: ...390 424 455 483 516 571 CFM 1391 1377 1377 1375 1366 1352 1344 1360 Indoor Fan Performance 4WCY4042 4WCY4042 HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0...

Страница 14: ...0 400 CFM TON OFF OFF OFF OFF Watts 302 349 386 423 465 509 552 583 599 628 CFM 1574 1580 1585 1589 1594 1598 1601 1597 1584 1556 450 CFM TON OFF OFF ON OFF Watts 501 523 555 592 631 672 714 760 800 8...

Страница 15: ...speed to provide improved comfort quietness and potential energy savings The Graph below shows the ramping process COOLING FAN DELAY OPTIONS SWITCH SETTINGS DELAY NOMINAL AIRFLOW OFF OFF 50 80 100 if...

Страница 16: ...16 Typical Wiring...

Страница 17: ...17 Typical Wiring...

Страница 18: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Страница 19: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Страница 20: ...s to construct build or modify the items depicted in the drawings The manufacturer is not respon sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resu...

Страница 21: ...ovide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manu facturer is not responsible for th...

Страница 22: ...ot responsible for the unauthorized use of these drawings and expressly disclaims any liability for dam ages resulting from such unauthorized use D C B A E Manual Fresh Air Model Unit Application Mode...

Страница 23: ...23 Dimensional Data and Weights 4WCY4024 through 4WCY4036 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 24: ...24 Dimensional Data and Weights 4WCY4024 through 4WCY4036 2 of 3...

Страница 25: ...25 Dimensional Data and Weights 4WCY4024 through 4WCY4036 3 of 3...

Страница 26: ...26 Dimensional Data and Weights 4WCY4042 through 4WCY4060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 27: ...27 Dimensional Data and Weights 4WCY4042 through 4WCY4060 2 of 3...

Страница 28: ...28 Dimensional Data and Weights 4WCY4042 through 4WCY4060 3 of 3...

Страница 29: ...tac tors Accessories Roof Curb The roof curb shall be de signed to mate with the unit and provide support and complete weathertight instal lation when properly installed Adhesive back polyurethane sea...

Страница 30: ...The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 90...

Отзывы: