13

Indoor Fan Performance 4WCY4036

Down Airflow

Horizontal Airflow

4WCY4036-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

162 

173 

197 

226 

256 

285 

313 

343 

360 

CFM 

1058 

1062 

1063 

1063 

1062 

1060 

1057 

1053 

1010 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

179 

230 

265 

296 

329 

366 

403 

431 

436 

CFM 

1179 

1196 

1204 

1206 

1205 

1203 

1199 

1194 

1185 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

318 

336 

365 

399 

435 

469 

502 

533 

CFM 

1390 

1376 

1370 

1366 

1361 

1354 

1349 

1351 

4WCY4036-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

169 

182 

210 

243 

273 

301 

331 

370 

433 

CFM 

1025 

1062 

1068 

1063 

1060 

1061 

1064 

1055 

1015 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

225 

253 

283 

315 

348 

381 

414 

449 

484 

CFM 

1187 

1201 

1203 

1201 

1198 

1197 

1194 

1184 

1157 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

339 

357 

390 

424 

455 

483 

516 

571 

CFM 

1391 

1377 

1377 

1375 

1366 

1352 

1344 

1360 

Indoor Fan Performance 4WCY4042

4WCY4042-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

181 

211 

241 

270 

298 

327 

355 

382 

408 

CFM 

1248 

1250 

1253 

1254 

1249 

1240 

1225 

1209 

1195 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

261 

296 

325 

352 

380 

411 

444 

477 

509 

CFM 

1444 

1448 

1441 

1429 

1417 

1407 

1400 

1394 

1386 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

353 

390 

426 

462 

499 

536 

573 

609 

645 

CFM 

1608 

1611 

1613 

1613 

1612 

1608 

1603 

1597 

1590 

4WCY4042-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

195 

229 

258 

283 

308 

335 

362 

390 

415 

CFM 

1240 

1244 

1245 

1243 

1238 

1229 

1217 

1203 

1189 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

289 

312 

341 

371 

402 

432 

461 

491 

523 

CFM 

1433 

1422 

1415 

1411 

1405 

1399 

1392 

1383 

1377 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

385 

422 

457 

491 

527 

563 

600 

636 

670 

CFM 

1604 

1602 

1600 

1598 

1596 

1593 

1590 

1585 

1578 

*Factory Default Setting

Down Airflow

Horizontal Airflow

Indoor Blower Performance

Содержание 4WCY4024

Страница 1: ...2013 Trane Pub No 22 1789 19 Product Data 4WCY4024 through 4WCY4060 Single Packaged Convertible Heat Pump 14 SEER 2 5 Ton R 410A 22 1789 19...

Страница 2: ...are easy and versatile to install Because cooling and heating functions are all contained in a single cabinet a Trane packaged heat pump system is easy to install and service It can be flush mounted b...

Страница 3: ...Contents Optional Equipment Listing 4 General Data 5 Heater Data 8 SPEK Data 9 Performance Data Indoor Blower 12 Typical Wiring 16 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 2...

Страница 4: ...BAYADAP053A Adapter Curb 4WCY4042 060 to BAYCURB034 BAYADAP054A 12 Duct Shroud Covers Horizontal 4WCY4024 0607 BAYCOVR112A 18 Duct Shroud Covers Horizontal 4WCY4024 060 7 BAYCOVR118A Extreme Condition...

Страница 5: ...Net lbs 4WCY4030A1000B 208 230 1 60 30000 875 2 15 12 0 14 25 71 27600 2 15 15200 1 81 8 0 208 230 1 60 19 2 30 30 RECIPROCATING 200 230 1 60 11 1 63 SPINE FIN 2 24 13 32 3 8 EXPANSION VALVE PLATE FIN...

Страница 6: ...3 468 372 4WCY4048B1000B 208 230 1 60 47500 1400 3 96 12 0 14 0 73 45000 3 77 28400 3 44 8 0 208 230 1 60 33 9 50 50 SCROLL 208 230 1 60 20 5 109 SPINE FIN 2 24 18 01 3 8 EXPANSION VALVE PLATE FIN 3 1...

Страница 7: ...61 75 607 479 4WCY4060A3000C 208 230 3 60 58000 1780 4 95 11 5 14 0 76 55000 4 60 37600 4 29 8 0 208 230 3 60 28 6 45 45 SCROLL 208 230 3 60 16 0 110 SPINE FIN 2 24 23 57 3 8 EXPANSION VALVE PLATE FIN...

Страница 8: ...048 060 4 W TC 3060 4 WCZ6048 060 4 7 5 10 0 40 45 40 45 208 240 3 42 48 15 0 20 0 51200 68300 2 7 5 10 0 45 60 208 240 1 54 63 11 27 15 0 38500 51200 2 7 5 10 0 1 36 42 7 5 10 0 25600 34100 W TC 3036...

Страница 9: ...9 Single Power Entry Kit Data Table 2 BAYSPEK060F Ampacity and Max Fusing Circuit Breakers...

Страница 10: ...10 Table 3 BAYSPEK061 Ampacity and Max Fusing Circuit Breakers Single Power Entry Kit Data...

Страница 11: ...11 Single Power Entry Kit Data Table 4 BAYSPEK062F 63F 64E 65E Ampacity and Max Fusing Circuit Breakers...

Страница 12: ...10 816 813 803 794 800 846 450 CFM TON OFF OFF ON OFF Watts 86 102 127 156 185 213 242 275 319 CFM 884 870 882 899 909 907 895 886 898 Indoor Fan Performance 4WCY4030 4WCY4030 HOR DIPSWITCH SETTINGS E...

Страница 13: ...390 424 455 483 516 571 CFM 1391 1377 1377 1375 1366 1352 1344 1360 Indoor Fan Performance 4WCY4042 4WCY4042 HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0...

Страница 14: ...0 400 CFM TON OFF OFF OFF OFF Watts 302 349 386 423 465 509 552 583 599 628 CFM 1574 1580 1585 1589 1594 1598 1601 1597 1584 1556 450 CFM TON OFF OFF ON OFF Watts 501 523 555 592 631 672 714 760 800 8...

Страница 15: ...speed to provide improved comfort quietness and potential energy savings The Graph below shows the ramping process COOLING FAN DELAY OPTIONS SWITCH SETTINGS DELAY NOMINAL AIRFLOW OFF OFF 50 80 100 if...

Страница 16: ...16 Typical Wiring...

Страница 17: ...17 Typical Wiring...

Страница 18: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Страница 19: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Страница 20: ...s to construct build or modify the items depicted in the drawings The manufacturer is not respon sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resu...

Страница 21: ...ovide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manu facturer is not responsible for th...

Страница 22: ...ot responsible for the unauthorized use of these drawings and expressly disclaims any liability for dam ages resulting from such unauthorized use D C B A E Manual Fresh Air Model Unit Application Mode...

Страница 23: ...23 Dimensional Data and Weights 4WCY4024 through 4WCY4036 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 24: ...24 Dimensional Data and Weights 4WCY4024 through 4WCY4036 2 of 3...

Страница 25: ...25 Dimensional Data and Weights 4WCY4024 through 4WCY4036 3 of 3...

Страница 26: ...26 Dimensional Data and Weights 4WCY4042 through 4WCY4060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 27: ...27 Dimensional Data and Weights 4WCY4042 through 4WCY4060 2 of 3...

Страница 28: ...28 Dimensional Data and Weights 4WCY4042 through 4WCY4060 3 of 3...

Страница 29: ...tac tors Accessories Roof Curb The roof curb shall be de signed to mate with the unit and provide support and complete weathertight instal lation when properly installed Adhesive back polyurethane sea...

Страница 30: ...The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 90...

Отзывы: