background image

21

Pre-start checkout

Installation Checklist

When installation is complete, but
prior to putting the unit into service,
the following pre-start procedures
must be reviewed and verified:

• Inspect all wiring connections to be

sure they are clean and tight.

W

WA

AR

RN

NIIN

NG

G

Disconnect all electric power,
including remote disconnects, before
servicing. Failure to disconnect
power before servicing can cause
severe personal injury or death.

C

CA

AU

UT

TIIO

ON

N

• Check the tightness of all

connections in the compressor
power circuit (disconnects, terminal
block, contactors, compressor
junction box terminals,…). Loose
connections can cause overheating
at the connections and
undervoltage conditions at the
compressor motor.

• Open all refrigerant valves in the

discharge, liquid, oil, and oil return
lines.

C

CA

AU

UT

TIIO

ON

N

Do not operate the unit with the
compressor, oil discharge, liquid-line
service valves, or the manual shutoff
on the refrigerant supply to the
auxiliary coolers "CLOSED." Failure
to have these "OPEN" may cause
serious compressor damage.

• Check the power-supply voltage to

the unit at the main-power fused-
disconnect switch. Voltage must be
within the voltage utilization range
and also stamped on the unit
nameplate. Voltage imbalance must
not exceed 2%.

• Check the unit power phasing L1-

L2-L3 in the starter to ensure that it
has been installed in an "A B-C"
phase sequence.

C

CA

AU

UT

TIIO

ON

N

Improper power phasing can result
in equipment damage due to reverse
rotation.

Do not use untreated or improperly-
treated water. Equipment damage
may occur.

• Fill the evaporator chilled-water

circuit. Vent the system while it is
being filled. Open the vents on the
top of the evaporator water box
while filling and close when filling
is completed.

The use of improperly-treated or
untreated water in this equipment
may result in scaling, erosion,
corrosion, algae, or slime. The
services of a qualified water-
treatment specialist should be
engaged to determine what
treatment, if any, is advisable. Trane's
warranty specifically excludes
liability of corrosion, erosion, or
deterioration of Trane equipment.
Trane assumes no responsibilities for
the results of the use of untreated or
improperly-treated water, or saline or
brackish water.

• Close the fused-disconnect

switch(es) that supplies power to
the chilled-water pump starter.

• Start the chilled-water pump to

begin circulation of the water.
Inspect all piping for leakage and
make any necessary repairs.

• With water circulating through the

system, adjust the water flow and
check the water pressure drop
through the evaporator.

• Adjust the chilled-water flow switch

for proper operation.

W

WA

AR

RN

NIIN

NG

G

Use extreme caution when
performing the following procedure
with power applied. Failure to do so
can result in personal injury or
death.

• Reapply power to complete the

procedures.

• Prove all Interlock and

Interconnecting Wiring  Interlock
and External as described in the
Installation section.

• Check and set, as required, all

UCM-CLD menu items.

• Stop the chilled-water pump.

• Energize the compressor and oil

separators 24 hours prior to unit
startup.

Unit Voltage  Power  Supply

Voltage to the unit must meet the
criteria given in the Installation
section. Measure each leg of the
supply voltage at the main power
fused-disconnect switch for the unit.
If the measured voltage on any leg is
not within the specified range, notify
the supplier of the power and correct
the situation before operating the
unit.

C

CA

AU

UT

TIIO

ON

N

Provide adequate voltage to the unit.
Failure to do so can cause control
components to malfunction and
shorten the life of relay contact,
compressor motors and contactors.

Unit Voltage  Imbalance 

Excessive voltage imbalance
between the phases of a three-phase
system can cause motors to
overheat and eventually fail. The
maximum allowable imbalance is
2%. Voltage imbalance is determined
using the following calculations:

% Imbalance = [(Vx - V ave) x 100]/V
ave

V ave = (V1 + V2 + V3)/3

Vx = phase with the greatest
difference from V ave (without
regard to the sign)

For example, if the three measured
voltages are 391, 407, and 402 volts,
the average would be:

(391+407+402)/3 = 400

The percentage of the imbalance is
then:

[100(400-391)]/400 = 2.25%

This exceeds the maximum
allowable (2%) by 0.25%

Unit Voltage  Phasing

It is imperative that L1, L2, and L3 in
the starter be connected in the A-B-C
phase sequence to prevent
equipment damage due to reverse
rotation.

It is important that proper rotation of
the compressors be established
before the unit is started. Proper

Operation

RLC-SVX03A-E4

Содержание 108-216

Страница 1: ...Installation Operation Maintenance RTUB 207 224 Liquid chillers with helical rotary compressors RTCA 108 216 Remote air cooled condenser RLC SVX03A E4...

Страница 2: ...delivery note and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery Notify the localTrane Sales Office at the same time The unit should be totally inspe...

Страница 3: ...a RTCA 8 Installation Installation Responsibilities 9 Storage 9 Special Lifting and Moving Instructions 10 Isolation 10 Foundation 10 Clearances 11 Drainage 12 Releasing the Nitrogen Holding Charge 12...

Страница 4: ...Temporary Shutdown and Restart 23 Extended Shutdown Procedure 23 System Restart after Extended Shutdown 23 Maintenance Periodic Maintenance 25 Refrigerant and Oil Charge Management 27 R134a Field char...

