BAS-SVX36C-EN
Configuration
0140 Schedule options
1
0
Non-programmable
1
Programmable
0150 TOD/Economizer
output
(terminal
A)
0
0
Unused
1
TOD energizes terminal A during occupied period, not during
unoccupied
period.
2
Economizer energizes terminal A during a call for cool
0151 Heat fan
operation
0
0
System controls fan
1
Thermostat controls fan
0153 Reversing value
O/B
0
0
O/B terminal energized in cooling
1
O/B terminal energized in heating
0160 CPH 1st stage
compressor
(2)
3
1-5
Cycles per hour for 1st stage compressor - only for systems with cool or heat
pump stage - also changes 2nd stage cool default CPH
0161 CPH 2nd stage
compressor
(2)
3
1-5
Cycles per hour for 2nd stage compressor - only for systems with two cool or
heat pump stages
0162 CPH 1st stage
conventional
heat
(2)
5
1-10
Cycles per hour for 1st stage conventional heat - only for systems with heat
stages - also changes 2nd stage heat default CPH
0163 CPH 2nd stage
conventional
heat
(2)
9
1-10
Cycles per hour for 2nd stage conventional heat - only for systems with two
conventional heat stages
0164 CPH for auxiliary
heat
(2)
9
1-10
Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
0165 CPH for
emergency
heat
(2)
9
1-10
Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages
0170 Continuous
backlight
0
0
Backlight “ON” time is limited
1
Backlight does not turn off
0180 Changeover
1
0
Manual changeover (heat/cool/off) - manually changeover the thermostat
between heat, cool, and off
1
Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
0181 Deadband
(3)
3
2
2° F (1° C)
3
3° F (1.5° C)
4
4° F (2.0° C)
5
5° F (2.5° C)
6
6° F (3.0° C)
7
7° F (3.5° C)
8
8° F (4.0° C)
9
9° F (4.5° C)
0182 Minimum
compressor off
time
5
0-5
Minutes for compressor off time - for systems with cool or heat pump stages
- (Minutes specified here are added to the 5 min base off time.)
0190 Power supply
frequency
0
0
60Hz
1
50 Hz
0210 Temperature
sensor
selection
0
0
Internal for H/C - display can show only local temperature and setpoint
1
Internal for H/C - remote (connected to S1 & S2)
(4)
for display - display can
show local and remote temperature, and setpoint
2
Internal for H/C, remote (connected to S1 & S2)
(4)
for compressor and
auxiliary lockout; display can show local and remote temperature, and
setpoint - (Disabled for conventional systems.)
3
Remote (connected to S1 & S2)
(4)
for H/C, internal disabled; display can show
remote indoor temperature and setpoint
Table 6.
Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No.
Name
Default
Opts. Descriptions