46 °F (8 °C) operation
Before test run
Execute a test run
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
• Before turning on the power supply, carry out the
following procedure.
1) By using 500V-megger, check that resistanceof
1MΩ or more exists between the terminal block
1 to 3 and the earth (grounding).
If resistance of less than 1MΩ is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner’s Manual.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
Push the [
CANCEL] button to return.
SET DATA
46 °F (8 °C) Operation setting
0000
None
(Factory default)
0001
46 °F (8 °C) Operation setting
9
Test run
Do not use the forced test run for cases other than
the test run because it applies an excessive load to
the devices.
CAUTION
Item
Function
1. Test mode
Settings for when performing
the test operation after
installation
2. Register service info
Registration of information
about the contact number for
service, model name and
serial number of the indoor unit
and outdoor unit
3. Alarm history
List of latest 10 alarm data:
information of check code, date,
time, and unit
4. Monitor function
Monitoring data of sensor
temperature, rotating speed of
the compressor or other factor.
5. Setting louver
position
Change the louver indication
setting to match the indoor unit
type.
6. Setting timer
operation mode
Set whether or not the
operation mode can be selected
when setting the schedule timer.
7. DN setting
Advanced settings using
DN code
Push the [
CANCEL] button to return.
� 23 �
45-EN
46-EN
Push the [
˄
] / [
˅
] button to select
“DN setting” on the “Field setting menu”
screen, then push the “
Set”
[ F2] button.
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
Specify CODE No. [D1]
Move the cursor to select “Code(DN)” with the
“
˂ ” [ F1] button, then set
“Code(DN)” with the [
˄
] / [
˅ ]button.
Move the cursor to select “Data” with the
“
>” [
F2] button, then set “Data”
with the [
˄ ] / [
˅] button.