11
Installation
condensation coils must be
protected from side winds when
their speed exceeds 16 km/h.
Position the unit above the average
height of snow observed in the
region where it is installed. Never
install temporary or permanent
objects (tarp or roof) over the unit,
because recycling of hot air would
reduce the capacity of the
condensation coils. Discharged air
from the fans must not be
obstructed. It is prohibited to install
ducts for the fan discharge air (even
short ones). This is because the fans
supplied on standard units do not
generate any additional static
pressure.
Clearances
Provide enough space around the
unit to allow the installation and
maintenance personnel unrestricted
access to all service points. Refer to
Figure 5 and Table 4 for unit
Figure 5: Unit Dimensions and
Recommended Minimum
Clearances - RTCA
Figure 6: Unit Dimensions and
Recommended Minimum
Clearances - RTUB
A
C
D
B
A
C
D
B
Table 4 - Unit Dimensions and Recommended Minimum Clearances (mm)
Length
Width
Height
A
B
C
D
RTCA 108/109/111/208/209/211
2870
2285
1630
1000
1000
1000
1000
RTCA 113/213
4610
2285
1630
1000
1000
1000
1000
RTCA 115/116/215/216
5450
2285
1630
1000
1000
1000
1000
RTUB 207/208
2880
890
1789
950
800
1800
500
RTUB 210/211/212/214/216/217
4150
890
1832
950
800
2750
500
RTUB 218/220
4150
890
1932
950
800
2750
500
RTUB 222/224
4150
890
2041
950
800
2750
500
dimensions and recommended
clearances. Unobstructed flow of
condenser air is essential to maintain
chiller capacity and operating
efficiency.
Note for RTCA: When determining
unit placement, give careful
consideration to ensuring a sufficient
flow of air across the condenser
heat-transfer surface.
RLC-SVX03A-E4