– 89 –
Concealed Duct High Static Pressure
Installation Manual
Concealed Duct High Static Pressure
Installation Manual
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
3400
3200
3800
4200
4600
5000 5200
3360
3600
4000
4400
4800
5040
5
50
100
150
200
250
300
350
Standard air volume: 4200m³/h
High static pressure tap (50Hz)
Low static pressure tap (50Hz)
Current of fan motor (A)
External static pressure (Pa)
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Air volume (m³/h)
Low static pressure tap (50Hz)
Lower limit of air volume
Upper limit of air volume
Medium static pressure tap (50Hz)
4
4.5
5
5.5
6
6.5
7
7.5
8
3000
2800
3400
3800
4200
4400
2880
3200
3600
4000
4320
5
50
100
150
200
250
300
Standard air volume: 3600m³/h
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Low static pressure tap (50Hz)
Current of fan motor (A)
External static pressure (Pa)
Medium static pressure tap (50Hz)
Air volume (m³/h)
High static pressure tap (50Hz)
Low static pressure tap (50Hz)
Lower limit of air volume
Upper limit of air volume
5
FAN CHARACTERISTICS
Current value as a criterion, adjust the air volume value to become within the range of the chart below.
<RAV-SM2242 Type>
<RAV-SM2802 Type>
REQUIREMENT
Add a air volume damper to the air supply duct, and adjust the air volume in the range from 80% to 120% of the standard
air volume.