background image

29

The evaporator is large enough to
hold all the charge, for any unit,
below the centerline of the shell.
Therefore, no special precautions are
required to restart the unit after
isolating the charge in the
evaporator.

Filter Replacement
Procedure

A dirty filter is indicated by a
temperature gradient across the
filter, corresponding to a pressure
drop. If the temperature downstream
of the filter is 8°F [4.4°C] lower than
the upstream temperature, the filter
should be replaced. A temperature
drop can also indicate that the unit is
undercharged. Ensure proper
subcooling before taking
temperature readings.
1. With the unit off, verify that the

EXV is closed. Close the liquid-line
isolation valve. On units with
remote evaporators or oil cooling
circuits, close the ball valve on the
oil cooler liquid line.

2. Attach the vacuum hose to the

service port on the liquid-line filter
flange.

3. Evacuate the refrigerant from the

liquid-line and store.

4. Remove the vacuum hose.

5. Depress the Schrader valve to

equalize pressure in the liquid line
with atmospheric pressure.

6. Remove the bolts that retain the

filter flange.

7. Remove the old filter element.

8. Inspect the replacement filter

element and lubricate the o-ring
with Trane  OIL00048.

C

CA

AU

UT

TIIO

ON

N

Do not use mineral oil. It will
contaminate the system.

9. Install the new filter element in the

filter housing.

10. Inspect the flange gasket and

replace it with a new one if
damaged.

11. Install the flange and torque the

bolts to 14-16 lb-ft [19-22 n-m].

12. Attach the vacuum hose and

evacuate the liquid line.

13. Remove the vacuum hose from

the liquid line and attach the
charging hose.

14. Replace the stored charge in the

liquid line.

15. Remove the charging hose.

16. Open the liquid-line isolation

valve. On units with remote
evaporators or oil cooler circuits,
open the oil cooler liquid-line ball
valve.

Lubrication System

The lubrication system has been
designed to keep most of the oil
lines filled with oil as long as there is
a proper oil level in the oil sump. The
total oil charge can be removed by
draining the oil system, the oil return
line from the evaporator, the
evaporator, and the compressor. Very
small quantities of oil may be found
in other components.

Oil Charging Procedure

Proper charging of the oil system is
critical to the reliability of the
compressor and chiller. Too little oil
can cause the compressor to run hot
and inefficiently. When taken to an
extreme, low oil level may result in
infant failure of the compressor. Too
much oil will result in high oil-
circulation rates, which will foul the
condenser and evaporator
performance. This will result in
inefficient operation of the chiller.
Taken to an extreme, high oil levels
may result in erratic expansion-valve
control or shut down of the chiller
due to low evaporator-refrigerant
temperature. Too much oil may
contribute to long-term bearing
wear. Additionally, excessive
compressor wear is probable when
the compressor is started with the oil
lines dry. Oil system consists of the
following components:

• Compressor

• Oil separator

• Discharge line with service valve

• Oil line from separator to

compressor

• Oil line drain (lowest point in

system)

• Oil cooler

• Oil temperature sensor

• Oil line shutoff valve with flare

service connection

• Oil filter (internal to compressor)

with flare-fitting service connection
and Schrader valve

• Oil flow-control valve (internal to

the compressor after the filter)

• Oil return line from evaporator with

shutoff valve, strainer, and solenoid
control valve. The standard oil
charge for each circuit size is shown
in Table  1.

Measuring the oil level

1. To measure the oil level, use the

oil drain valve on the oil line and a
service valve on the discharge line.
This measurement can only be
made when the circuit is not
running. Note: the bottom plate of
the oil separator is approximately
1" [25 mm] thick.

2. The initial oil charge should be

approximately at the level as
shown in Table 6. This is the
approximate oil level if all the oil is
in the oil lines, filter, and oil sump,
and the unit is in vacuum so that
there is no refrigerant dissolved in
the oil.

3. After the unit has run for a while,

the oil level in the sump can vary
greatly. 

The field-charging procedure
depends on the circumstances that
resulted in the need for oil charge. 
1. Some service procedures may

result in loss of small quantities of
oil that must be replaced (oil
analysis, compressor filter
replacement, re-tubing the
evaporator, and so forth). 

2. Additionally, some maintenance

procedures may result in virtually
all of the oil being removed
(compressor motor burn or total
removal of the charge to trouble-
shoot a unit). 

3. Finally, leaks may result in a loss

of oil that must be replaced.

Maintenance

RLC-SVX03A-E4

Содержание 108-216

Страница 1: ...Installation Operation Maintenance RTUB 207 224 Liquid chillers with helical rotary compressors RTCA 108 216 Remote air cooled condenser RLC SVX03A E4...

Страница 2: ...delivery note and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery Notify the localTrane Sales Office at the same time The unit should be totally inspe...

Страница 3: ...a RTCA 8 Installation Installation Responsibilities 9 Storage 9 Special Lifting and Moving Instructions 10 Isolation 10 Foundation 10 Clearances 11 Drainage 12 Releasing the Nitrogen Holding Charge 12...

Страница 4: ...Temporary Shutdown and Restart 23 Extended Shutdown Procedure 23 System Restart after Extended Shutdown 23 Maintenance Periodic Maintenance 25 Refrigerant and Oil Charge Management 27 R134a Field char...

