background image

23

operating load. Overheating may
vary slightly on the circuit if the
system load is lower, when the slide
valve is moving.

Overheating must stabilize at
approximately 4°C when the above
components have stabilized.

Subcooling

Normal subcooling for each circuit
ranges from 8-10°C, depending on
the units. If subcooling for either
circuit does not fall within these
values, check the overheating for the
circuit and adjust if necessary. If
overheating is normal but
subcooling is not, contact a qualified
service technician.

Seasonal Unit Start-up

1. Close all valves and reinstall the

drain plugs in the evaporator.

2. Service the auxiliary equipment

according to the startup and
maintenance instructions provided
by the respective equipment
manufacturers.

3. Close the vents in the evaporator

chilled-water circuits.

4. Open all the valves in the

evaporator chilled-water circuits.

5. Open all refrigerant valves to

verify they are in the open
condition.

6. If the evaporator was previously

drained, vent and fill the
evaporator and chilled-water
circuit. When all air is removed
from the system (including each
pass), install the vent plugs in the
evaporator water boxes.

C

CA

AU

UT

TIIO

ON

N

Ensure that the compressor and oil-
separator heaters have been
operating for a minimum of 24 hours
before starting. Failure to do so may
result in equipment damage.

7. Check the adjustment and

operation of each safety and
operating control.

8. Close all disconnect switches.

9. Refer to the sequence for daily

unit startup for the remainder of
the seasonal startup.

Shutdown procedures

Temporary Shutdown and Restart

To shut the unit down for a short
time, use the following procedure:

1. Press the Stop key on the UCM-

CLD. The  compressors  will
continue to operate and, after
unloading for 20 seconds, will stop
when the compressor contactor
de-energizes.

2) Stop the water circulation by

disconnecting the power supply to
the chilled water and cooling
water pumps.

C

CA

AU

UT

TIIO

ON

N

Under freezing conditions, the chilled
water pump must remain in
operation during the full shutdown
period of the chiller if the chilled
water loop does not contain glycol,
to prevent any risk of evaporator
freeze-up.

Extended period shutdown

The procedure below must be
performed if the system has to be
stopped for a prolonged period, for
example seasonal shutdown.

1. Test the unit for refrigerant leakage

and repair as necessary.

2. Open the electrical disconnect

switches for the chilled-water
pump. Lock the switches in the
"Open" position.

C

CA

AU

UT

TIIO

ON

N

Lock the chilled-water pump
disconnects open to prevent pump
damage.

3. Close all chilled-water supply

valves. Drain the water from the
evaporator.

4. Open the unit main electrical

disconnect and unit-mounted
disconnect (if installed) and lock in
the "Open" position. If the optional
control-power transformer is not
installed, open and lock the 115 V
disconnect.

C

CA

AU

UT

TIIO

ON

N

Lock the disconnects in the "Open"
position to prevent accidental startup

Operation

and damage to the system when it
has been set up for extended
shutdown.

5. At least every three months

(quarterly), check the refrigerant
pressure in the unit to verify that
the refrigerant charge is intact.

C

CA

AU

UT

TIIO

ON

N

During an extended shutdown
period, especially over the winter
season, the evaporator must be
drained of water, if the chilled water
loop does not contain glycol, to
prevent any risk of evaporator freeze-
up.

System Restart After Extended
Shutdown

1. Verify that the liquid-line service

valves, oil line, compressor
discharge service valves, and
suction service valves are open
(backseated).

C

CA

AU

UT

TIIO

ON

N

To prevent damage to the
compressor, ensure that all
refrigerant valves are open before
starting the unit.

2. Check the oil separator oil level

(see Maintenance section).

3. Fill the evaporator water circuit.

Vent the system while it is being
filled. Open the vent on the top of
the evaporator and condenser
while filling, and close it when
filling is completed.

C

CA

AU

UT

TIIO

ON

N

Do not use untreated or improperly
treated water. Equipment damage
may occur.
4. Close the fused-disconnect

switches that provide power to the
chilled-water pump.

5. Start the evaporator water pump

and, while water is circulating,
inspect all piping for leakage.
Make any necessary repairs before
starting the unit.

6. While the water is circulating,

adjust the water flows and check
the water pressure drops through
the evaporator. Refer to "Water-

RLC-SVX03A-E4

Содержание 108-216

Страница 1: ...Installation Operation Maintenance RTUB 207 224 Liquid chillers with helical rotary compressors RTCA 108 216 Remote air cooled condenser RLC SVX03A E4...

Страница 2: ...delivery note and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery Notify the localTrane Sales Office at the same time The unit should be totally inspe...

Страница 3: ...a RTCA 8 Installation Installation Responsibilities 9 Storage 9 Special Lifting and Moving Instructions 10 Isolation 10 Foundation 10 Clearances 11 Drainage 12 Releasing the Nitrogen Holding Charge 12...

Страница 4: ...Temporary Shutdown and Restart 23 Extended Shutdown Procedure 23 System Restart after Extended Shutdown 23 Maintenance Periodic Maintenance 25 Refrigerant and Oil Charge Management 27 R134a Field char...

Страница 5: ...ane Sales Office Do not proceed with installation of a damaged unit without sales office approval Inspection Checklist To protect against loss due to damage incurred in transit complete the following...

Страница 6: ...l for shipment Description of the Unit The RTUB units are liquid chillers equipped with two helical rotary compressors and an evaporator designed to operate with remote RTCA air cooled condensers or o...

Страница 7: ...ng Weight kg 2130 2130 2845 2845 2845 3250 Shipping Weight kg 1860 1860 2570 2570 2570 2975 Unit size 216 217 218 220 222 224 Compressor Type Quantity Helical rotary 2 Nominal size tons 70 85 85 85 10...

Страница 8: ...8 1 5 8 1 5 8 Liquid connection inches 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 Unit size 208 209 211 213 215 216 Condenser Condenser type Aluminium fins copper tubes Fin spacing fins ft 168 168 144 168 16...

Страница 9: ...for RTUB Furnish and install strainers ahead of all pumps and automatic modulating valves Furnish and install check valves on the discharge lines between oil separators and condenser in order to avoi...

Страница 10: ...e sound transmitted through water piping To reduce the sound transmitted through electrical conduit use flexible electrical conduit State and local codes on sound emissions should always be considered...

Страница 11: ...igure 5 andTable 4 for unit Figure 5 Unit Dimensions and Recommended Minimum Clearances RTCA Figure 6 Unit Dimensions and Recommended Minimum Clearances RTUB A C D B A C D B Table 4 Unit Dimensions an...

Страница 12: ...n transmission through the water lines If desired install thermometers in the lines to monitor entering and leaving water temperatures Install a balancing valve in the leaving water line to control wa...

Страница 13: ...tween the water and system components Foreign matter in the chilled water system can also increase pressure drop and consequently reduce water flow Proper water treatment must be determined locally de...

Страница 14: ...es for relief valve installation guidelines Installing and connecting temperature sensors General Recommendations Regardless of the type of monitoring sensor required by a particular application the s...

Страница 15: ...ambient temperature and condenser temperature sensors must be connected to the RTUB to monitor it The ambient temperature sensor must be installed in a position which represents most accurately the c...

Страница 16: ...its each with its own ventilation The ventilation cannot be common to the two circuits For this type of installation non RTCA condenser an On Off signal is available on the unit control module UCM of...

Страница 17: ...commended to place a trap on the discharge line at the oil separator outlet if this discharge line is horizontal for a distance greater than 5 m at a height greater than the connection to the oil sepa...

Страница 18: ...n the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops The height of the liquid line in relation to the condenser base must be less than 5 m Legen...

Страница 19: ...uction line using the following criteria 1 2 5 m s minimum in the horizontal parts 2 5 0 m s minimum in the vertical parts 3 Maximum speed 20 m s The minimum slope of the suction line to the condenser...

Страница 20: ...ent manometer must be installed upstream of the vacuum pump stop valve 1 Close valve B and open valve A After a few minutes the manometer reading indicated the lowest vacuum level that can be obtained...

Страница 21: ...f untreated or improperly treated water or saline or brackish water Close the fused disconnect switch es that supplies power to the chilled water pump starter Start the chilled water pump to begin cir...

Страница 22: ...ions prior to start up have been performed see previous sections the unit is ready to start Press the Stop key on the UCM CLD If necessary adjust the setpoint values in the UCM CLD reports refer to th...

Страница 23: ...ain glycol to prevent any risk of evaporator freeze up Extended period shutdown The procedure below must be performed if the system has to be stopped for a prolonged period for example seasonal shutdo...

Страница 24: ...Flow Rates and Water System Pressure Drop 7 Adjust the flow switch on the evaporator piping for proper operation 8 Stop the water pump The unit is now ready for startup as described in Startup Proced...

Страница 25: ...even more if conditions are very poor or if corrosion damage begins to occur To clean the coils use a soft brush and a sprayer garden pump up type A high quality detergent such as Trane Coil Cleaner...

Страница 26: ...ser 2 After the compressor stops close the compressor discharge valve and disconnect the unit Note Do not make successive vacuums by using the compressor Irreversible compressor damage could occur 3 V...

Страница 27: ...line due to high vapor velocity High Condenser Subcooler Pressure drop Some symptoms of a refrigerant over charged unit High subcooling Larger than normal condenser approach temperatures Entering Con...

Страница 28: ...tenance on the compressor or high side It is much more preferable to isolate the charge in the evaporator if this option is available High side charge isolation procedure 1 Make sure the circuit is of...

Страница 29: ...he oil system is critical to the reliability of the compressor and chiller Too little oil can cause the compressor to run hot and inefficiently When taken to an extreme low oil level may result in inf...

Страница 30: ...s than 15 minutes If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes However reduce the amount of oil added to the unit by the norm...

Страница 31: ...tainer or is otherwise contaminated then this small volume must be subject to vacuum as well However the filter cavity is full of oil Therefore be sure to use a flash tank in line with the vacuum pump...

Страница 32: ...stem should be carried out only by qualified and experienced personnel Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency This contract...

Отзывы: