59
The drainpipe can be lifted 450mm.
When the down gradient of the drainpipe can't be ensured,
after upright lifting, the drainpipe is in the down slope.
The attached hoses can be used to adjust the eccentricity
and angle of the hard PVC tube.
• Stretch the hose directly to make connections as to avoid
distortion. The soft end of the hose should be positioned
with a clamp.
Heat Insulating Treatment:
• Wrap the connection between the clamp and the
root segment of the indoor unit without any gap with
heat insulating materials as shown in the drawing
Lifting Drainpipe
Confirming Drainage
Hose
1.5m~2m support bracket
heat
insulating
material
down gradient
over 1/100
s-shape
elbow
as big as possible (about 10 CM)
down gradient
over 1/100
VP30
•
The hose should be used in the horizon direction.
45°bending (max.)
45°
eccentricity adjustment (max.20mm)
20
indoor unit
hose
hose
hose clamp
hose clamp
Hose
Hose clamp
PVC pipe
Rigid PVC adhesive
Water outlet
100mm
below
lifting
450mm below
lifting 600mm below
under the ceiling
drain connection
injection nozzle
Hose
Hose clamp
PVC pipe
Rigid PVC adhesive
Water outlet
100mm
below
lifting
450mm below
lifting 600mm below
under the ceiling
drain connection
injection nozzle