MD1064 Rev. F
13 of 32
The PRI150 requires two wires from the field. Figure 7 shows an extract from Tracerco
Document DD23870 detailing the PRI150 wiring. Attention is drawn to the requirement for
an internal connection between terminals 1 and 3 on the PRI150. Without this connection
the device will fail to communicate with the Optimus™ control module.
Figure 7. PRI150 connections.
A HART 4-20mA repeater power supply is required to provide both power and isolation to
the PRI150 radiation detector. Tracerco recommends the use of the MTL 5541 module to
provide this functionality. A HART 4-20mA repeater power supply is required for each
PRI150 radiation detector in the system.
There is a safe area connection to the Optimus™
control module. Table 1 details the connections of the MTL 5541 barrier.
Terminal
Description
1
I OUT (Connect to Pin 1 of PRI150)
2
+ VE (Connect to Pin 2 of PRI150)
3
-VE (Not used)
10
Current VE via 220Ω resistor (Not used during normal operation)
11
Current Output
–
VE (To T221)
12
Current VE (To T221)
13
Power Input
–
VE
14
Power Input +VE (24Vdc)
Table 1. MTL5541 connections.