– 69 –
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Group address
Individual
: 0000
Header unit : 0001
Follower unit : 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address
→
1
Indoor unit address
→
1
Group address
→
1
2
1
2
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
10-3. Address Setup (Manual Setting from Remote Controller)
1
Push
SET
+
CL
+
TEST
buttons simultaneously
for 4 seconds or more.
2
(
←
←
←
←
←
Line address)
Using the temperature setup
/
buttons,
set
12
to the CODE No.
3
Using timer time / buttons, set the line address.
4
Push
SET
button.
(OK when display goes on.)
5
(
←
←
←
←
←
Indoor unit address)
Using the temperature setup
/
buttons, set
13
to the CODE No.
6
Using timer time / buttons, set 1 to the line address.
7
Push
SET
button.
(OK when display goes on.)
8
(
←
←
←
←
←
Group address)
Using the temperature setup
/
buttons, set
14
to the CODE No.
9
Using timer time / buttons, set
0000
to Individual,
0001
to Master unit, and
0002
to sub unit.
10
Push
SET
button.
(OK when display goes on.)
11
Push
TEST
button.
Setup completes. (The status returns to the usual stop status.)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.