Страница 5: ...ane Sales Office Do not proceed with installation of a damaged unit without sales office approval Inspection Checklist To protect against loss due to damage incurred in transit complete the following...

Страница 6: ...l for shipment Description of the Unit The RTUB units are liquid chillers equipped with two helical rotary compressors and an evaporator designed to operate with remote RTCA air cooled condensers or o...

Страница 7: ...ng Weight kg 2130 2130 2845 2845 2845 3250 Shipping Weight kg 1860 1860 2570 2570 2570 2975 Unit size 216 217 218 220 222 224 Compressor Type Quantity Helical rotary 2 Nominal size tons 70 85 85 85 10...

Страница 8: ...8 1 5 8 1 5 8 Liquid connection inches 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 Unit size 208 209 211 213 215 216 Condenser Condenser type Aluminium fins copper tubes Fin spacing fins ft 168 168 144 168 16...

Страница 9: ...for RTUB Furnish and install strainers ahead of all pumps and automatic modulating valves Furnish and install check valves on the discharge lines between oil separators and condenser in order to avoi...

Страница 10: ...e sound transmitted through water piping To reduce the sound transmitted through electrical conduit use flexible electrical conduit State and local codes on sound emissions should always be considered...

Страница 11: ...igure 5 andTable 4 for unit Figure 5 Unit Dimensions and Recommended Minimum Clearances RTCA Figure 6 Unit Dimensions and Recommended Minimum Clearances RTUB A C D B A C D B Table 4 Unit Dimensions an...

Страница 12: ...n transmission through the water lines If desired install thermometers in the lines to monitor entering and leaving water temperatures Install a balancing valve in the leaving water line to control wa...

Страница 13: ...tween the water and system components Foreign matter in the chilled water system can also increase pressure drop and consequently reduce water flow Proper water treatment must be determined locally de...

Страница 14: ...es for relief valve installation guidelines Installing and connecting temperature sensors General Recommendations Regardless of the type of monitoring sensor required by a particular application the s...

Страница 15: ...ambient temperature and condenser temperature sensors must be connected to the RTUB to monitor it The ambient temperature sensor must be installed in a position which represents most accurately the c...

Страница 16: ...its each with its own ventilation The ventilation cannot be common to the two circuits For this type of installation non RTCA condenser an On Off signal is available on the unit control module UCM of...

Страница 17: ...commended to place a trap on the discharge line at the oil separator outlet if this discharge line is horizontal for a distance greater than 5 m at a height greater than the connection to the oil sepa...

Страница 18: ...n the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops The height of the liquid line in relation to the condenser base must be less than 5 m Legen...

Страница 19: ...uction line using the following criteria 1 2 5 m s minimum in the horizontal parts 2 5 0 m s minimum in the vertical parts 3 Maximum speed 20 m s The minimum slope of the suction line to the condenser...

Страница 20: ...ent manometer must be installed upstream of the vacuum pump stop valve 1 Close valve B and open valve A After a few minutes the manometer reading indicated the lowest vacuum level that can be obtained...

Страница 21: ...f untreated or improperly treated water or saline or brackish water Close the fused disconnect switch es that supplies power to the chilled water pump starter Start the chilled water pump to begin cir...

Страница 22: ...ions prior to start up have been performed see previous sections the unit is ready to start Press the Stop key on the UCM CLD If necessary adjust the setpoint values in the UCM CLD reports refer to th...

Страница 23: ...ain glycol to prevent any risk of evaporator freeze up Extended period shutdown The procedure below must be performed if the system has to be stopped for a prolonged period for example seasonal shutdo...

Страница 24: ...Flow Rates and Water System Pressure Drop 7 Adjust the flow switch on the evaporator piping for proper operation 8 Stop the water pump The unit is now ready for startup as described in Startup Proced...

Страница 25: ...even more if conditions are very poor or if corrosion damage begins to occur To clean the coils use a soft brush and a sprayer garden pump up type A high quality detergent such as Trane Coil Cleaner...

Страница 26: ...ser 2 After the compressor stops close the compressor discharge valve and disconnect the unit Note Do not make successive vacuums by using the compressor Irreversible compressor damage could occur 3 V...

Страница 27: ...line due to high vapor velocity High Condenser Subcooler Pressure drop Some symptoms of a refrigerant over charged unit High subcooling Larger than normal condenser approach temperatures Entering Con...

Страница 28: ...tenance on the compressor or high side It is much more preferable to isolate the charge in the evaporator if this option is available High side charge isolation procedure 1 Make sure the circuit is of...

Страница 29: ...he oil system is critical to the reliability of the compressor and chiller Too little oil can cause the compressor to run hot and inefficiently When taken to an extreme low oil level may result in inf...

Страница 30: ...s than 15 minutes If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes However reduce the amount of oil added to the unit by the norm...

Страница 31: ...tainer or is otherwise contaminated then this small volume must be subject to vacuum as well However the filter cavity is full of oil Therefore be sure to use a flash tank in line with the vacuum pump...

Страница 32: ...stem should be carried out only by qualified and experienced personnel Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency This contract...

Отзывы: