124
After oil return in cooling mode, the quit condition of refrigerant eliminated:
1 minute later after oil return is over
&
Td Tc
‐
>
30
℃
OR
OR Ts Tc2AVE
‐
>
30
℃
Tc2AVE
<
35
‐
℃
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return:
Max. 9 minutes (E)
OR
OR
Td Tc
‐
<
20
℃
for 30s continuously(5 minutes later, begin
to count)
&
Ts Tc2AVE
‐
<
15
℃
for 30s continuously(5 minutes later,
begin to count)
Running for min. 5 minutes(E)
Send oil return signal
oil return begins
oil return over
Inverter compressor
indicated FQCY
60s
oil return FQCY
60s
soft startup
0HZ
0HZ
5s
Outdoor motor
AUTO
AUTO
AUTO (TC control)
4-way valve
ON
OFF
15s
450pulse
450pulse
350pulse(E)
All expansion valves
auto angle
auto angle
All indoors
ON
OFF
anti-freezed startup
Содержание 4TXM2318BF300AA