Страница 5: ...ane Sales Office Do not proceed with installation of a damaged unit without sales office approval Inspection Checklist To protect against loss due to damage incurred in transit complete the following...

Страница 6: ...l for shipment Description of the Unit The RTUB units are liquid chillers equipped with two helical rotary compressors and an evaporator designed to operate with remote RTCA air cooled condensers or o...

Страница 7: ...ng Weight kg 2130 2130 2845 2845 2845 3250 Shipping Weight kg 1860 1860 2570 2570 2570 2975 Unit size 216 217 218 220 222 224 Compressor Type Quantity Helical rotary 2 Nominal size tons 70 85 85 85 10...

Страница 8: ...8 1 5 8 1 5 8 Liquid connection inches 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 Unit size 208 209 211 213 215 216 Condenser Condenser type Aluminium fins copper tubes Fin spacing fins ft 168 168 144 168 16...

Страница 9: ...for RTUB Furnish and install strainers ahead of all pumps and automatic modulating valves Furnish and install check valves on the discharge lines between oil separators and condenser in order to avoi...

Страница 10: ...e sound transmitted through water piping To reduce the sound transmitted through electrical conduit use flexible electrical conduit State and local codes on sound emissions should always be considered...

Страница 11: ...igure 5 andTable 4 for unit Figure 5 Unit Dimensions and Recommended Minimum Clearances RTCA Figure 6 Unit Dimensions and Recommended Minimum Clearances RTUB A C D B A C D B Table 4 Unit Dimensions an...

Страница 12: ...n transmission through the water lines If desired install thermometers in the lines to monitor entering and leaving water temperatures Install a balancing valve in the leaving water line to control wa...

Страница 13: ...tween the water and system components Foreign matter in the chilled water system can also increase pressure drop and consequently reduce water flow Proper water treatment must be determined locally de...

Страница 14: ...es for relief valve installation guidelines Installing and connecting temperature sensors General Recommendations Regardless of the type of monitoring sensor required by a particular application the s...

Страница 15: ...ambient temperature and condenser temperature sensors must be connected to the RTUB to monitor it The ambient temperature sensor must be installed in a position which represents most accurately the c...

Страница 16: ...its each with its own ventilation The ventilation cannot be common to the two circuits For this type of installation non RTCA condenser an On Off signal is available on the unit control module UCM of...

Страница 17: ...commended to place a trap on the discharge line at the oil separator outlet if this discharge line is horizontal for a distance greater than 5 m at a height greater than the connection to the oil sepa...

Страница 18: ...n the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops The height of the liquid line in relation to the condenser base must be less than 5 m Legen...

Страница 19: ...uction line using the following criteria 1 2 5 m s minimum in the horizontal parts 2 5 0 m s minimum in the vertical parts 3 Maximum speed 20 m s The minimum slope of the suction line to the condenser...

Страница 20: ...ent manometer must be installed upstream of the vacuum pump stop valve 1 Close valve B and open valve A After a few minutes the manometer reading indicated the lowest vacuum level that can be obtained...

Страница 21: ...f untreated or improperly treated water or saline or brackish water Close the fused disconnect switch es that supplies power to the chilled water pump starter Start the chilled water pump to begin cir...

Страница 22: ...ions prior to start up have been performed see previous sections the unit is ready to start Press the Stop key on the UCM CLD If necessary adjust the setpoint values in the UCM CLD reports refer to th...

Страница 23: ...ain glycol to prevent any risk of evaporator freeze up Extended period shutdown The procedure below must be performed if the system has to be stopped for a prolonged period for example seasonal shutdo...

Страница 24: ...Flow Rates and Water System Pressure Drop 7 Adjust the flow switch on the evaporator piping for proper operation 8 Stop the water pump The unit is now ready for startup as described in Startup Proced...

Страница 25: ...even more if conditions are very poor or if corrosion damage begins to occur To clean the coils use a soft brush and a sprayer garden pump up type A high quality detergent such as Trane Coil Cleaner...

Страница 26: ...ser 2 After the compressor stops close the compressor discharge valve and disconnect the unit Note Do not make successive vacuums by using the compressor Irreversible compressor damage could occur 3 V...

Страница 27: ...line due to high vapor velocity High Condenser Subcooler Pressure drop Some symptoms of a refrigerant over charged unit High subcooling Larger than normal condenser approach temperatures Entering Con...

Страница 28: ...tenance on the compressor or high side It is much more preferable to isolate the charge in the evaporator if this option is available High side charge isolation procedure 1 Make sure the circuit is of...

Страница 29: ...he oil system is critical to the reliability of the compressor and chiller Too little oil can cause the compressor to run hot and inefficiently When taken to an extreme low oil level may result in inf...

Страница 30: ...s than 15 minutes If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes However reduce the amount of oil added to the unit by the norm...

Страница 31: ...tainer or is otherwise contaminated then this small volume must be subject to vacuum as well However the filter cavity is full of oil Therefore be sure to use a flash tank in line with the vacuum pump...

Страница 32: ...stem should be carried out only by qualified and experienced personnel Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency This contract...

Отзывы: