BAS-SVX36C-EN
29
Configuration
0220 Heat pump
compressor
lockout
point
(5)
0
0
None
15
15° F (–9.5° C)
20
20° F (–6.5° C)
25
25° F (–4.0° C)
30
30° F (–1.0° C)
35
35° F (1.5° C)
40
40° F (4.5° C)
45
45° F (7.0° C)
0221 Heat pump aux
lockout point
0
0
None
40
40° F (4.5° C)
45
45° F (7.0° C)
50
50° F (10.0° C)
55
55° F (13.0° C)
60
60° F (15.5° C)
0230 Temp occupied
duration
limit
for
TOV override
3
0
0 hours
(
Note:
TOV function is still available)
1
1 hour
2
2 hours
3
3 hours
4
4 hours
0231 Number of
periods
2
2
Two scheduling periods per day
4
Four scheduling periods per day
0232 Period occupied/
unoccupied
definitions
4
If Option #0231 is set to 2:
Day
Night
0
Unoccupied
Unoccupied
1
Unoccupied
Occupied
2
Unoccupied
Unoccupied
3
Unoccupied
Occupied
4
Occupied
Unoccupied
5
Occupied
Occupied
6
Occupied
Unoccupied
7
Occupied
Occupied
8
Unoccupied
Unoccupied
9
Unoccupied
Occupied
10
Unoccupied
Unoccupied
11
Unoccupied
Occupied
12
Occupied
Unoccupied
13
Occupied
Occupied
14
Occupied
Unoccupied
15
Occupied
Occupied
If Option #0231 is set to 4:
Morning
Day
Evening
Night
0
Unoccupied
Unoccupied
Unoccupied
Unoccupied
1
Unoccupied
Unoccupied
Unoccupied
Occupied
2
Unoccupied
Unoccupied
Occupied
Unoccupied
3
Unoccupied
Unoccupied
Occupied
Occupied
4
Unoccupied
Occupied
Unoccupied
Unoccupied
5
Unoccupied
Occupied
Unoccupied
Occupied
6
Unoccupied
Occupied
Occupied
Unoccupied
7
Unoccupied
Occupied
Occupied
Occupied
8
Unoccupied
Unoccupied
Unoccupied
Unoccupied
9
Occupied
Unoccupied
Unoccupied
Occupied
10
Occupied
Unoccupied
Occupied
Unoccupied
11
Occupied
Unoccupied
Occupied
Occupied
12
Occupied
Occupied
Unoccupied
Unoccupied
13
Occupied
Occupied
Unoccupied
Occupied
14
Occupied
Occupied
Occupied
Unoccupied
15
Occupied
Occupied
Occupied
Occupied
Table 6.
Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No.
Name
Default
Opts. Descriptions